Ademco Vista-20psia
|
|
Bookmark Ademco Vista-20psia |
All the same features as the VISTA-20P - UL approval for ANSI/SIA CP-01-2000
Details
Brand: ADEMCO
Part Number: VISTA-20PSIA
UPC: 781410724709
Here you can find all about Ademco Vista-20psia, for example manual and review. You can also write a review. [ Report abuse or wrong photo | Share your Ademco Vista-20psia photo ]
Manual
Preview of first few manual pages (at low quality). Check before download. Click to enlarge.
Download
(English)Ademco Vista-20psia - Programming Guide, size: 382 KB |
Ademco Vista-20psia
User reviews and opinions
No opinions have been provided. Be the first and add a new opinion/review.
Documents

ADEMCO VISTA SERIES
VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA
Security Systems Programming Guide
K5305-1PRV5 10/04 Rev. A
TO ENTER PROGRAMMING MODE (using an alpha keypad connected to the control):
A. POWER UP, then press [] and [#] at the same time, within 50 seconds of powering up (this method must be used if 98 was used to exit program mode). OR B. Initially, key: Installer Code (4 + 1 + 1 + 2) plus 8 + 0 + 0. Command/Explanation Press [] + [Field Number], followed by the required entry. When the desired field number appears, simply make the required entry. When the last entry for a field is entered, the keypad beeps three times and automatically displays the next data field in sequence. If the number of digits that you need to enter in a data field is less than the maximum digits available (for example, the phone number fields *41, *42), enter the desired data, then press [ ] to end the entry. The next data field number is displayed. Press [#] + [Field Number]. Data will be displayed for that field number. No changes will be accepted in this mode. Press [] + [Field Number] + []. (Applies only to fields 40 thru *46, *94, and pager fields) Press 96. Initializes download ID and subscriber account number. Press 97. Sets all data fields to original factory default values. Press 56. Zone characteristics, report codes, alpha descriptors, and serial numbers for 5800 RF transmitters. Press 57. Unlabeled keypad keys (known as ABCD keys) for special functions Press 58. Same options as *56 mode, but with fewer prompts. Intended for those familiar with this type of programming, otherwise *56 mode is recommended. Press 79. Assign module addresses and map individual relays/powerline carrier devices Press 80. 4229 or 4204 Relay modules, Powerline Carrier devices, or on-board triggers Press 81. Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc. Press 82. Zone alpha descriptors Press 98. Exits programming mode and prevents re-entry by: Installer Code + 8 + 0 + 0. To reenter programming mode, the system must be powered down, then powered up. Then use method A above. See field *88 for other *98 Program mode lockout options. Press 99. Exits programming mode and allows re-entry by: Installer Code + 8 + 0 + 0 or method A above.
PROGRAMMING MODE COMMANDS
Task Go to a Data Field Entering Data
Review a Data Field Deleting an Entry Initialize Download ID Reset Factory Defaults Zone Programming Function Key Programming Zone Programming (Expert Mode) Output Device Mapping Output Programming Zone List Programming Alpha Programming Exit Program Mode with installer code lockout Exit Program Mode
SPECIAL MESSAGES
OC = OPEN CIRCUIT (no communication between Keypad and Control). EE or ENTRY ERROR = ERROR (invalid field number entered; re-enter valid field number). After powering up, AC, dI (disabled) or Busy Standby and NOT READY will be displayed after approximately 4 seconds. This will revert to a Ready message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this delay by pressing [#] + [0]. If E4 or E8 appears, more zones than the expansion units can handle have been programmed. The display will clear after you correct the programming.
TABLE OF DEVICE ADDRESSES
This Device Uses Address RF Receiver 00 AUI AUI Long Range Radio Voice Module 04 Zone Expanders (4219/4229): module 1 (for zones 09 - 16) 07 module 2 (for zones 17 - 24) 08 module 3 (for zones 25 - 32) 09** module 4 zones 33 - 40 10** module 5 zones 41 - 48 11** Relay Modules (4204): module module module 3 14** module 4 15** Keypads: keypad keypad keypad keypad keypad keypad keypad keypad 5800TM Module 28 Reports as n/a n/a n/a n/a n/a n/a n/a n/a n/a Enabled By *56 zone programming: input device type entry Automatic if AUI enable field *189 enabled for AUI 1 Automatic if AUI enable field *189 enabled for AUI 2 automatic if output to long range radio field *29 enabled automatic if phone module access code field *28 enabled *56 zone programming: input device type entry, then: automatic if zone no. 9-16 entered as AW type or relay assigned automatic if zone no. 17-24 entered as AW type or relay assigned automatic if zone no. 25-32 entered as AW type or relay assigned automatic if zone no. 33-40 entered as AW type or relay assigned automatic if zone no. 41-48 entered as AW type or relay assigned *79 output device programming: device address prompt: entered at device address prompt entered at device address prompt entered at device address prompt entered at device address prompt data field programming as listed below: always enabled, all sounds enabled. data field *190 data field *191 data field *192 data field *193 data field *194 data field *195 data field *196 automatic
[FFFFFFFFFF] To clear, press *44*.
34 Exit Delay
[60,60]
00 - 96 = 0 - 96 secs; 97 = 120 secs Part. 1 SIA Guidelines: minimum exit delay is 45 seconds V20PSIA/V15PSIA: 45 - 96 = 45 - 96 secs; 97 = 120 secs NOTE: Entries less than 45 will result in a 45-second delay. UL: see inst. instr. for requirements.
45 Partition 2 Primary Acct. No. (see field *43 for entries)
| | | / | | | / | | | | | | | | | |
[FFFFFFFFFF] To clear, press *45*.
46 Partition 2 Secondary Acct. No. (see field *43 for entries)
[FFFFFFFFFF] To clear, press *46*.
Common zones use part. 1 delay.
35 Entry Delay #1
47 Phone System Select 48 Report Format
Common zones use same delay as partition 1. Part. 1 Part. - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs SIA Guidelines: minimum entry delay is 30 seconds V20PSIA/V15PSIA: 30-96 = 30 - 96 secs; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs NOTE: Entries less than 30 will result in a 30-second delay. For UL Residential Burglary Alarm installations, must be set for a maximum of 30 seconds; entry delay plus dial delay should not exceed 1 min. For UL Commercial Burglar Alarm, total entry delay may not exceed 45 seconds.
If Cent. Sta. is not on a WATS line: 0=Pulse Dial; 1=Tone Dial; if Cent. Sta. is on a WATS line: 2 = Pulse Dial ; 3 = Tone Dial
0 = 3+1, 4+1 ADEMCO L/S STANDARD primary secondary 1 = 3+1, 4+1 RADIONICS STANDARD 2 = 4+2 ADEMCO L/S STANDARD 3 = 4+2 RADIONICS STANDARD 5 = 10-digit ADEMCO CONTACT ID REPORTING 6 = 4+2 ADEMCO EXPRESS 7 = 4-digit ADEMCO CONTACT ID REPORTING 8 = 3+1, 4+1 ADEMCO L/S EXPANDED 9 = 3+1, 4+1 RADIONICS EXPANDED
49 Split/Dual Reporting
0 = Standard/backup reporting only (all to primary) Primary Phone No. 2nd Phone No. 1 = Alarms, Restore, Cancel Others 2 = All except Open/Close, Test Open/Close, Test 3 = Alarms, Restore, Cancel All 4 = All except Open/Close, Test All 5 = All All
66 Arm Away/Stay Rpt Code
[0,0,0,0,0,0]
Away Stay Part. 1 Away Stay Part. 2 Away Stay Common
67 RF Trans. Low Bat Report Code
UL: must be enabled if wireless devices are used
[00] [00]
50 Burglary Dialer Delay
68 Cancel Report Code
V20PSIA/V15PSIA: [10] Report enabled.
Delay Time: Delay Time V20PSIA/V15PSIA 0 = no delay UL: must be 0 Delay Disable 1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds SIA Guidelines: delay must be minimum of 30 seconds V20PSIA/V15PSIA: Delay Time: 1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds Delay Disable: 0 = use delay set in entry = dial delay disabled for zones listed in zone list 6 (use zone list 6 to enter those zones that require dial delay to be disabled; these zones ignore the setting in entry 1) UL: Dial delay plus entry delay must not exceed one minute; use zone list 6 to disable dial delay from appropriate zones, if necessary.
This is a command, not a data field. See page 2.
89 Event Log Full Report Code
See box above field *59 for report code entries.
PAGER OPTIONS (160- 172) 160 Pager 1 Phone No.
Enter up to 20 digits. 09; #+11 = ''; #+12 = '#'; #+13 = 2-sec pause
90 Event Log Enables
NOTE: System messages are logged when any non-zero entry is made. 0 = None; 1 = Alarm/Alarm Restore 2 = Trouble/Trouble Restore; 4 = Bypass/Bypass Restore; 8 = Open/Close. Example: To select Alarm/Alarm Restore, and Open/Close, enter 9 (1 + 8); To select all, enter #15.
161 Pager 1 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits. 09; #+11 = ''; #+12 = '#'; #+13 = 2-second pause.
91 Option Selection
[8, 0]
V20PSIA/V15PSIA
162 Pager 1 Report Options
[0,0,0] Part. 1 Part. 2 common For each partition, select from the following options: 0 = no reports sent 1 = Opens/closes all users 4 = All alarms and troubles 5 = All alarms / troubles, and opens/closes for all users 12 = Alarms / troubles for zones entered in zone list = Alarms / troubles for zones entered in zone list 9, and opens/closes for all users
Options: 0 = None Options 4 = AAV UL: must use ADEMCO UVCM module 8 = Exit Delay Restart/Reset UL: must be disabled #+12 = AAV and Exit Delay Restart/Reset SIA Guidelines: Exit Delay should be enabled.
Call Wait Disable
V20PSIA/V15PSIA: Options: Same as listed above. Call Waiting Disable: 0 = call waiting not used 1 = call waiting disable digits (*70) entered in field *40; (when selected, the system dials the entry in field *40 only on alternate dial attempts; this allows proper dialing in the event call waiting service is later canceled by the user).
163 Pager 2 Phone No.
Enter up to 20 digits. 09; #+11 = 'Q'; #+12 = '#'; #+13 = 2-sec pause
92 Phone Line Monitor Enable
164 Pager 2 Characters
UL: see Inst. Instructions for requirements NOTE: Output Device must either be programmed to be STOPPED in field 80 or STOPPED by Code + # + 8 + output number. Entry 1:: 0 = disabled, 1-15 = 1 min - 15 min (#+10 = 10 min; #+11 = 11 min; #+12 = 12 min; #+13 = 13 min; #+14 = 14 min; #+15 = 15 min) Entry 2: 0 = Keypad display when line is faulted 1 = Keypad display plus keypad trouble sound 2 = Same as 1, plus programmed output device STARTS. If either partition is armed, external sounder activates also.
165 Pager 2 Report Options
Part. 1 Part. 2 common See field *162 for reporting options. Select for each partition (use zone list 10 if using options 12 or 13).
93 Reports In Armed Period
Restrict V20PSIA/V15PSIA Report Pairs Unlimited Reports Enable
166 Pager 3 Phone No.
Per Zone (Swinger Suppression)
Restrict Report Pairs: 0 = Unlimited Reports 1 = 1 report pair 2 = 2 report pairs SIA Guidelines: Must be set for option 1 or 2.
167 Pager 3 Characters
V20PSIA/V15PSIA: Restrict Report Pairs: 1 = 1 report pair; 2 = 2 report pairs Unlimited Reports Enable: 0 = restrict reports to the setting in entry = unlimited reports for zones listed in zone list 7; (use zone list 7 to enter those zones that require unlimited reporting; these zones ignore the setting in entry 1)
168 Pager 3 Report Options
0,0,0]
Part. 1 Part. 2 common See field *162 for reporting options. Select for each partition (use zone list 11 if using options 12 or 13).
DOWNLOAD INFORMATION (94, 95) 94 Download Phone No.
Enter up to 20 digits, 09; #+11 for ''; #+12 for '#'; #+13 for a 2second pause. Do not fill unused spaces. If fewer than 20 digits, exit field by pressing. To clear entries from field, press 94. UL: downloading may be performed only if a technician is at the site.
169 Pager 4 Phone No.
170 Pager 4 Characters
95 Ring Count For Downloading
NOTE: Do not enter 0 if using 4285/4286 Phone Module. 0 = Disable Station Initiated Download; 114 = number of rings (19, # +10 =10, # +11 =11, # +12 =12, # +13 =13, # +14 =14); 15 = answering machine defeat (# +15 =15).
171 Pager 4 Report Options
Part. 1 Part. 2 common See field *162 for reporting options. Select for each partition (use zone list 12 if using options 12 or 13).
172 Pager Delay Option For Alarms
0 = none; 1 = 1 minute; 2 = 2 minutes; 3 = 3 minutes This delay is for ALL pagers in the system.
MISCELLANEOUS SYSTEM FIELDS (*174-*181)
KEYPAD OPTIONS *190-*196
NOTES: 1. Options for keypad address 16 are set by the factory and cannot be changed.) 2. Each keypad must be assigned a unique address. Keypads programmed with the same address will give unpredictable results.
174 Clean Me Reporting Options
(for ESL smoke detectors) 0 = disable; 1 = Clean Me signal reports; NOTE: If Clean Me is enabled, you must enter 3 in field 56 programming for zone 1 response time.
INTACT EOL
SHORTED
ZONE-003-V0
ENTRY 7
Display Faults
ENTRY 8
Use Exit Delay 0 = no 4 = use exit delay Respond as Interior Type 0 = no 8 = yes see note 2
Zone Conditions Represented in Entries 1-6 NOTES: 1. Do not use the fault delay option with a configurable zone type if it is set for an entry or exit delay, otherwise unpredictable results may occur. 2. To create an interior type zone, select respond as interior zone type (entry 8, interior type = yes), and set zone response to fault in entries 3-4 to ensure fault displays; do not set as normal, alarm, or trouble. 3. Do not set fire zones to respond as a fault (entries 1-6), otherwise faults will not display unless the [] key is pressed. 4. 4219/4229 modules must use EOLRs or unpredictable results may occur. 5. RF Zones: The open option in entries 1, 3, and 5 is not applicable for RF zones. Use the intact EOL option for normal RF zone conditions and shorted for offnormal RF zone conditions. 6. a. Zone-Doubling/Double-Balanced: A short on either zone of a zone-doubled pair or on a double-balanced zone causes a tamper condition. b. For double-balanced zones, this entry must be 0. c. For zone-doubled zones, both zones of the doubled pair must be assigned the same response to a short.
Power Reset/ Use Entry Verification Delay 1/= no 0 = show alarms 0 = no 1 = delay 1 when armed 4 = power reset 2 = delay 2 & disarmed after fault (by code + OFF) 1 = dont show alarms when 12 = verification (see zone armed (show type 16) alarms, trbles,
faults when disarmed)
3 = never show any alarms, trbles, faults Entry 7 = fault display + power reset/verification
Entry 8 = entry delay 1/entry delay 2 + exit delay + interior zone type
ENTRY 9
Alarm Sounds Use Bell Timeout 0 = no 4 = yes Respond as Fire Zone 0 = no 8 = yes
ENTRY 10
Trouble Sounds 0 = none 1 = periodic beep 2 = trouble beeps Chime when Chime Mode On 0 = no 4 = yes
0 = none 1 = steady keypad 2 = steady bell see fields *32, see zone type and keypad *33 09; see note = pulsing bell and keypad Entry 9 = alarm sounds + bell timeout + fire zone
Entry 10 = trouble sounds + chime
*5800 button-type transmitters only
PARTITION
1, 2, or 3-common (VISTA-20P)
REPORT CODE
1-9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F For Contact ID, enter any non-zero entry as the first digit to enable reporting for this zone. To disable the report code for this zone, enter 00.
58 Expert Zone Programming Mode
(press 58 while in Data Programming mode) SET TO CONFIRM?
Select whether you want confirmation of wireless device enrollment. (See XMIT TO CONFIRM prompt later in this section.) We recommend that you confirm the programming of every transmitter.
HARDWIRE TYPE
Appears only for zones 02-08. Zone 1 is automatically set for EOL operation. Enter the desired hardwire type: 0 = EOL; 1 = NC; 2 = NO; 3 = zone doubling (ZD); 4 = double-balanced (DB) ( VISTA-20P)
SUMMARY SCREEN Zn ZT P RC HW: RT EL 1
(Typical for Zone 1, initial summary screen)
RESPONSE TIME
For hardwired zones 01-08. Enter the desired response time for this zone: 0 = 10mSec; 1 = 350mSec; 2 = 700mSec; 3 = 1.2 secs (see field 174). NOTE: If zone doubling is being used, the response time selected for zones 02-08 automatically applies to each zones associated doubled zone.
INPUT TYPE
Skipped for zones 2-8, and for zones 10-16 if zone-doubling enabled. Enter the input type: 2 = AW (Aux wired zone); 3 = RF (supervised RF); 4 = UR (unsupervised RF); 5 = BR (unsupervised button type) NOTE: To change the input type of a previously programmed wireless device to a wired zone, you must first delete the transmitters serial number.
Zn ZT P RC IN: L RF:
(Typical for entered zone number; zone 10 in this example) System displays summary of zone 1s current programming. Enter the zone number being programmed, then press []. A summary screen for that zone is displayed, along with any current programming values, and the cursor moves to the Zone Type location. The cursor then automatically moves to the next locations after each entry is made. Special Function Keys: [A] (Advance) and [B] (Back) keys on the keypad move the cursor within the screen. [C] (Copy) key will insert the previous zones attributes, if desired. [D] key starts the Wireless Key Programming Templates menu (see Wireless Key Programming Templates section that follows this section). Sequentially enter Zone Type (ZT), Partition (P), and Report Code (RC), then Hardwire Type (HW) and Response Time (RT) for basic wired zones 1-8 or Input Device Type (IN) for zones 9 and higher (Loop Number [L] is programmed at the INPUT S/N prompt). See *56 Zone Programming Menu Mode section described earlier for entry values. applies to VISTA-20P Press [] to save the programming and continue. If needed, press the [#] key to back up without saving. For wireless devices (input types RF, UR, BR), continue to the INPUT S/N (serial number/loop number) and XMIT TO CONFIRM prompts described earlier in the *56 Zone Programming Menu Mode section. When done, the display returns to the initial summary screen prompt to let you program the next zone. For wired devices, the display returns to the initial summary screen prompt to let you program the next zone. To Quit, enter 00 at the zone number location and press [].
INPUT S/N
Enroll the transmitters serial number and loop number as follows: 1. a. Transmit two open/close sequences (for button-type transmitters, press and release the button twice, waiting about 4 seconds before pressing the button the second time). OR b. Manually enter the 7-digit serial number printed on the label of the transmitter. Press the [] key to move to the L position, then enter the loop number. Use the [A] (Advance) and [B] (Back) keys to move the cursor forward and back within the screen. Pressing the [C] (Copy) key will insert the previously enrolled serial number, if desired (used when programming a transmitter with several input loops). To delete an existing serial number, enter 0 in the loop number field. The serial number will change to 0's. If 0 was entered in error, simply re-enter the loop number or press [#], and the serial number will return to the display. 2. Press [] to continue. The system now checks for a duplicate serial/loop number. If no duplicate is found, the display shows the serial number and loop number. 3. Press [] to continue to confirmation screen.
(prompts continued in next column)
Wireless Key Programming Templates (press the [D] key from *58 Menu mode Summary Screen)
This procedure programs the wireless keys, but a key is not active for arming/disarming until it is assigned to a user number (see System Operation section, Assigning Attributes Command in the Installation Instructions). TEMPLATE ?
Enter desired template number 16 (see chart below), then press [] to continue. To exit the Template screen, press [#]. The system returns to the *58 Menu mode Summary Screen.
ENTER START ZONE
The system displays the lowest zone number of the highest available consecutive 4-zone group. To start at a different zone number, enter the zone desired, and press []. If the system has four consecutive zones beginning with that zone, the zone number is displayed. If not, the system will again display a suggested zone that can be used. If the required number of consecutive zones is not available at all, the system will display 00. Press [] to accept. Continue to the INPUT S/N (serial number/loop number) and XMIT TO CONFIRM prompts described earlier in the *56 Menu Mode section. IMPORTANT: When confirmed, the key is not active for arming/disarming until it is assigned to a user number (using the assigning attributes command, attribute 4). See System Operation section in Installation Instructions. When done, the keypad beeps three times and the display returns to the ENTER START ZONE prompt to let you enter the starting zone for the next wireless key.
SUMMARY SCREEN
A summary screen appears showing the programmed settings. Press [] to return to OUTPUT FUNCTION NUMBER prompt.
OUTPUT TYPE
0 = delete; 1 = relay (skip to B prompt); 2 = Powerline Carrier device (skip to A prompt) [] to continue.
*81 Menu Mode
(press *81 while in Programming mode)
The Zone List Worksheet is on page 14.
ZONE LIST NO.
Enter the zone list number (01-12) to program (or 00 to exit this mode). Press [] to continue.
A (if X-10 was selected) UNIT No.
Enter the unit code (01-16, set at the device). [] to return to the Output Number prompt continue
Enter each zone number (01-64) to add to the zone list, followed by pressing [] (example, 01, 02, 03). Press 00 to continue. VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56. IMPORTANT: Do not include fire zones in zone lists that are used to STOP device actions.
B (if relay was selected) MODULE ADDR
Enter the predefined address for this module (07-15; see Table of Device Addresses on page 2). Make sure the modules DIP switches are set to the selected address. [] to continue
DEL ZN LIST?
0 = dont delete list; current zone list remains saved 1 = delete this zone list; All zones in the zone list will be deleted. [] to continue
REL POSITION (actual relay number on module)
For 4204 modules, relay numbers are 1-4. For 4229 modules, relay numbers are 1-2. [] to return to the Output Number prompt for programming the next device
DELETE ZONE?
0 = dont delete zones; save the entire zone list and return to the Zone List No. prompt 1 = go to next prompt to delete zones [] to continue
80 Menu Mode
OUTPUT FUNCT. #
(press 80 while in Programming mode)
The Output Definition Worksheet is on page 15.
Enter the output function number to be defined (VISTA-20P: 01-48; VISTA-15P: 01-24)). [] to continue; 00 = exit
ZN TO DELETE?
Enter each zone (01-64) to be deleted from the list, following each with []. 00 when done to return to the Zone List No. prompt. VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56.
SUMMARY SCREEN 01 A E P Trig ?0 ZL=00
This screen displays a summary of the current output programming A = Output Action; E = Triggering event; P = Partition; Trig = Trigger type Question mark indicates the device shown has not been mapped. Use *79 Menu mode to map the device. [] to continue
*82 Alpha Descriptor Programming
PRE-DEFINED DESCRIPTORS PROGRAM ALPHA
0 = no (quit Alpha mode) 1 = yes Press [] or [#] to continue.
ACTIVATED BY
0 = delete (deletes the output function and any previous programming); a confirmation prompt appears. To delete this output definition, press 1. If you do not want to delete this output, press 0. 1 = zone list (go to A prompt); 2 = zone type (go to B prompt); 3 = zone number (go to C prompt) Press [] to continue
0 = all partitions; 1 = partition 1; 2 = partition 2; 3 = common [] to continue.
ENTER EVENT
00 = clear event 01 = Relay On/Off 02 = User Access 03 = Latch Key Report to Pager (sent to all pagers in the users partition; message sent is 777-7777. User must be enabled for paging and system must be armed before reporting can occur.) 04 = Forced Stay Arming (Forced bypass is automatically enabled regardless of setting in field *23) 05 = Forced Away Arming (Forced bypass is automatically enabled regardless of setting in field *23) 06 = Auto Disarm 07 = Display Reminder 10 = Display custom words (if selected, system displays custom words 8, 9, and 10 at defined time. Can be used as installers reminder message to the end user); programmable by installer only 11 = Periodic Test Report (see key commands in Test Report Code, data field *64, to quickly set periodic test reporting intervals); programmable by installer only [] to continue.
01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM; to select days, position the cursor under the desired days using the [] key to move forward, then press 1 to select the day. [] to continue.
STOP (for events 1 relay on/off; 2 user access; 3 latch key report)
See START for entries. [] to continue.
REPEAT
0 = do not repeat; 1 = repeat schedule weekly; 2 = repeat schedule biweekly (every other week); 3 = repeat schedule every third week; 4 = repeat schedule every fourth week [] to continue
RANDOMIZE (for events 01 and 11)
0 = no; 1 = yes If selected, the scheduled start and stop times will vary within 60 minutes of the hour time. For example, if a schedule is set to start at 6:15pm, it will do so the first time 6:15pm arrives, but on subsequent days it will start anytime between 6:00 and 6:59 p.m. NOTE: Do not use the random option if the start and stop times are within the same hour setting, otherwise unpredictable results may occur (e.g., the randomized stop time may occur before the start time). [] to continue and return to ENTER SCHED NO. prompt to program the next schedule.
DEVICE NUMBER ( for event 1 relay on/off)
01-18; [] to continue.
SCHEDULES WORKSHEET(installer code + [#] + [6] [4]; master code can only access schedules 01-16 for VISTA-20P, 01-04 for
VISTA-15P, and events 00-07 for both controls; VISTA-15P supports up to 8 schedules, VISTA-20P supports up to 32 schedules )
(see list below)
Device No.
for 01 events: enter 01-18
Group No.
for 02 events: enter 1-8
Partition
for 04-06 events: enter 1, 2, or 3 (VISTA-20P)
Start Time/ Days
Stop Time/ Days
Repeat
Random
(yes/no)
Events: Master/Installer Installer Only 00 = clear event 04 = forced STAY arm 10 = display custom words 8-= device on/off 05 = forced AWAY arm 11 = periodic test report 02 = user access 06 = auto disarm 03 = latch key report 07 = display reminder Repeat Options: 0 = none; 1 = repeat weekly; 2 = repeat every other week; 3 = repeat every third week; 4 = repeat every fourth week
*56 ZONE PROGRAMMING WORKSHEET (VISTA-15P supports up to 32 zones: 1-6, 9-34, 49-56) [default shown in brackets]
Zone Zn Type Part. Report Hardwire Type Rsp. Time Location
[09] [01] [03] [03] [03] [03] [03] [03]
Zn Type
[1] [1] [1] [1] [1] [1] [1] [1]
Part. Report
[EOL] [EOL] [EOL] [EOL] [EOL] [EOL] [EOL] [EOL]
Input Type Loop
Serial No. Location
NOTES:
Zone Type: see chart on page 12; Report Code: enabled if any digit entered as 1st digit; Hardwire Type (zns 1-8): 0 = EOL 3 = ZD 1 = NC 4 = DB 2 = NO Input Type: 2 = AW (zones 9-48) 3 = RF (zones 9-48) 4 = UR (zones 9-48) 5 = BR (zones 49-64) NOTE: Zones 9-16 not available if zone doubling enabled. Response Time: 0 = 10msec 1 = 350msec 2 = 700msec 3 = 1.2 sec
Reserved Zones 91 = addressable device
report enable/disable default zone type = [05].
92 = Duress report
enable/disable
[1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [00] [00] [06]
[BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] N/A N/A N/A
N/A N/A N/A N/A N/A N/A
keypad [1] / [] keypad [3] / [#] keypad [] / [#]
*57 FUNCTION KEY WORKSHEET
A Option
com P1 P2 com P1
P2 com P1
ZONE TYPE/SYSTEM OPERATION Choices for Zone Types are: 00 = Not Used 05 = Trouble Day/Alarm Night 10 = Interior w/Delay 24 = Silent Burglary 01 = Entry/Exit#= 24 Hr Silent 12 = Monitor Zone 77 = Keyswitch 02 = Entry/Exit#= 24 Hr Audible 14 = Carbon Monoxide 81 = AAV Monitor Zone 03 = Perimeter 08 = 24 Hr Aux 16 = Fire w/Verification 90-91 = Configurable 04 = Interior Follower 09 = Fire 23 = No Alarm Response Choices for System Operation are: Note: In normal operation mode: 20 = ArmingStay 38 = Chime 52 = Kissoff Code + # + 7 + NN Key Entry starts Device 21 = ArmingAway 39 = Any Fire Alarm 54 = Fire Zone Reset Code + # + 8 + NN Key Entry stops Device 22 = Disarming (Code + OFF) 40 = Bypassing 58 = Duress 31 = End of Exit Time 41 = **AC Power Failure 60 = AAV Trigger ** Use 0 (any) for Partition No. (P) entry. 32 = Start of Entry Time 42 = **System Battery Low 66 = Function key *** Or at Disarming, whichever occurs earlier. 33 = Any Burglary Alarm 43 = Communication Failure 67 = Bell Failure Use *57 Menu mode to assign the function key. 36 = **At Bell Timeout*** 68 = TELCO Line Fault Duration is set in program field *177. 78 = Keyswitch red LED Device action not used for these choices. 79 = Keyswitch green LED
4-WIRE SMOKE DETECTOR CONNECTIONS
OUTPUT 17 (TRIG. 1)
+12 AUX GND OUTPUT 18 (TRIG. 2)
SEALED LEAD-ACID TYPE. BATTERY NORMALLY NEED NOT BE REPLACED FOR AT LEAST 3 YRS. TO DETERMINE TOTAL STANDBY LOAD ON BATTERY, ADD 100mA TO TOTAL OF AUX. POWER OUTPUT AND REMOTE KEYPAD CURRENTS. USE UL LISTED LIMITED ENERGY CABLE FOR ALL CONNECTIONS RED JUMPER CUT FOR BELL SUPERVISION. ALSO, CONNECT 2000 OHM RESISTOR DIRECTLY ACROSS SOUNDER.
5881L: UP TO 8 5881M: UP TO 16 5881H: UP TO 56 *5882 IN CANADA
OPTIONAL FOR UP TO 40 ADDITIONAL ZONES ( FROM EITHER OR BOTH GROUPS)
USE 1361X10 TRANSFORMER INTERFACE IN PLACE OF 1321 OR 1321CN WHEN POWER LINE CARRIER DEVICES ARE BEING USED. (SEE INSTRUCTIONS FOR CONNECTIONS)
ZONE 7
ZONE 1
ZONE 8
ZONE 2
ZONE 3
ZONE 4
ZONE 5
BLACK: KEYPAD GROUND (- ) RETURN
ALL OUTPUTS ARE POWER LIMITED. 2000 OHMS EOLR
ZONE 6
VISTA-20P ONLY
GREEN: DATA IN FROM KEYPAD
RED: KEYPAD PWR ( + )
YELLOW: KEYPAD DATA OUT
165 Eileen Way, Syosset, NY 11791 Copyright 2003 Honeywell International Inc.
THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION'S STANDARD 72, CHAPTER 2 (NATIONAL FIRE PROTECTION ASSOCIATION, BATTERY-MARCH PARK, QUINCY,MA 02269). PRINTED INFORMATION DESCRIBING PROPER INSTALLATION, OPERATION,TESTING, MAINTENANCE, EVACUATION PLANNING AND REPAIR SERVICE IS TO BE PROVIDED WITH THIS EQUIPMENT.
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
24-HR BATTERY STANDBY REQUIRED FOR FIRE INSTALLATIONS. USE 12V, 17.2AH BATTERY FOR 600mA AUX POWER. SEE INSTRUCTIONS.
BATTERY FUSE 3A FOR REPLACEMENT, USE SAME VALUE (e.g. ADEMCO No. 90-12)
RELAY PROGRAM RELAY AS ZONE TYPE 54 (FIRE ZONE RESET) _ 4
BATTERY CAPACITY FOR EMERGENCY BURGLARY STANDBY USE AT LEAST 4 HRS
8-PIN CONNECTOR USED FOR 1361X10 TRANSFORMER CONNECTIONS AND FOR ON-BOARD TRIGGERS SEE INSTRUCTIONS. 7 8
BLK RED GRN YEL AND/OR
ADEMCO 5881* Type RF RECEIVER WIRELESS ZONES
AUX PWR SET UNITS OUTPUT DIP SWITCH TERMINALS FOR DEVICE ADDRESSES 7 - 15 SEE OR INSTRUCTIONS.
BATTERY 12V, 4AH RED
CHARGING VOLTAGE 13.8VDC. MAXIMUM CHARGING CURRENT 650mA.
TO TERM 4 TO TERM 5 TO TERM 6 TO TERM 7
BLK RED GRN YEL BLK RED GRN YEL
ADEMCO No. 4219 WIRED EXPANSION MODULE (8 ADD'L EOLR WIRED ZONES) -AND/ORADEMCO No. 4229 WIRED EXPANSION/RELAY MODULE (8 ADD'L EOLR WIRED ZONES PLUS 2 OUTPUT RELAYS) -AND/ORADEMCO No. 4204 RELAY MODULE (4 OUTPUT RELAYS)
SET RECEIVERS DIP SWITCH FOR DEVICE ADDRESS OF 0. SEE INSTRUCTIONS.
CONTACT OPENS MOMENTARILY UPON FIRE ALARM RESET
VIOLET +
FLYING LEADS FOR BATTERY CONNECTION
(USE SA4120XM-1 CABLE) SYNC TO COM TRANS. DATA
4-WIRE SMOKE OR COMBUSTION DETECTOR
EOL POWER SUPERVISION RELAY MODULE A77-716B. USE N.O. CONTACT, WHICH CLOSES WHEN POWER IS APPLIED.
TO OUTPUT 17 PROGRAM OUTPUT 17 FOR "OUT NORM LOW" = YES IN 79 MENU MODE AND AS ZONE TYPE 54 IN 80 MENU MODE MAX. CURRENT = 100 mA (UP TO 16 DETECTORS PLUS EOL MODULE)
2000 OHMS EOLR
K5305-1PRV5V
TO ZONE TERM. ( +) (ZONES 2 - 8 ONLY) TO ZONE TERM. ( _) HEAT DETECTOR
CLASS 2 PLUG-IN TRANSFORMER 16.5VAC, 25VA (e.g. ADEMCO No. 1321). (USE No. 1321CN IN CANADA)
RING TIP RING TIP (BROWN) (GRAY) (GREEN) (RED)
TO 110VAC UNSWITCHED OUTLET (24HR)
AUX. POWER OUTPUT 10.5-13.8VDC 600mA MAX. (500mA MAX. FOR UL INSTALLATIONS)
HANDSET
INCOMING PHONE LINE TELEPHONE WIRING (VIA RJ31X* JACK AND DIRECT CONNECT CORD) *CA38A IN CANADA

This system uses addressable keypads and Zone Expander Modules (see Table of Addresses in Section 2. Mounting and Wiring Wiring the Keypads and Other Addressable Devices). Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from previous controls) and programmed in data fields *190-*196. Zone Expander Modules must be set for specific addresses (07-11), based on the zone numbers used. 4204 Relay Modules must be set for specific addresses (12-15). This control will not power-up unless AC power is connected (will not power-up on battery alone). However, once the system is powered up, it will operate on battery power in the event of AC loss. Relays have two programming menu modes: Use *79 Menu mode to map module addresses and device (output) numbers. Use *80 Menu mode to define the output functions. This system supports programmable function keys. Use *57 Menu mode to define the function keys. This system provides various paging features. Refer to the Programming Overview section for a summary on pager programming.
Mounting and Wiring the Control
Installing the Control Cabinet and PC Board
Cabinet and Lock 1. Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to the general public, using fasteners or anchors (not supplied) with the four cabinet mounting holes. 2. Remove cabinet door, then remove the lock knockout from the door. Insert the key into the lock.
CHECK POSITION
LOCKED PUSH
ADEMCO ADEMCO
SNAP TAB
PUSH ON LOCK UNTIL IT IS SEATED SECURELY
UNLOCKED
CABINET DOOR BOTTOM
STEP 1
STEP 2
Mounting the PC Board Alone (no RF Receiver)
Figure 1. Installing the Cabinet Lock 3. Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed. When correctly positioned, push the lock until the snap tabs hold it securely. The cabinet can be secured without a lock by using 2 screws in the cover's edge. Before installing the cabinet's contents, remove the metal cabinet knockouts required for wiring entry. Do not remove the knockouts after the circuit board has been installed. 1. Hang two short mounting clips (provided) on the raised cabinet tabs (see Detail B). 2. a. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure that the board rests on the correct row (see Detail A). b. Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws (see Detail B).
CIRCUIT BOARD CIRCUIT BOARD CABINET DETAIL A SIDE VIEW OF BOARD SUPPORTING SLOTS
KEY (YELLOW) OUTPUT 18 (GREEN) (ORANGE) (BLUE) (PURPLE) OUTPUT 17 +12 AUX. GND (-) (BLACK) (RED)
Sounder (Bell) Connections
Basic Connections
Make sounder connections to alarm output terminals 3 (+) and 4 (). The 12VDC sounder output activates when an alarm occurs. Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will overload the power supply, or may cause the electronic circuit protecting the sounder output to trip). You must install a battery, since the battery supplies this current.
spkr_conn-001-V0
ALARM OUTPUT 10.5 - 13.5 VDC 2A MAX.
Supervised output 1. Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the PC board. 2. Connect a 2k ohm resistor across the terminals of the last sounder. See Figure 5.
This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses pause 3 pulses pause 3 pulsesetc.
Use only UL Listed sounding devices for UL installations. Bell supervision is required for fire alarm installations. The total current drawn from the alarm output and the auxiliary power output, combined, cannot exceed 600 mA. In addition, the sounding device must be a UL Listed audible signal appliance rated to operate in a 10.2-13.8 VDC voltage range, and must be mounted indoors.
ALARM OUTPUT TERMINALS
TERMINALS ON CONTROL BOARD
EXTERNAL ALARM SOUNDER
OBSERVE POLARITY 2000 OHM EOL RESISTOR
CUT RED JUMPER ON CONTROL BOARD TO ENABLE BELL (SOUNDER) SUPERVISION.
DO NOT CONNECT THE RESISTOR AT THE ALARM OUTPUT TERMINALS THEMSELVES!
Figure 5. Sounder Wiring (Supervised)
Connecting the Keypads and Other Addressable Devices
Connections
4_ 5+ 6 IN 7 OUT
AR MED
RE AD Y
Connect keypads and other addressable devices (4204, 4219, 4229, 4286, 5881, LRR, etc.) to the controls keypad terminals as shown on the Summary of Connections diagram. The system supports up to 8 keypads, which can be assigned to partitions in any combination (see program fields *190-*196). Determine wire size using the Wire Run Chart on the following page. For single 4-wire runs, determine the current drawn by all units, then refer to the Wiring Run chart to determine the maximum length that can be safely used for each wire size.
RED GREEN
YELLOW
Supplementary Power (optional)
conn-001-V0
TO KEYPAD BLK WIRE TO KEYPAD GRN WIRE TO KEYPAD YEL WIRE
TO KEYPAD RED WIRE
TO KEYPAD GRN WIRE
TO KEYPAD BLK WIRE
IMPORTANT: Keypads powered from supplies that do not have a backup battery will not function if AC power is lost. Make sure to power at least one keypad in each partition from the controls auxiliary power output.
4_wiresmk-008-V0
4_wiresmk-007-V0
Figure 10. Wiring Connections, 4219 & 4229 (4229 shown)
Installing the RF Receiver and Wireless Transmitter Zones
Compatible Receivers Use any ADEMCO 5800 Series Wireless Receivers, such as: RF Receiver No. of Zones 5881L/5882L up to 8 5881M/5882M up to 16 5881H/5882H, VISTA-20P = up to 40 plus 16 buttons 5883, 6150RF VISTA-15P = up to 26 plus 8 buttons 1. Set Device Address to 00 (set all switches to the right, off position). 2. Mount the receiver, noting that the RF receiver can detect signals from transmitters within a nominal range of 200 feet. 3. Connect the receiver's wire harness to the control's keypad terminals. Plug the connector at the other end of the harness into the receiver. Refer to the installation instructions provided with the receiver for further installation procedures regarding antenna mounting, etc.
Receiver Connections
WIRELESS ZONE NUMBERS VISTA-20P: transmitter zones 9-48 button zones 49-64 VISTA-15P: transmitter zones 9-34 button zones 49-56
RF Receiver Notes
These fields must be enabled for Residential Fire, UL Residential Burglar Alarm, and UL Commercial Burglar Alarm installations.
Figure 11. 5881/5882 RF Receiver (cover removed) Set the following options: *22 RF Jam Option *24 RF House ID Code (if using wireless keypads) for each partition *67 Transmitter Low Battery Report Code *75 Transmitter Low battery restore report code The receiver is supervised and a trouble report is sent (CHECK 100 displayed) if communication between the panel and receiver is interrupted, or if no valid RF signals from at least one supervised transmitter are received within 12 hours. If the receiver is mounted remotely: Place the RF receiver in a high, centrally located area for best reception. Do not locate the receiver or transmitters on or near metal objects. This will decrease range and/or block transmissions. Do not locate the RF receiver in an area of high RF interference (indicated by frequent or prolonged lighting of the LED in the receiver; random flicker is OK). Do not locate RF receiver closer than 10 feet from any keypads to avoid interference from the microprocessors in those units.
Installing a 5800TM Module Use this module only if you are using one or more wireless bi-directional keypads or keyfobs with a wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g., 5883). The 5800TM must be set to address 28 (cut red-W1 jumper). The 5800TM can be used in partition 1 only. For additional information regarding the 5800TM, refer to the 5800TMs instructions. 1. Mount the 5800TM next to the RF receiver (between one and two feet from the receivers antennas) using its accompanying mounting bracket. Do not install within the control cabinet. 2. Connect the 5800TM to the control panels keypad connection terminals as shown on the Summary of Connections diagram and set to address 28. Refer to the table of compatible devices at the back of this manual. Supervised transmitters send check-in signals to the receiver at 70-90 minute intervals. If at least one check-in message is not received from each transmitter within a 12-hour period, the missing transmitter number(s) and CHECK is displayed. ( Hand-held transmitters, e.g., 5802, 5802CP, 5804, 5804BD, 5827, 5827BD, do not send check-in signals.) To be sure reception of the transmitter's signal at the proposed mounting location is adequate, perform a Go/No Go Test, described in the Testing the System section. Install transmitters in accordance with the instructions provided with each. Set 5827, 5827BD, 5804BD wireless keypads to the programmed House ID (field *24), using its DIP switches (5827) or follow the instructions provided with the device. Use *56 or *58 Zone Programming Menu modes to program zone information and enroll transmitters (VISTA-20P: zones 9-48, buttons 49-64; VISTA-15P: zones 9-34, buttons 49-56). Wireless Keys: Use Wireless Key Programming Templates section of the *58 Zone Programming Menu mode to program zone information and enroll each button of the wireless keys used. Once a wireless key is enrolled, it must be assigned to a user before it becomes active. See Adding/Deleting Security Codes section for procedure. ULC NOTE: In accordance with ULC standards, the RF supervision period for the VISTA-20PCN
Use 4146 keyswitch or any N.O. keyswitch. Use only one keyswitch per partition. When using a keyswitch, the zone it is connected to is no longer available for use as a protective zone. Use *56 Menu mode to program the keyswitch zone and assign it zone type 77. Use *80 Menu mode to program the LED functions: program outputs 17 and 18 for system operation zone type 78 (red LED) and 79 (green LED) as appropriate (see Output Device Programming section).
Connecting Relay Modules, Powerline Carrier Devices and Output Triggers
4204/4229 Relay Modules 1. Mount either remotely or in the control panel. 2. Connect each module to the controls keypad terminals and set the device addresses as previously described in the Connecting Keypads and Other Addressable Device section. Use the connector harness supplied with the module. Use standard 4-conductor twisted cable for long wiring runs. VISTA-20P: Up to 16 relays (if no powerline carrier devices are used) VISTA-15P: Up to 8 relays (if no powerline carrier devices are used) 3. Connect the desired field wiring to the unit's relay contact terminals.
For UL installation requirements, refer to the Installation Instructions for the 4204.
Figure 13. 4204 Connections to Control Supervision: 4204 and 4229 modules are supervised against removal. The modules device address is displayed as follows if a module is disconnected from the controls terminals, or if the module cover is removed and the tamper jumper is installed: Alpha: CHECK xx Wire Expansion FAULT xx Wire Expansion ALARM xx Wire Expansion Fixed-Glass: lxx (or 91 if field *199 set for 2-digit display) where xx is the modules address. If communication/tamper failure occurs on a device with zones wired to it, all zones on the device will be displayed in their respective partitions. 1. Install the powerline carrier devices according to the instructions included with each. VISTA-20P: Up to 16 devices (if no relays are used) VISTA-15P: Up to 8 devices (if no relays are used) 2. Use Programming Mode to enter the device house ID in data field*27, and enter the unit code using *79 Output Device menu Mode. 3. See connections diagram in the AC Wiring section for connecting the 1361X10 transformer to the triggers. You must use a 1361X10 Transformer instead of the 1321 Transformer. The 1361X10 Transformer provides AC power to the control panel, and also supplies signals from the control panel through the premises AC wiring to the Powerline Carrier devices (which are plugged into AC outlets). You can then make devices that are plugged into Powerline Carrier devices perform various functions in response to commands you enter at the security system keypads. Canada: Use the PSC04 Powerline Interface as shown below.
Powerline Carrier Devices
Powerline Carrier devices and the 1361X10 Transformer are not UL Listed for fire or burglary functions and are intended for home automation.
(BLUE)
(ORANGE)
(YELLOW)
Type 02 Entry/Exit Burglary #2
Type 03 Perimeter Burglary Type 04 Interior Follower
Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering a sensitive area such as a stock room, drug supply room, etc. Can also be used on a sensor or contact in an area where immediate notification of an entry is desired. Provides an instant alarm if faulted when armed in the Away, Stay, Night-Stay, Instant or Maximum (night) modes. During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a central station report, if desired). Type 06 Usually assigned to a zone containing an emergency button. 24-hr Silent Alarm Sends a report to the central station but provides no keypad display or sounding. Type 07 Assign to a zone that has an emergency button. 24-hour Audible Sends a report to the central station, and provides an alarm sound at the keypad, and an Alarm audible external alarm. Type 08 Assign to a zone containing an emergency button, or to a zone containing monitoring devices 24-hour such as water or temperature sensors. Auxiliary Alarm Sends a report to the central station and provides an alarm sound at the keypad. (No bell output is provided.) Type 09 Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm Supervised Fire produces a pulsing bell output. This zone type is always active and cannot be bypassed. Type 10 Provides entry delay (using the programmed entry time), if tripped when the panel is armed in Interior w/Delay the Away mode. Entry Delay 1 begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit delay zone was tripped first. Bypassed when the panel is armed in the Stay or Instant modes; if armed in Night-Stay mode, zones assigned to zone list 05 (night-stay zone list) are not bypassed when system armed in Night-Stay mode. Type 12 Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a short/open, the Monitor Zone message, "*ALARM*-24 Hr. Non-Burg. -#XXX " (where XXX is the zone number) will be sent to the Central Station. The system keypad will display a check message indicating the appropriate zone (but keypad beeping does not occur). Upon restoral of the zone, the message, "*RESTORE*-24 Hr. Non-Burg. -#XXX " will be sent to the Central Station. The check message will automatically disappear from the keypad dynamically, when the zone restores; a user code + off sequence is not needed to reset the zone. Faults of this zone type are independent of the system, and can exist at the time of arming without interference. Since this is a trouble zone type, do not use this zone type with relays set to activate upon alarm. Type 14 Assigned to any zone with a carbon monoxide detector. 24 Hour Carbon The bell output will pulse when this zone type is alarmed. Monoxide Always active and cannot be bypassed. Monitor Type 16 Provides a fire alarm when zone is shorted, but only after alarm verified. Fire System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent w/Verification short circuit within 90 seconds triggers fire alarm. Provides a trouble response when zone is open. Type 20 Arms the system in Stay mode when the zone is activated. Arm-Stay (BR Pushbutton units send the user number to the central station when arming or disarming. only) User number for button must be assigned. Type 21 Arms the system in Away mode when the zone is activated. Arm-Away (BR Pushbutton units send the user number to the central station when arming or disarming. only) User number for button must be assigned. Type 22 Disarms the system when the zone is activated. Disarm (BR only) User number for button must be assigned. Type 05 Trouble by Day/ Alarm by Night
*38 Confirmation Of Arming Ding
0 = no ding; 1 = confirmation ding after arming system 2 = ding after arming from RF button or RF keypad only Confirmation of arming is 1/2-sec external sounder ding. If 1 selected, ding occurs when closing report is sent, or at the end of Exit Delay. If 2 selected, ding occurs upon reception of the wireless arming command. UL Installations: must be 1 for UL Commercial Burglar Alarm installations.
*33 Alarm Sounder Timeout
0 = No timeout; 1 = 4 min; 2 = 8 min; 3 = 12 min; 4 = 16 min This field determines whether the external sounder will shut off after time allotted, or continue until manually turned off. UL Installations: For residential fire alarm installation, must be set for a minimum of 4 min (option 1); for UL Commercial Burglary installations, must be minimum of 16 min (option 4).
*39 Power-Up In Previous State
0 = always power-up in a disarmed state 1 = assume the system status prior to power down When the system powers up armed, an alarm will occur 1 minute after arming if a zone is faulted. Note that if the previous state was armed Away or Stay, the system will not respond to sensor changes for 1 minute, which allows sensors such as PIRs to stabilize. UL Installations: must be 1 (power-up in previous state) SIA Guidelines: must be 1
*34 Exit Delay
00 - 96 = 0 - 96 seconds; 97 = 120 seconds
VISTA-20PSIA: 45 - 96 = 45 - 96 secs; 97 = 120 secs NOTE: Entries less than 45 will result in a 45-sec delay. The system waits the time entered before arming entry/exit zones. If the entry/exit door is left open after this time expires, an alarm will occur. Common zones use same delay as partition 1. UL installations: For UL Commercial Burglar Alarm (Grade AA) and UL Residential Burglar Alarm installations with line security, total exit time must not exceed 60 seconds. For UL Burglar Alarm installations without line security (Grade A), total exit time must not exceed 120 seconds. SIA Guidelines: minimum exit delay is 45 seconds
Dialer Programming (40 50) *40 PABX Access Code or Call Waiting Disable
Enter up to 6 digits if PABX is needed to access an outside line. Do not fill unused spaces. 09, # + 11 for , # + 12 for #, # + 13 for a pause (2 seconds) To clear entries from field, press 40. If fewer than 6 digits need to be entered, exit by pressing []. Call Waiting: If the subscribers phone service has call waiting (and is not using PABX), enter *70 (# + 11) plus # + 13 (pause) as the PABX entry to disable call waiting during control panel calls. If the subscriber does not have call waiting and is not using PABX, make no entry in this field. NOTES: 1. The call waiting disable feature cannot be used on a PABX line. 2. Using Call Waiting Disable on a non-call waiting line will prevent successful communication to the central station.
0 = disabled (both signals sent); 115 = entry times a 15-second delay. e.g., 1 = 15 seconds, 2 = 30 seconds, etc. Intended for use with Long Range Radio reporting. This field lets you select the time the panel should wait for acknowledgment from the first reporting destination (see 55) before it attempts to send a message to the second destination. Delays can be selected from 0 to 225 seconds, in 15-second increments. This delay is per message. If 0 is entered in this field, the control panel will send redundant reports to both Primary Dialer and LRR. UL Installations: For Fire Alarm and UL Burglar Alarm installations without Line Security (Grade A), the maximum Dynamic Signaling Delay must be no more than 15 secs. For UL Burglar Alarm installations with Line Security (Grade AA), Dynamic Signaling Delay must be 0. Reports will be sent to both the dialer and the LRR.
*48 Report Format (Primary/Secondary)
0 = 3+1, 4+1 ADEMCO L/S STANDARD 1 = 3+1, 4+1 RADIONICS STANDARD 2 = 4+2 ADEMCO L/S STANDARD 3 = 4+2 RADIONICS STANDARD 5 = ADEMCO 10-digit Contact ID 6 = 4+2 ADEMCO EXPRESS 7 = ADEMCO 4-digit Contact ID 8 = 3+1, 4+1 ADEMCO L/S EXP. 9 = 3+1, 4+1 RADIONICS EXP. Select format for primary/secondary phone numbers.
*49 Split/Dual Reporting
0 = standard/backup reporting only (see Backup Reporting below) To Primary No. To Secondary No. 1 = alarms, restore, cancel others 2 = all except open/close, test open/close, test 3 = alarms, restore, cancel all 4 = all except open/close, test all 5 = all all Backup Reporting: All reports are sent only to the primary number unless unsuccessful after 8 attempts. If unsuccessful, the system will make up to8 attempts to send all reports to the secondary number. If still unsuccessful after the 16 attempts, the system displays the COMM. FAILURE message (FC for fixed-word displays).
*55 Dynamic Signaling Priority
0 = Primary dialer first; 1 = Long Range Radio (LRR) first. Intended for use with Long Range Radio reporting. You must also enable field 29, OUTPUT TO LONG RANGE RADIO. Select the initial reporting destination for messages as follows: Primary Dialer First selected (0): If acknowledged before delay expires (see 54), then message will not be sent to LRR. If not acknowledged before delay expires, message is sent to both the Primary Phone No. and LRR. Long Range Radio First selected (1): If acknowledged before delay expires, then message will not be sent to the primary dialer. If not acknowledged before delay expires, message is sent to both the Primary Phone No. and LRR. UL Installations: For UL Commercial Burglary installations that use a DACT and LRR, the DACT must be programmed for priority (option 0).
0 = normal 0 = no 0 = no 1 = alarm 4 = yes 8 = yes 2 = trouble 3 = fault see note 6 Entry 2 = Short + auto restore + vent zone
Zone Conditions Represented in Entries 1-6
Configurable Zone Type Notes 1. Do not use the fault delay option with a configurable zone type if it is set for an entry or exit delay, otherwise unpredictable results may occur. 2. To create an interior type zone, select respond as interior zone type (entry 8, interior type = yes), and set zone response to fault in entries 3-4 to ensure fault displays; do not set as normal, alarm, or trouble. 3. Do not set fire zones to respond as a fault (entries 1-6), otherwise faults will not display unless the [] key is pressed. 4. 4219/4229 modules must use EOLRs or unpredictable results may occur. 5. RF Zones: The open options in entries 1, 3, and 5 are not applicable for RF zones. Use the intact EOL option for normal RF zone conditions and shorted for off-normal RF zone conditions. 6. a. Zone-Doubling/DoubleBalanced: A short on either zone of a zone-doubled pair or on a double-balanced zone causes a tamper condition. b. For double-balanced zones, this entry must be 0. c. For zone-doubled zones, both zones of the doubled pair must be assigned the same response to a short.
ENTRY 3
RF zone normal RF zone N/A
ENTRY 4
Byp. when disarmed Byp. when armed
RF zn off-normal
Response when armed STAY and zone is: Intact EOL Open Shorted 0 = normal 1 = alarm 2 = trouble 3 = fault 0 = normal 4 = alarm 8 = trouble 12 = fault see note 5 Entry 3 = EOL + Open
0 = normal 0 = no 0 = no 1 = alarm 4 = yes 8 = yes 2 = trouble 3 = fault see note 6 Entry 4 = Short + byp. disarmed + byp. armed
ENTRY 5
ENTRY 6
Dial Delay (see field *50) Fault Delay (see field *87)
Response when armed AWAY and zone is: Intact EOL Open Shorted 0 = normal 1 = alarm 2 = trouble 3 = fault 0 = normal 4 = alarm 8 = trouble 12 = fault see note 5 Entry 5 = EOL + Open
0 = normal 0 = no 0 = no 1 = alarm 4 = use delay 8 = use delay 2 = trouble 3 = fault see note 1 see note 6 Entry 6 = Short + dial delay + fault delay
ENTRY 7
Power Reset/ Verification 0 = show alarms 0 = no when armed 4 = power reset after fault & disarmed (with code + 1 = dont show OFF) alarms when armed (show 12 = verification (see zone alarms, trbles, type 16) faults when
disarmed)
ENTRY 8
Use Entry Delay 1/= no 1 = delay = delay 2 Use Exit Delay 0 = no 4 = use exit delay Respond as Interior Type 0 = no 8 = yes see note 2
Display Faults
3 = never show any alarms, trbles, faults Entry 7 = fault display + power reset/verification
Zone Programming Procedure
1. Enter the zone number to be programmed. 2. Make appropriate entries at the prompts. 3. Confirm the serial number of wireless transmitter zones. Start Zone Programming mode by pressing 56 while in Data Programming mode.
SET TO CONFIRM? 0 = NO 1 = YES
Set to Confirm
0 = no; 1 = yes If 1 (Yes) is entered, you will be prompted to confirm each transmitter after entering the serial and loop numbers (at the XMIT TO CONFIRM prompt later in this procedure). We recommend that you confirm the programming of every transmitter.
Enter Zn Num. (00 = Quit)
Zone Number
VISTA-20P: wired 01-08 (and 09-48); wireless 09-48; RF button zones 49-64 VISTA-15P: wired 01-06 (and 07-22); wireless 09-34; RF button zones 49-56 Both Controls: 91 = addr. device report enable; 92 = duress report enable 95, 96, 99 =emerg. zones if zone expanders are used. [] to continue; 00 to quit
Enter the zone number that you wish to program. Zone 10 has been entered in the example display at left. Enter a report code for zone 91 to enable addressable device reporting. Enter a report code for zone 92 to enable duress reporting. 95, 96, 99 are emergency (panic) key zones.
Zn ZT P RC OR
In: L RF: 1
Summary Screen [] to continue
A summary display appears. IN: L appears for wireless zones and indicates input type and loop. IN: AD appears for hardwire expansion zones (AW) and indicates the modules address (AD), which is based on the zone number. HW: RT appears for hardwire zones and indicates configuration (EOL, NO, NC, zone doubling, double-balanced) and response time selection.
Zn ZT P RC In: AD AW: 07 OR Zn ZT P RC HW: RT EL 1
10 Zone Type Perimeter
Zone Type (ZT)
See table below. Each zone must be assigned to a zone type, which defines the way in which the system responds to faults in that zone. Enter the Zone Type code from the list below: Note: If 00 is entered, Delete Zone ? will be displayed.
00 = Not used 01 = Entry/exit #= Entry/exit #= Perimeter 04 = Interior Follower 05 = Day/Night 06 = 24-Hr Silent
*5800 button-type transmitters only
07 = 24-Hr Audible 08 = 24-Hr Aux 09 = Fire 10 = Interior w/Delay 12 = Monitor Zone 14 = Carbon Monoxide 16 = Fire w/Verify
20 = ArmSTAY* 21 = ArmAWAY* 22 = Disarm* 23 = No Alarm Resp 24 = Silent Burglary 77 = Keyswitch 81 = AAV Mon. Zone 90-91 = Configurable
10 Partition Report Code 1st 01 2nd 00 10
Partition No. (P) (VISTA-20P) 1-3 = partition (3 = common); [] to continue
Enter the Partition number for this zone. Partition 1 is shown entered.
Report Code (RC)
First Digit: 1-9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F 00 to disable Second Digit: same as above; [] to continue Enter the report code for this zone, which consists of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, for a report code of 10, enter 01 and 00. For Contact ID, entering any non-zero entry as the first digit enables the report code for this zone. Refer to the System Communication section for information about report codes and formats.
The prompt to confirm appears. This prompt will only appear if the first prompt after entering 58 was answered Yes. To confirm, activate the loop input or button that corresponds to this zone. The system checks for duplicate. If a duplicate exists, a long error beep will sound. Press [#] to back up and re-enter the serial and/or loop number.
Installation and Setup Guide If Serial or Loop Numbers do not match after activating the transmitter [] to continue
If the serial/loop number combination transmitted does not match the serial and loop number entered, a display similar to the one below will appear. If the loop number does not match, it will also be displayed. If so, activate the transmitters loop input or button one or more times. If a match is still not obtained (i.e., summary display does not appear), press the [#] key twice and enter the correct loop input or, if correct, press [#] again and then enter the correct serial number.
Entd Rcvd
A022-4063 A022-4064
Zn ZT P RC In L RF: 1s
Note that an s indicates that a transmitters serial number has been enrolled.
If the serial number transmitted matches the serial number entered, the keypad will beep 3 times and a summary display will appear, showing the programmed information for that zone. Press [] to begin programming the next zone. See first Summary Screen prompt paragraph on previous page. To exit this mode, enter 00 at the Summary Screen prompt.
Wireless Key Programming Templates
This procedure programs the wireless keys, but a key is not active for arming/disarming until it is assigned to a user number (see System Operation section, assigning attributes command). Enter this mode by pressing the D key while at the *58 Menu mode Summary Screen. The following prompts appear.
TEMPLATE ? 16
Template Number
13 = 5804 templates; 46 = 5804BD templates Enter Template number 16 (see chart on next page). See the defaults provided for each template in the chart that follows these procedures. Select from templates. Press [] to display template (1 shown selected). NOTE: If necessary, press [#] to back up and re-enter template number. Press [#] if you want to return to *58 Menu mode summary screen.
Template Display
When [] is pressed, the selected template will be displayed. Top line of display represents loop numbers; bottom line represents zone type assigned for each loop. Press [] to accept template.
PARTITION 1
ENTER START ZONE
Partition
VISTA-20P. 1 = partition 1; 2 = partition 2; 3 = common partition Enter the partition in which the key is to be active, then press [] to continue.
Start Zone Number
The system will search for the highest available consecutive 4-zone group (the four zones in the case of the 5804 and 5804BD), and display the lowest zone number of the group. If you want to start at a different zone, enter the zone desired, and press []. If that zone number is displayed, the system has the required number of consecutive zones available, beginning with the zone you entered. If not, the system will again display a suggested zone that can be used. If the required number of consecutive zones is not available at all, the system will display 00. To quit this mode and return to *58 Menu mode, enter 00 at this prompt. Press [] to accept.
XX MODULE ADDR 07-15 yy
Module Address (prompt appears if relay is selected)
07-15 = predefined address [] to continue Enter the predefined address for this module as listed below. Make sure the modules DIP switches are set to the selected address. Module Addresses
Address 15 Module 1st 4229 (with zones 09-16) 2nd 4229 (with zones 17-24) 3rd 4229 (with zones 25-32) 4th 4229 (with zones 33-40) 5th 4229 (with zones 41-48) 1st 4204 2nd 4204 3rd 4204 4th 4204 These addresses apply to VISTA-20P only.
XX REL POSITION 1-4 zz
Relay Position
1-4 = relay position [] to continue This is the actual (or physical) relay number with respect to the Relay Module upon which it is located. For 4204 modules, relay numbers are 1-4. For 4229 modules, relay numbers are 1-2. The system returns to the Output Number prompt for programming the next device.
*80 Menu Mode: Defining Output Functions
Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components: Output Definition Components
Component Output Function No. Activated By Event Partition Output Action Description A reference number that defines an outputs characteristics. Determines whether the initiating event occurs on a zone, a zone list, or a zone type. Event that triggers the output action. Can be an event occurring on a specific zone number or a zone list, or a specific zone type. If the output is activated by zone type, this defines the partition in which the programmed event is to cause the device action. Defines the action of the relay/X-10 device when the defined event occurs. Can close for 2 seconds, stay closed until reset, continuously pulse (1-second close-open-close-open, etc.), toggle the device state, or activate for a defined duration (set in data field *177). Assigns this function to a specific output number (defined in *79 Menu Mode). This is the output number that will perform this function upon the triggering event. Note that each defined function is associated with only one output number. This means that if more than one output device needs to perform this particular function, you need to define another output function number with the same attributes, but assign the appropriate output number. (i.e. output devices can be assigned more than one function number, but each function number can only be assigned a single output number.
Output No.
For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to output number 2 (as programmed in *79 Menu Mode), program the following in *80 Menu Mode: Prompt Output Funct. # Activated By: Enter Zn No. Output Action Output Number 80 Menu Mode
Output Funct. # (00 = Quit) 01
EXIT ALARM
CHECK ALARM 1xx FAULT 1xx CHECK 1xx
CHECK 1xx 1xx 1xx 91
SYSTEM LO BAT LO BAT
BAT BAT
TELCO FAULT
Busy-Standby Mode m Comm no display
dl CC no display
Comm. Failure Open Circuit Long Rng Trbl Bell Failure RCVR Jam KEYPAD LOW BAT Phone Okay Dialer Off Test in Progress Upload Completed Upload Failed
FC OC bF 00 BAT Cd dO dd dC dF
Testing the System
About Test Procedures
After the installation is complete, you should perform the following tests: System Test: Checks that all zones have been installed properly and the system responds to faults. Dialer Test: Checks that the phone connection to the central station is working properly. Go/No Go Test: Checks that transmissions can be received from transmitters. Should be performed before permanently mounting transmitters. RF Sniffer Mode: Checks that RF transmitter serial numbers have been properly enrolled. Battery Tests: Automatic battery tests are performed by the system.
System Test
With the system in the disarmed state, check that all zones are intact (not faulted). Doors and windows with contacts should be closed, PIRs should be covered (use a cloth to mask them temporarily if necessary). If a NOT READY message is displayed, press [] to display the faulted zone(s). Restore faulted zone(s) if necessary, so that the READY message is displayed. 1. Enter Installer Code + 5 [TEST] , then press 0 at the prompt to start Walk Test mode.
1=DIAL, 0=WALK (no special display on Fixed-Word keypads)
The following will be displayed and a Contact ID report will be sent (code 607):
TEST IN PROGRESS (dd displayed on Fixed-Word Display Keypads)
2. Upon entering the system test mode, the outside sounder should sound for 1 second. If the backup battery is discharged or missing, the sounder may not turn on and a LOW BATTERY report will be transmitted with a TEST report. The keypad will beep about every 40 seconds as a reminder that the system is in the Test mode. NOTE: Wireless motion detectors (Passive Infrared units) will send signals out only if they have been inactive for 3 minutes (conserves battery life). 3. Test all sensors using the procedure described in the Users Guide Testing the System section. 4. After checking sensors, turn off the test mode by entering installer code + OFF. NOTE: Test mode automatically ends after 4 hours. During the final 5 minutes (after 3 hours 55 minutes of Test mode), the keypad emits a double-beep every 30 seconds to alert that the end of Test mode is nearing.
Dialer Communication Test and Periodic Test Reports
1. Enter Installer Code + 5 [TEST], then press 1 at the prompt to start the Dialer Test.
The following will be displayed (accompanied by 2 beeps) if test is successful:
PHONE OKAY (Cd displayed on Fixed-Word Display Keypads)
A Contact ID report will also be sent (code 601) If the dialer test is unsuccessful, COMM FAILURE (or FC) is displayed. 2. Enter Installer code + OFF to clear the display and exit. Automatic Periodic Test Report The system can be set to automatically send test reports (enabled in field *64; Contact ID code 602) at specified intervals. Frequency of the reports is set in Scheduling mode (event 11) or by the following key commands: installer code + [#] + 0 + 0 = test report sent every 24 hours
installer code + [#] + 0 + 1 = test report sent once per week installer code + [#] + 0 + 2 = test report sent every 28 days
Each mode sets schedule 32 (VISTA-20P) or schedule 08 (VISTA-15P) to the selected repeat option; the first test report is sent 12 hours after command. To ensure that test reports are sent at the times expected, set the Real-Time Clock to the proper time before entering the test report schedule command. Automatic Standby Battery Tests 1. An automatic test is conducted every 3 minutes to ensure that a standby battery is present and properly connected. If a battery is not present or is not properly connected, a LOW BATTERY message is displayed and, if so programmed, will be reported to the central station. 2. A battery capacity test is automatically conducted for 2 minutes every 4 hours, beginning 4 hours after exiting the Programming mode or after powering up the system. In addition, entry into the Test mode will also cause a battery capacity test to be initiated. If the battery cannot sustain a load, a Low Battery message is displayed and, if so programmed, will be reported to the central station.
Specifications & Accessories
Security Control
1. Physical: 12-1/2 W x 14-1/2 H x 3 D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, ADEMCO 1321 (in U.S.A.) RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type). Charging Voltage: 13.8VDC. ALARM SOUNDER: 12V, 2.0 Amp output can drive 12V BELLS or can drive one or two 702 (series connected) self-contained 20-watt sirens. Do not connect two 702s in parallel. AUXILIARY POWER OUTPUT: 12VDC, 600mA max. NOTE: For UL installations, Alarm Sounder plus Auxiliary Power currents should not exceed 600mA total. FUSE: Battery (3A) No. 9012 3. Communication: FORMAT SUPPORTED: ADEMCO Express: 10 characters/sec, DTMF (TouchTone) Data Tones, 1400/2300Hz ACK, 1400Hz KISSOFF. ADEMCO Low Speed: 10 pulses/sec, 1900Hz Data Tone, 1400Hz ACK/KISSOFF. Radionics/SESCOA: 20 pulses/sec, 1800Hz Data Tone, 2300Hz ACK/KISSOFF. Can report 0-9, B-F Ademco Contact ID 10 characters/sec., DTMF (TouchTone) Data Tones, 1400/2300Hz ACK, 1400Hz KISSOFF. LINE SEIZE: Double Pole RINGER EQUIVALENCE: 0.1B FCC REGISTRATION No.: 5GBUSA-44003-AL-E 4. Maximum Zone Resistance: Zones 18 = 300 ohms excluding EOLR standard zones
Tags
LW310 Kd-g230 42PG60 VH6-II Chorus A8 PSR-83-PSR-82 PS-5000 HD Ryobi P231 WLI-PCM-l11GP CHM189W VT 9113 CM907 LA40B750 RX-E5S IC-756PRO3 Cyclecomputing A4 HK 3490 Platinum Radio Portable Strvx250 T2130-24 SR4021 HP 500 Suite MP5000 M2N68 Plus Elura 90 KX-TG7100E W1300 32LX1D WXT-850 Breadmaker Touch 332 700DXN Tagliasiepi SR-L3916BSS Bread XXL 1710N P4I45G 4351FCT MPC-206 WV-CU550CJ DRC-BT30 800SI CVA-1005 KV-25DA1 DV-HRD2 FX-570D League XR-6700RDS IRC3580-J1 Thermo LE40B653t5W EM 3732 S2-250 Dect 623 HD-FOX T2 Thomson RR95 DMC-LS2 Workstation Edition Studioworks 700E YP-55V 1100A DS-330 KV-28FQ75U 60AZ-AR XR 400 LN705 KDC-W7144UY Krups FNA2 P4S-X Switch 550WP Dead 2 MRD-M300 Laserjet 2840 PM645VXI Roomba 510 RX425 Kinetiz 7T PM655 Hillsfar MB-D10 Optigo OP10 SFP30BF1 Desktop PC Netbox HD Series2 DT SEW 67A VGN-FE650G KRF-V4060D Perfecta Officejet 6210 Logmein PRO 250 DF IC-2710H VR9261 Review Elyos V150
manuel d'instructions, Guide de l'utilisateur | Manual de instrucciones, Instrucciones de uso | Bedienungsanleitung, Bedienungsanleitung | Manual de Instruções, guia do usuário | инструкция | návod na použitie, Užívateľská príručka, návod k použití | bruksanvisningen | instrukcja, podręcznik użytkownika | kullanım kılavuzu, Kullanım | kézikönyv, használati útmutató | manuale di istruzioni, istruzioni d'uso | handleiding, gebruikershandleiding
Sitemap
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101







