ADE Accenta G3 Intruder System
|
|
Bookmark ADE Accenta G3 Intruder System |
About ADE Accenta G3 Intruder SystemHere you can find all about ADE Accenta G3 Intruder System like manual and other informations. For example: review.
ADE Accenta G3 Intruder System manual (user guide) is ready to download for free.
On the bottom of page users can write a review. If you own a ADE Accenta G3 Intruder System please write about it to help other people. [ Report abuse or wrong photo | Share your ADE Accenta G3 Intruder System photo ]
Manual
Preview of first few manual pages (at low quality). Check before download. Click to enlarge.
Download
(English)ADE Accenta G3 Intruder System, size: 115 KB |
ADE Accenta G3 Intruder System
User reviews and opinions
| emanuele.gissi |
3:03pm on Tuesday, May 11th, 2010 ![]() |
| Love both the silicone case and zebra sleeve pouch. This product is EXACTLY what I wanted. It fits perfectly and it got here very fast. The item was all that the description said it would be! I am very pleased with this product and would recommend it to friends. | |
| tinez |
1:57am on Sunday, April 4th, 2010 ![]() |
| I came into Vanns on a whim on the iPads launch day not really expecting to see any there still available. I replaced my first-gen iPod Touch, which I had since they first came out a few years ago, with this new beast of a device. First of all. | |
Comments posted on www.ps2netdrivers.net are solely the views and opinions of the people posting them and do not necessarily reflect the views or opinions of us.
Documents
b. Fixing
Board There are four fuses mounted on the circuit Fit the panel to the wall with suitable fixings. Ensure the wall surface is flat to board, all are 20mm quick blow. F1 1.6A - to protect the +ve line of 12V battery prevent base distortion. There are cable entry holes provided in the rear F2 1A - to protect the RKP 13V supply of the base and around the outside F3 1A - to protect the Speaker 13V supply edges through the thinned out plastic F5 1A - to protect the Bell and Strobe supply sections which may be cut away as required. As supplied, wire links are fitted across the PA The hole provided adjacent to the and Tamper terminals to represent a closed mains transformer is a dedicated mains circuit. cable entry point.
Communicator is not fitted to Optima compact G3 panel
L/FAIL +13V 0V FIRE PA ABORT CONF INT SET
Keypad and LEDs (except Power LED) are not fitted to Accenta G3 and Accenta mini G3 panels
RKP FUSE
D6 D7 D8 D9 D10
1A SOUND COMMS +13V 0V
VOLUME
13V / SPEAKER BELL/STROBE
BATTERY
F1 J4 + BATT AC
J8 PA +
TAMP +13V 0V -
J6 + T A
STROBE
Factory fitted links
A combination of up to four remote keypads and lighting controller can be connected to the panel.
Wiring the system
Caution: Always power-down the panel when wiring external circuits, to prevent damage to the panel electronics.
Systematically wire and test each circuits.:
Security zones
Panel Board
Zone, Tamper circuit and PA circuits
Finish by wiring any additional extension speaker sounders, external bell/sounder, strobe and the 13V supply.
TAMP +13V 0V
Terminal block is not supplied
Tamper network
The Tamper circuit is used to protect all cables and detectors in the system from unauthorised access including the panel and RKP covers. The zone and PA tampers should be series wired and connected to the TAMP terminals. Terminals T & A are for the external bell / sounder tamper. The TAMP terminals at the bottom left of the PCB are for the RKP tampers. Tamper alarms that occur in the Day mode operate internal sounders only. Tamper alarms in Set cause a full alarm condition. Tamper is indicated on the control panel and RKPs by the Tamper indicator.
Door Contact
Connect Remote Keypads / Lighting controllers
Note: Where an Accenta G3 or Accenta mini G3 panel is being installed ensure there is at least one remote keypad wired to the panel before first power up.
OPTI-CAM Lighting Controller Board
COMMS SOUND LD R
GND 12V
Note: The G3 range of panels are not supplied with wire links for unused zones. All unused zones must be programmed out by setting them to disabled using the Zone Type function see page 19.
It is recommended that no more than 10 magnetic contacts are connected to the same zone.
Keypad Board
COMMS SOUND
F2 SOUND COMMS +13V 0V
Maximum of up to 4 Remote Keypad / OPTI-CAM Lighting Controller combination allowed (See also the instructions supplied with the OPTI CAM lighting controller)
If only one Remote keypad is being used then connect TAMP back to the panel
Unused zones must be programmed as Unused.
would have to be momentarily turned to its Set position then returned to its Unset position. The keyswitch will always Set program 1. It will also Unset the system or switch off an alarm activation. To Reset after an alarm and return to Day mode, the Reset key on the RKP will have to be pressed.
Push to set zone
Any zone can be wired and configured as a Push to Set input. This can be a standard door bell push located outside the premises After starting the exit timer the building is vacated. As the switch is then momentaraily closed, a chime tone is produced and the system Sets. Sometimes referred to as Terminate Set this facility is mandatory for communicating systems installed to NACOSS guidelines
Fire zone
Any zone may be programmed as a fire zone. This will automatically exclude the availability of the zone from programs and normal security applications.
Press to Set Switch
Note: The push to set switch can be connected to any zone. The zone must be programmed for PTS application.
Fire detector
Remote keyswitch zone
Any zone can be wired and programmed as a keyswitch input and used with a remote keyswitch or lock switch. For security reasons it is recommended that a tamper proof switch is used and that the switch wiring is not accessible from outside the premises.
Note: Fire detector with relay base for output to intruder system.
There are two types of fire zone, Standard and 24 hour type. The Standard fire zone detects fires only when the system is Set, where as the 24 hour fire zone detects fires all the time and will operate whether the system is Set or Unset. A fire will cause a distinctive internal sounder tone. The external sounders will pulse on and off at 2 second intervals and all RKP indicators will flash the affected zone.
Keyswitch Note: A keyswitch can be connected to any zone. The zone must be programmed for keyswitch application.
PA circuit
Any quantity of normally closed type personal attack button may be wired in series and then connected to the PA circuit. Operational in Day and Set, the PA circuit will cause a full alarm condition when activated. PA is indicated on the control panel or RKP as Attack.
The keyswitch may be used to Set (open contacts) or Unset (closed contacts) independently of RKPs. However in this situation the keyswitch may have to catch up with the system. For example if the system is Set via an RKP and Unset with the keyswitch, it
A control marked VOLUME in the centre of the PCB may be used to adjust the low volume entry/exit tones to suit environmental conditions. To adjust this control, partially lift up the top cover.
Bell Output (External sounder)
Panic Button
The bell is usually installed in a high position from where the bell could be seen and heard. Terminal T A D B are for connection to the external bell or sounder. These terminals provide a power/hold-off supply, sounder trigger and tamper circuit to protect the external sounder housing.
BELL/STROBE
PA buttons may be fitted near the front door, or in a bedroom.
Extension speaker
Extension speaker may be connected to the loudspeaker terminals to produce high volume alarm tones and low volume entry / exit fault tones.
13VSPEAKER
+ STROBE
16 W Extension Speaker
Sonade
Up to two 16 ohm extension speakers may also be wired across the speaker terminals. Mounted in convenient positions within the installation the extension speakers will reproduce all of the alarm tones generated by the control panel.
The terminals are summarised as follows: T-Ve tamper return A-Ve supply (0V) D+Ve supply (12V) B-Ve Sounder trigger For ease of installation, ADE sounders and modules use the same markings. Where a discrete bell sounder is used, it should be connected to terminals D & B. Terminals T &
A are then used for tamper protection for the sounder housing.
Remote signalling Input and Outputs
These outputs are not applicable to the Optima compact G3 panel.
# Terminal block is not supplied
These terminals have been provided for connection to remote signalling equipment such as a digital communicator, Red Care STU or speech dialler.
+ STROBE T E A D B + STROBE T E A D B
Note: The operating polarity of the Communicator output terminals are programmable.
L/FAIL This is a telephone line fail input which is held at approximately 6V by the panel circuitry. The input is activated when pulled to 0V by the telephone line fault output of the communicator. This is usually a voltage free relay or open collector transistor. When a telephone line fault occurs in the Day mode the panel provides an audible double beep every 10 minutes. This indication is automatically cleared when the fault is removed. A telephone line fault which occurs while the system is Set will not cause an alarm condition but any bell delay which is programmed will be cancelled and any intruder alarm which is triggered will operate instant sounders. 13V 0V These terminals provide a 13V supply for the communicator up to a total load of 200mA. The output is protected by a 250mA thermal fuse. If this fuse operates it may be reset by removing the load and allowing a few seconds for it to recover. OUTPUT PORT By default these outputs are programmed as active low output. They are held at 13V and fall to 0V when active, it can source or sink 10mA. The output polarity can be programmed.
Filtering of Intruder alarms
A condition of most police Force Policies and under the guidance of NACOSS NACP 14 (Code of Practice for intruder Alarm Systems Signalling to Alarm Receiving Centres) is that all intruder alarm signals received by an Alarm Receiving Centre (ARC) must be filtered to establish their validity before passing to the police. The exact method of filtering should be decided according to the regional Police Force Policy and ARC procedures. In general, the panels offer the following methods which could be used to filter an alarm. Set/Unset A Set or Unset signal which is received by the ARC at around the same time as an intruder signal can be used to filter the alarm. Abort Output The abort output operates whenever a user code is entered or a keyswitch is used to switch off an intruder alarm condition. When an abort signal is received by ARC at or around the same time as an intruder signal, the alarm can be filtered. Restore of the Intruder Output The intruder alarm output is restored to 12V whenever a user code is entered or a keyswitch is used to switch off an intruder alarm condition. Where an intruder alarm is shortly followed by a restore at the ARC, this can be used to filter the alarm.
Factory set condition
User code 1 - User code 2 - Duress Code - Engineer Code Bell Duration Bell Delay - Program 1 Zone 1 - - Zone 2 - - Zones 38 Exit time- Entry - - Exit mode Factory set condition Program 2 Zone1 - - Zone 2 - - Zone 38 Exit time- Entry time Exit mode Program 3 Zone 1 - Zone 2 - Zone38 Exit timeEntry time Exit mode 0123 Not programmed Not programmed minutes No delay Flag A Silent PA - - - - - - RKP PA Enable - - - Engineer Reset- - - - Anti Code Reset - - - Door bell on push to set Single key setting - - Strobe on setting - - - External bell on Fire - Flag B No Yes No No No No No No
Timed Time Inhibited Immediate 30seconds 30seconds timed
Note: The entries marked # are not applicable for Optima compact G3 panel.
#Communicator Output active high - - - - - #Line Fail active high - - - - - User Reset PA - - - User Reset Fire - - - #Program 1 to report #Program 2 to report #Program 3 to report Rearm counter - - - Service counter - - - Site Code - - - - - - Light Controller Light Threshold Light Hold Time Light Channel 1 Light Channel 2 Light Channel 3 Light Channel 4 Light Channel 5 Light Channel 6 Light Channel 7 Light Channel 8 - - - - No (active low) No (active low) No No Yes Yes Yes 3 (re-arms) Off 00
Timed Time inhibited Immediate 30seconds 30seconds Disabled
Timed Time Inhibited Immediate 30seconds 30seconds Disabled Zones 18 None programmed None programmed None programmed None programmed None programmed None programmed 300mS ALL zones
Security Zones - - - Standard Fire zones 24 hour Fire zones - Push to set zones - - Keyswitch zones - - Double Knock zones Omit prevent zones- Zone debounce period
50% 30 seconds No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned
Engineering information Note: The G3 range of panels are not supplied with wire links for unused zones. All unused zones must be programmed out by setting them to disabled using the Zone Type function see page 19.
First Power up
Before power up for Optima compact only - fit the top cover on to the base and connect the speaker wires. Leave the cover in position throughout the reset of the installation. a. Check that the factory fitted links are connected to terminals PA, TAMP and T-A. Fit the battery wires to the BATT terminals on the PCB, Red to + and Black to -.
Mains Connection
The mains power should be connected using a 3 core cable of not less than 0.75mm sq. from a fused spur to the mains connector inside the control panel. The 2 Amp fused spur must be located close to the control panel.
Dedicated mains supply from consumer unit. 2A Fused Spur unit
J4 + BATT AC
(red) +
Black BATTERY
N E L 125mA Fuse
12V battery Transformer
+ BATT
On connecting the battery the system will now go into alarm condition and Tamper is indicated
Tamper
Black -
and there is an audible
12V battery
Transformer
Alarm. indication. Fit the cover to hold down the tamper spring at the bottom centre of the PCB.
Enter the user code: (factory set at 0123). The alarm condition will cease and the system will go to Day mode. Immediately enter the engineer code
Note: The mains supply must be connected by a technically competent person and according to current IEE regulations. CAUTION: To avoid the risk of electrical shock you must always totally isolate the mains supply before opening the control panel cover(s).
. The system is now in Engineer program mode and can be programmed. Note the
Mains Input Fuse rating: 125mA, 250V type T (anti surge) and of a type approved to IEC 127 part 2 sheet III. On connecting the mains supply to the panel the power indicator is lit.
Tamper indicator is lit.
Testing the system
Complete the wiring of the system and then:
System indications
Day Power
- Unset system indication
fully test the system and ensure it is fault free. Fully program the system Fill in the installation log at the back of the manual and retain if for future reference. Finally explain the operation of the system to the end user. The Operating Instructions are attached to the centre of this manual. Detach them and leave them with the user.
- Set system indication
To enter Engineer program mode
Note: The factory configured engineers access code is 9999. If however this code is changed then enter the appropriate code.
ZONE 1 - 8 Momentarily On
Engineer program mode
The panel may be programmed to suit a wide variety of installations. Once the engineer program mode has been accessed, each configuration may be changed in any order. As each configuration is completed the system will automatically return to top level of engineering program mode. Before entering engineer program mode the system should be in the Day mode, with the Day and Power indicators lit. Key
LED steady On indication LED flashing indication LED Off
o/p ARC Output to Alarm Receiving Centre Communicator outputs are not applicable for Optima compact G3 panel
Acknowledge
To Exit Engineer program mode
To reset panel to Factory set conditions
CAUTION: All configurations of the panel are restored to factory default conditions.
Within 5 seconds of powering up the panel
Reset Reset
Internal sound
Sound description
NOTE: In general a flat beep is an indication of an incorrect key press. External devices Strobe Bell
reset beeps
To exit
Quit the current function Leave program menu Down one menu level
Example: To change User 1 code to 3457 Press:
Access Codes
There are four codes used in the system, all are 4 digit and can be set to any number from 0000 to 9999. The access codes ensure that only authorised users can operate the system. User 1 and 2 codes The user 1 and user 2 codes have the same operation for testing, Setting and Unsetting, but user 1 code which is usually considered to be the Managers code has the authority to add, change or delete the user 2 code and duress code. Duress code Should be used in a hold up situation where there is pressure to Set or Unset the system. Entry of the code will allow the system to work normally but also generate a silent PA type alarm by operating the PA communicator output. Engineer code Accesses the Engineer Program mode to allow the system to be programmed. The engineer code will not set or unset the system. If configured the Engineers access code can be used to reset the system after an alarm.
Zone Type
The G3 range of panels are not supplied with wire links to terminate unused zones. Therefore all unused zones must be programmed out by setting them to disabled using the Zone Type function.
Example: To disable an unused zone 8, Press: Prog 0 Reset Enter Engineer program mode Zone 5 Configuration
Press a number button to select Zone to be configured
Zone 1 type Zone 2 type Zone 3 type
Disabled Security Fire 24h Fire PTS Keyswitch
Factory default Zone 1
Zone 4 type
Press a number button to select zone type
Zone 5 type Zone 6 type Zone 7 type Zone 8 type
Exit to zone type
Day Attack
Exit zone configuration Leave engineer mode
Appropriate Zone indicator is lit to show Zone type
Zone Attributes
Example: To configure zones 4 and 5 for Double knock operation, Press: Prog Reset Reset Reset Enter Engineer program mode Zone 6 Attributes
Double Knock Omit Prevent Zone Delay
ZONE 1 - 8 Momentarily On Day
Deselect all zones Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7
Press number button to select / deselect zone delay, Omit zone or Double knock
Factory defaults: Appropriate Zone indicator is lit to show zone having 800mS delay, Omit prevent or double knock.
All zones have delay of 300mS
No Zones are set as omit prevent
No zones are in double knock Exit to zone type Exit zone attributes Leave program mode
Day Acknowledge Tamper Day Attack
Zone attribute descriptions Double knock: The panel will require 2 activations of the same detector before causing an alarm condition. This setting is used as a false alarm measure.
Note: Double knock must not be used on zones having magnetic door/window contacts.
Omit Prevent: The panel will prevent the zone from being omitted by the user when setting the system. Zone Delay: The panel programs a zone delay to 800mS to give extra immunity to false alarms.
Bell and Service Timers
Example: To set bell timer for 10 minutes duration, Press: Prog Reset Reset Enter Engineer program mode Timers and 7 Counters
Attack Zone 1
Continous operation 1 minute bell duration 2 minute bell duration 3 minute bell duration 20 minute bell duration (factory default) 99 minute bell duration
Bell timer Bell delay timer Service timer Re-arm counter (00 to 99) Anti-code reset site code
Zone 2 Day ZONE 1 - 8 Momentarily On Day
No delay (Factory default) 1 minute bell duration 2 minute bell duration 3 minute bell duration 20 minute bell duration 99 minute bell duration
Press a number button to select Service timer
Service timer disabled (Factory default) 100 Set/Unset 200 Set/Unset 300 Set/Unset 400 Set/Unset 500 Set/Unset 600 Set/Unset 700 Set/Unset 800 Set/Unset
Appropriate Set / Unset values LED is lit
Lit when selected Day
Exit Timer and counters Leave engineer mode
Re-arm and Anticode reset code
Example: To set panel re-arms to 10 times before panel is shut down, Press:
Enter Engineer program mode Timers and 7 Counters
Re-arm After an alarm the panel will automatically reset itself when the bell timer has expired. Any zones which still remain open at that time will be omitted automatically.
Note: By default there are 3 automatic re-arms before the panel is shut down.
Anti code reset (Engineer reset) If the system has been programmed to be engineer reset, after an alarm it will lock out and the RKP will continually display the cause of the alarm. The engineer would then be required to attend the site and use the engineer code to reset the system. Where anti-code reset has also been enabled, the RKP will still show the alarm cause and also display a 4 digit 'quote code' by sequentially flashing zone indicators 1-8. At this point the end user would contact the engineer. After determining the cause of the alarm and deciding that a engineer call was not necessary, a 6 digit anti-code would be given to the user which would reset the system. This anti-code is generated from a small computer program which is installed at most UK Alarm receiving Centres, or alternatively can be run on a PC by the engineer. Security of the anti-code reset system is maintained by a 2 digit site code which is set up in the anti-code generator programme. The same 2 digit site must also be set up in the control panel during installation.
No re-arm 1 re-arms 3 re-arms (factory default) 99 re-arms
Zone 2 Day
factory default code 99
Exit to Timer and counters Leave program mode
Lighting controller
Example: To assign zones 1 and 2 to lighting controller channel 1, Press: Prog Reset Reset Reset Enter Engineer program mode Lighting 9 Controller
To assign zones to channel press to select and again to deselect zone (Factory default: No zones are selected)
Channel assigned zones Channel assigned zones
Press a number button to select the appropriate light channel
Channel assigned zones
Channel 5 assigned zones
Day Zone n assigned to the channel Zone n not assigned to the channel
Channel assigned zones Channel assigned zones Channel assigned zones
Exit current level Exit Lighting controller
Hold time (0-99 seconds) 9 (20 seconds factory default)
Set the light threshold level (0 - 99%)
Leave program mode
0% threshold or 0 second hold time 1% threshold or 1 second hold time 20% threshold or 20 seconds hold time
acknowledge
Exit Lighting controller
Day Tamper Acknowledge
Appropriate Zone indicator is lit to identify its assignment to channel
g. Before testing or replacing any fuses, ALL power must be removed. Fuses which fail continually are almost certainly the result of a short circuit or low resistance across the 13V supply or external bell supply (terminal D). Whenever working close to the mains supply or connector, you should exercise extreme caution. Always isolate the mains supply before removing the control panel covers. Where normally open detectors are connected to adjacent zones two pull-up resistors (not supplied) of value 33kohms must be installed. The example below shows how to wire normally open detectors on zones 3 and 4.
Faults
Fault conditions are often the result of minor installation errors or misinterpretation of the equipment being installed. The following points outline the most common installation and commissioning faults. a.
As supplied the user code is 0123 and h. the engineer code is 9999. Both codes will revert back to these default settings on clearing the NVM. The Engineer Program is accessed directly from Day mode via the engineer code. If a tamper, PA or 24Hr fire fault is present on the system, it will go to a lock out condition (showing the appropriate indication). The keypad will not produce any audible responses and the system will not operate until the fault has been found and rectified. The most common cause of a zone not responding to detection is incorrect wiring. Normally closed detectors must be wired together in a series loop before connecting into the appropriate ZONE terminals. Tampers are series wired in the same manner. Where a permanent zone fault is showing and the loop resistance is found to be in order, the most probable cause is a short circuit between the zone wiring and the tamper wiring. When measured with a multimeter the series resistance between the zone and tamper wiring should be infinitely high. If totally lost as to the cause of a fault, remove ALL wiring from the PCB. Refit the 4-links and test the system. Never fit links to any positions other than those marked on the PCB. i.
Re-arm. Rearm counter. Red Care STU. Remote keypad. Remote keyswitch RKP. RKP PA enable. 2,8 2,3,10,25 17
AC terminals. Access Codes. Alarm test. Anti Code Reset ARC. 16 10,17,22 9
Hold time. 23
Battery. Bell Delay. Bell Duration. Bell in fire. Bell Output. Bell timer. Board. BS 4737 1986/87. 11,7,4 1
Immediate zone. 14
Security Zones. Service counter. Service timer. Set. Set system. Silent PA. Silent Set. Single key setting Site Code. Speakers. Specification. Standard Fire zone Strobe on setting. 5,10,12 10,17 14,15 10,3 25,26 6,10 10,17
Keyswitch zone. 10,19
light channel. 23 Light Hold Time. 10 Light threshold. 10,23 Lighting controller 2,10,23 Line Fail. 10 Local Authorit. 3
Charge Voltage. 25 Chime. 2 Codes. 2 Communicator. 17 Communicator Outputs 8,10 Current Consumption 25
Mains. 11,25 Managers code. 13
TADB. 7 Tamper. 25 Tamper fault. 24 Tamper network. 6 Terminated Set. 6,14,15 Time inhibited zone 14,15 Timed. 14 Timed exit. 15 Timed zones. 15 Total current. 3
NACOSS. 6,9 NACP 14. 9 Normally closed detectors 24 Normally open detector 24 NVM. 2,9
Day mode. Detectors. Dimensions. Door bell. Double knock Duress Code. 25 10,17 10,20 10,13
Omit prevent. 10,20 Operating temperature 25
Engineer Code. 10,13 Engineer program mode 12,24 Engineer Reset. 10,17 Entry deviate. 18 Entry time. 10,15 Event log. 18 Exit Mode. 10,14,15 Exit time. 10,15 Exit/Entry timers. 25 Extension speakers 7 External bell on Fire 10
Unset system. 12 Unused zone. 14,15 User code 1. 10 User 1. 2 User 1 and 2 codes 13 User 2. 2 User code 2. 10 User reset fire. 10,18 User reset PA. 10,18
PA. 2,6,25 PA fault. 24 PCB Fuses. 25 Pressure mats. 25 Program 1. 10,14 Program 1 to report10,18 Program 2. 10,14 Program 2 to report10,18 Program 3. 10,14 Program 3 to report10,18 Programs 1,2 and 315 PTS zone. 2,19
Volume. 7
Walk Test. 2,16
Servicing organisation Details
Servicing organisation name: _______________________________________ Telephone number: ______________________________________ Date of installation: ______________________________________ Account Number: _____________________________________
Below is a list of approved parts and accessories. 8SP 401 Accenta G3 panel 8SP 400 Accenta mini G3 panel 8EP 395 Optima G3 8EP 396 Optima compact G3 panel 8EP 219 Accenta LED RKP 8EP 332 Accenta LCD RKP 8EP 336 Accenta Speech Dialler 8EP 276 Informa 8EP 289 Extension Speaker 8EP 372 Opti-Cam Lighting Controller A range of detectors are also available, for more information contact your supplier.
An unset system will have both Day and Power Day Power indicators lit. This is a normal indication when the system is disarmed.
Note: If the Power indicator goes off at any time then there is a mains supply failure at the security panel, consult your servicing organisation.
Set System indication
An active Set system will have only the Power Power indicator lit. This is an armed system indication.
Operating instructions
Unset system indications - - - - - - - - - - Set System indication - - - - - - - - - - - Access codes - - - - - - - - - - - - - - - How to operate Personal Attack - - - - - How to unset system in alarm - - - - - - Programs 1, 2 and 3 - - - - - - - - - - - - How to set the system (on program 1) - - Push to Set Switch - - - - - - - - - - - - - Keyswitch Set - - - - - - - - - - - - - - - Faults during setting - - - - - - - - - - - - How to unset the system (turn off) - - - - How to set program1,2 or 3- - - - - - - - How to Quick set - - - - - - - - - - - - - How to Omit zone(s) on setting system - - Fire Alarm - - - - - - - - - - - - - - - - How to set Chime zone - - - - - - - - - - Operators Program mode - - - - - - - - - To exit operation at any time - - - - - - - - How to enter Operators program mode - How to view the event log - - - - - - - - - How to create/omit User 2 code - - - - - - How to change current user code - - - - - How to create/change/omit the Duress code How to carry out Alarm and Walk tests- - Servicing organisation details - - - - - - - - Quick Reference - - - - - - - - - - - - - - 7 8
How to unset system in alarm
Enter your code. Entering the code will turn the alarm off and the cause of the alarm will be displayed. After investigation press Reset to clear the indication.
n n n n
FIRST ZONE IN ALARM OTHER ZONES IN ALARM
Investigate the Alarm
ALL ZONE
Strobe Off
Access codes
Note: If the alarm indication does not clear, then the system may need to be reset by the installation engineer, contact you installer for further information.
Programs 1, 2 and 3 Access codes
There are two User codes used in the system, all are 4 digit and can be set to any number from 0000 to 9999, signified by:
Keyswitch Set
Your system may have been fitted with a remote keyswitch. This can be used as an alternative to arming the system with a code and will set Program 1. Where a keyswitch is used it may be necessary on occasions to allow it to catch up with the system. For example if the alarm was set with a code, to Unset with the keyswitch, it would have to be momentarily turned to Set then returned to Unset.
Faults during setting
If the system is not clear when you try to Set it, the sounder will produce an open zone tone and the fault will be displayed. Either re-enter your code to turn off and investigate or omit the faulty zone(s) from the system.
How to Quick set
During the exit period (on entering User code) Day the system may be Set Set the system or quickly by pressing Set. This removes the exit time Set a Program period.
5 seconds insistent beeps Day
How to set Chime Zones
Example: To set zone 3 and 4 to chime, Press:
If you omit zones and require Quick Set, you will need to press Set twice.
Timeout after 5 seconds if no selection is made
Day Chime
o/p ARC Set output
Deselect all zones (Factory default - no chime) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Appropriate Zone indicator is lit to show chime zone(s)
Zone n Chime selected Zone n Chime deselected
How to Omit zone(s) on setting system
Press number button to select / deselect Zone Chime
During the exit period after entering User code and selecting a Day program press Set the system or Set a Program and while theOMIT, the exit tone will stop and zones system is setting: that are about to be Omit ZONE(S) TO BE ARMED armed will be displayed. Key in Exit beep the zone number(s) to be omitted which Press the zone(s) n to be omitted will flash to confirm selection. Zone ZONE(S) TO BE OMITTED indicators which show steady are still Set about to be armed. 10 seconds Exit beep insistent beeps When the selection is complete press Day Set and the exit tone o/p ARC will start. Set output If a zone refuses to be omitted, it may be because the engineer has programmed the panel to prevent you from turning off the zone. If in doubt ask your installer for advice.
Leave chime mode
Fire Alarm
The fire zone will operate on detection of a fire, whether the system is Set or Unset, when configured as a 24 hour zone, and cause a distinctive internal sounder tone. The external sounders will pulse on and off at 2 second intervals and all keypad indicators will flash to attract attention.
Operators program mode menu map
Operators Progam Mode Prog
To exit Operators program mode
To set Chime zone
Alarm test Change / omit User code 2 (By user 1 only) Change the code of Current user (either User 1 or User 2) View the event log
n n n n n
10 seconds insistent beeps
Strobe test To omit the user 2 code
Automatic event scroll Starting from event 1 to 8 For manual scroll
Zone to chime
3 Bell test
View event 8 (Newest event)
View event 1 (oldest event)
Change / Omit 9 the Duress Code (By user 1 only)
Resume automatic scroll
Normal indications of an Unset system
6 n n n
Walk test Press zero to turn off options 2,3,4 and 5 before selecting a new one
Alarm indications
Stop event scroll / view
Bell On
Strobe
Tags
Polaroid A932 SP-43T8HE Grandam 2000 25PT4103 Ryobi 137R Honeywell CM51 FYB462X BC246T ICD-B50 Makita 9404 A75-S1253 LE-37R72B IGO 2441 DSM-320 WNR834M DCX2496 35 ML Yamaha QY22 D-copia 2200 MW 7804 Monster-2001 1 0 KX-TG5631S Digital Elph NP-N140-ja01ES LE32A656a1F 42PD7200A KX-TG8200FX DV4000 Kxtg4011 Review TH-42PV70PA SF-6800P A9200 VGN-N38e-W Nd V6 Dslr-A200W AZ2558 6900 Zoom Mobile Iriver T30 MFC-3320CN BMP7407 HVR-Z5N KX-P1131 MF5650 Alcatel 4059 PSR-600 PB8240 UA-25 XDR-S20 BOX 7240 RHH130 Magma 870 IS SV-5000W Dimension C521 Travelmate-C110 Rev 1 LN46C750r2F YFZ450-2007 SP100 650 RE P5000 DSC-P32 EWF810 SU-C3000 M-627V CS-29Z50MH RH177H LX3900SA L194WT Nclv-D CDX-L380X Pclk-MN10A IFP-800 Samsung C130 NV-DX100EG LA40A650 WM-EX910 LP-M5500 SR7500 GR-D72us-gr-d72 III GPS 6722DW Inhalt Rice Cube HTS9810 12 W910I SHV99A13UC Breadmaker SLV-SX710D N343I MFM-HT75W Command DG824M C 1020 Pentax MZ50 KX-TC1703B KD-G710 DSC-W170 G
manuel d'instructions, Guide de l'utilisateur | Manual de instrucciones, Instrucciones de uso | Bedienungsanleitung, Bedienungsanleitung | Manual de Instruções, guia do usuário | инструкция | návod na použitie, Užívateľská príručka, návod k použití | bruksanvisningen | instrukcja, podręcznik użytkownika | kullanım kılavuzu, Kullanım | kézikönyv, használati útmutató | manuale di istruzioni, istruzioni d'uso | handleiding, gebruikershandleiding
Sitemap
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101








