Reviews & Opinions
Independent and trusted. Read before buy Bentel Security J424!

Bentel Security J424


Bookmark
Bentel Security J424

Bookmark and Share

 

Bentel Security J424About Bentel Security J424
Here you can find all about Bentel Security J424 like manual and other informations. For example: review.

Bentel Security J424 manual (user guide) is ready to download for free.

On the bottom of page users can write a review. If you own a Bentel Security J424 please write about it to help other people.
[ Report abuse or wrong photo | Share your Bentel Security J424 photo ]

 

 

Manual

Preview of first few manual pages (at low quality). Check before download. Click to enlarge.
Manual - 1 page  Manual - 2 page  Manual - 3 page 

Download (English)
Bentel Security J424 - Installation, size: 2.5 MB

 

Bentel Security J424

 

 

User reviews and opinions

<== Click here to post a new opinion, comment, review, etc.

No opinions have been provided. Be the first and add a new opinion/review.

 

Documents

doc0

CONVENTIONAL F I R E PA N E L S

INSTALLATION MANUAL

ISO 14001 9191.BNT2 ISO 14001 IT-52588 ISO 9001 9105.BNT1 ISO 9001 IT-52587 OHSAS 18001 OHSAS 18001 9192.BSEC IT - 60983
This Control panel can be programmed using the respective Software J400 release 1.1 or higher. BENTEL SECURITYsrl shall not assume the responsibility for damage arising from improper application or use. This Control panel has been designed and manufactured to the highest standards of quality and performance. Installation of this Control panel must be carried out strictly in accordance with the instructions described in this manual, and in compliance with the local laws and bylaws in force The J424 and J408 Control panels comply with the essential requirements of standards EN54-2; EN54-4; EN12094-1. EN12094-1 certification shall be deemed void if the J400-EXT Extinguishment Module is not installed in the Control panel. BENTEL SECURITY srl reserves the right to change the technical specifications of these products without prior notice.
BENTEL SECURITY s.r.l. Via Gabbiano, 22 - Zona Ind. S. Scolastica 64013 Corropoli (TE) - ITALY
BENTEL SECURITY s.r.l. Via Gabbiano, 22 - Zona Ind. S. Scolastica 64013 Corropoli (TE) - ITALY - CPD - - CPD - - CPD - - CPD - 0195 (J408-2) (J408-4) (J408-8) (J424)
0051-CPD-0197 (J400-EXT in J424) 0051-CPD-0196 (J400-EXT in J408-2/J408-4/J408-8) EN12094-1 Electrical automatic control and delay device Environmental class A Protection level IP30 Flooding zones 1 to 4 CO2, inert gas, halogenate hydrocarbon Expected Options: Delay of extinguishing signal Monitoring of status of components Emergency hold device Control of flooding time Response delay activated condition: maximum 3 s
EN 54-2:1997+A1:2006 Control and indicating equipment for fire detection and fire alarm systems for buildings. EXPECTED OPTIONS Dependencies on more than one alarm signal: type C Delays to outputs Test condition Output to fire alarm devices Output to fire alarm routing equipment maximum 1 s
Response delay triggering of outputs:

Recycling information

BENTEL SECURITY recommends that customers dispose of their used equipments (panels, detectors, sirens, and other devices) in an environmentally sound manner. Potential methods include reuse of parts or whole products and recycling of products, components, and/or materials.
For specific information see:
www.bentelsecurity.com/en/environment.htm Waste Electrical and Electronic Equipment (WEEE) Directive In the European Union, this label indicates that this product should NOT be disposed of with household waste. It should be deposited at an appropriate facility to enable recovery and recycling.
www.bentelsecurity.com/en/environment.htm

CONTENS

INTRODUCTION
The J424 and J408 Control panels Accessory Items Description Inputs Outputs Operating features Interface Extinguishment Module Access to Signalling and Commands Power Supply
INSTALLING THE CONTROL PANEL

IDENTIFICATION OF PARTS

The Status LEDs Description of Parts Description of the Control keys
Installing accessory boards Installing Extinguishment Modules Installing Expander Module Kit (for J424 ONLY) Display Module (for J424 and J400-REP ONLY) Installing Repeaters Installing the Control panel Description of the Terminals Main Board and Expander Board terminals Main Board Terminals Extinguishment Module Terminals The System Wiring Connecting Fire Detectors Connecting Call-points Connecting Gas Detectors Connecting Signalling Devices Connecting a Repeater Connecting Extinguishment Modules Connecting a Dialler Connecting a Power Supply Connecting the Mains Supply Thermal Probe Maintenance Testing the Extinguishment Module

Figure 3 Maximum configuration of the J408 Control panel
Description Anchor for 230 V power supply wires Switching power supply screws Switching power supply/Battery charger Switching power supply support Batteries (NOT supplied!): J408 = two 7 Ah @ 12 V J424 = two 17 Ah @ 12 V Expander no. 1 (accessory item) Bag containing keys, resistors and diodes Flat cable (accessory item): for the Expander Module no. 1 to Expander Module no. 2 connection Thermal probe Expander Module no. 2 (accessory item) Flat cable(accessory item): for the Expander Module no. 1 to Main board connection Flat cable (accessory item): for the Extinguishment Module to Main board connection Extinguishment Module no.1 (accessory item)

P. 31 32

Description Flat cable (accessory item): for the Extinguishment Module no. 1 to Extinguishment Module no. 2 connection Flat cable (accessory item): for the Display Module connection Extinguishment Module no.2 (accessory item) Wire run

F 6.3A/25V B+ L B GND +V

F 2A/25V

P. 35 36

Description Anchor screw location holes Chased cable conduit entry RS485 Interface Soldered Earthing screw
Figure 4 Maximum configuration of the J400-REP Repeater: a) backplate; b) frontplate (inside view)
Description Battery output voltage control output (connected at factory) Thermal probe jack Switching-power-supply jack (connected at factory) Buzzer Terminal board Extinguishment Module anchor holes Address Jumper: // = Extinguishment Module no. 1 oo = Extinguishment Module no. 2 Terminal board Cable: connects the Switching power supply to the Main board (connected at factory) Switching-power-supply anchor Switching-power-supply closure rivet Mains indicator LED Switching-power-supply anchor hole Switching-power-supply output voltage control input (connected at factory) Fine trimmer for the Switching-power-supply output Voltage Auxiliary power-supply terminals (27.6 V) Mains power terminals (230 V / 50 Hz) Switching-power-supply screws Switching-power-supply fuse protects against overload: J408 = F 2A 250V J424 = F 3.15A 250V Jack for Extinguishment Module nr. 2 or the Display Module Microprocessor Jack for the Main board or Display Module Reserved Jumper DO NOT REMOVE Battery jacks Jumper for Ground (Earth) fault detection: // = Ground (Earth) fault monitored oo = Ground (Earth) fault NOT monitored Jumper to be REMOVED when connecting a 4-20 mA gas detector to terminal Z1 Jack for Extinguishment Module nr. 1 or the Display Module Expander Module jack Programming Jumper: PRG PRG o O Programming O Programming O Enabled O Disabled o Expander Control board jack (connected at factory) RS232 Serial Port

AC/N F 2A/25V AC/L FG

Figure 5 Identification of Parts: a) Main Board (2 or 4 zones); b) 8-zone Main Board; c) Extinguishment Module; d) J408 Control panel Switching-power-supply
Description Expander Module anchor holes (4) Terminal strip Address Jumper: // = Expander Module no. 1 oo = Expander Module no. 2 Expander Control Board anchor holes (4) Jack for the Expander Control Board to Expander Module connection Display Module anchor holes (5) Jack for the connection between the Display Module and the consecutive peripheral device Jack for the connection between the Display Module and the preceding peripheral device Address Jumpers Terminal strip Buzzer Jack for the Expander Control board (zones 17 to 24) Jack for the Expander Control board of zones 9 to 16 Jack for the Expander Control board of zones 1 to 8 Display module Programming Jumper: // = Programming Enabled oo = Programming Disabled Jack for the connection between the Expander Module and the consecutive peripheral device Jack for the connection between the Expander Module and the preceding peripheral device or Main Board Expander Control Board jack
Figure 6 Identification of Parts: a) Expander Module; b) Expander Control Board; c) Display Module; d) RS485 Repeater Interface; e) J424 Control panel Switching-po wer-supply
LED ON Electro- Glowing indicates Extinguishment in course valve Pre Ext. Manual Ext. Disab. Ext. Pres. Switch Logic Unit Disable Extinguish. Disable Manual Extinguish. Disable Automatic Extinguish.
Fault Fast blinking indicates power supply failure to the electrovalve connected to output EV, or that the latter is either open or shorted Glowing indicates Pre-Extinguishment in course. Fast blinking indicates that terminals [+] and [] Fast blinking indicates that alarms have been of output PR are either disconnected or shorted generated in some of the zones programmed for activation of the Extinguishment Module. Glowing indicates that input EM has been activa - Fast blinking indicates that terminals [+] and [] ted of input EM are either disconnected or shorted Glowing indicates that input IE has been activa- Fast blinking indicates that terminals [+] and [] ted of input IE are either disconnected or shorted Glowing indicates that the input PS has been ac- Fast blinking indicates that terminals [+] and [] tivated, due to low extinguishant gas pressure of input PS are either disconnected or shorted Fast blinkingindicates blocked Extinguishment Board Glowing indicates Extinguishment is inhibited Glowing indicates Manual Extinguishment is inhibited Glowing indicates that Automatic Extinguishment is inhibited
Table 1 (continued from page 9) Description of the LEDs
Description of the Control keys
The Control panel keys can be activated by Keyswitch and PIN Code Users ONLY (Access level 2 Key tur-
ned in keyswitch or PIN Code entered refer to Access to Signalling and Commands), unless otherwise stated.

7. Set the Display Module Address, as described in the Display Module section under PROGRAMMING FROM THE CONTROL PANEL
Figure 13 Connecting an LCD Module to a Control panel: a) without Extinguishment Modules; b) with ONE Extinguishment Module; c) with TWO Extinguishment Modules ;6) Display Module; 9) Main Control Board; 13) Main Board; 28) Extinguishment Module nr. 1; 30) Flat cable for the Display Module connection; 31) Extingui shment Module nr. 2.

c) 103

103 104

103 107

Figure 12 Installing the Display Module: 101) and 105) nuts; 102) glass plate; 103) and 107) soldered screws; 104) Brass tapped spacers; 106) Plastic spacers; 108) Protective film.

Installing Repeaters

Installing the Control panel
Work carefully through the following steps (see the Figures on pages 10, 12 and 14). 1. Remove the screws (4) and open the Control panel. 2. Drill the anchor screw holes 9.
+ The Display Module (if used) must be installed before the Repeaters.
Repeaters can be wall mounted, or flush mounted to an BL08 outlet box (or similar). Work carefully through the following steps. 1. Lay the connection cables (refer to Connecting Repeaters). 2. Remove the screws (4) and open the Control panel. 3. Take out the bag 22 containing the Repeater panel Keys (Access Level 2). 4. If necessary, install the Display Module as described in the Display Module section. 5. If you are flush mounting the Repeater, go to step 7. If you are wall mounting the Repeater, drill the anchor screw holes 33. 6. Pull the wires through the wire entry 34, then, using the anchor screws, secure the Repeater to the wall. 7. Complete the connections to the terminal board 77 of the RS485 Interface (part nr. 35), as described in the Connecting Repeaters section. 8. Using the jumpers 76 of the RS485 (part nr. 35), set the Repeater Address, as per the following Table: Repeater nr. 1 IN OUT IN OUT Jumpers IN IN OUT OUT
! Check for water pipes and electrical wiring before drilling.
3. If necessary, using a hammer or similar tool, remove the surface conduit wire knockouts 1. conduit union with must be + The cableHB Flame Class (orthe case lock nuts.secured by higher) 4. Pull the wires through the chased wire entry 12 then, using the anchor screws, secure the backplate to the wall.
Description of the Terminals
This section describes the Control panel terminals. n Main Board and Expander Board terminals [Z1]. [Z8] Supervised/Bypassable detection zones. Detection device terminals for Fire detectors, Call points, Gas detectors, etc. The Control panel will consider the zone: Open when the voltage is between 27.6 V and 26.31 V; In Standby when the voltage is between 26.31 V and 17.15 V; In Alarm when the voltage is between 17.15 V and 2.82 V; Shorted when the voltage is between 2.82 V and 0 V. If the Call point priority option has been enabled (refer to PROGRAMMING FROM A PC), the Control panel will distinguish between Alarms generated by Detectors and Alarms generated by Manual Call Point, as follows: Detector Alarm when the voltage is between 17.15 V and 13.15 V; Call point Alarm when the voltage is between 13.15 V and 2.82 V. The status thresholds can be programmed individually for each zone, in this way, it will be possible to compensate for voltage drops caused by the connections. Up to 30 devices can be connected to each zone. One 4-20 mA Gas detector can be connected to zone Z1 of the Main Board and the Expander Module, as described in the Connecting Gas Detectors paragraph.

Voltage on the zone terminal concerned drops below the Pre-Alarm threshold, that is, as long as the Alarm threshold value has not been exceeded in the meantime.
If the Non-Silenceable R Output option is DISABLED, it will be possible to Silence (force to standby) the Repeat Output of the zone concerned. Repeat Outputs will hold standby status for the programmed Silence Time. If Alarm conditions are present when the Silence Time expires, the Repeat Output will re-activate. Up to 0.1 A can circulate on each Repeat Output. R8 accept + Outputs R1, R2,.,ONLY. devices that operate within SELV limits
+ The OC Output accepts devices that operate within SELV limits ONLY.
[DL] Supervised/Bypassable Dialler Output This Output is for Dialler activation. Operating principles This Normally-Open Output (open-collector) will: pull down to 0 V (negative) when the Alarm Signalling Delay expires (refer to DL Output under Outputs in the PROGRAMMING FROM A PC section); restore to standby when the Control panel Resets. Activation of the DL Output will be indicated by Glowing on the Telecom LED. Short-circuit or power supply interruption on the DL Output will be indicated by fast blinking on the Disab./Fault Telecom LED. The DL Output can be disabled by means of the Disab./Fault Telecom key. Disablement of the DL Output will be indicated by Glowing on the Disab./Fault Telecom LED. If the DL Output is disabled, it will be unable to activate in the event of alarm. Up to 0.1 A can circulate on the DL Output.
Output accepts + The ALARM limits ONLY. devices that operate within SELV TROUBLE Silenceable Trouble Output This Output is for Trouble signalling. Operating principles in Standby status, terminal [C] closes to terminal [NC]; in Trouble status, terminal [C] will close to terminal [NO] (refer to Trouble in the INTRODUCTION). connect + DO NOTaudible orEN54 E, J or C rated devices (visual, telephone signalling devices) to the TROUBLE output. Up to 5 A can circulate on the TROUBLE Output. the power + The TROUBLE Output will activate whenand battery supply to the Control panel fails (Mains power supply). The TROUBLE Output accepts devices that operate within SELV limits ONLY.
+ The DL Output accepts devices that operate within SELV limits ONLY.
PL Power Loss Output This Output is for Power loss signalling. Operating principles This Normally-Open Output will: pull down to 0 V (negative) in the event of total power failure (Mains and battery power supply); restore to standby when the power supply conditions return to normal. Up to 1 A can circulate on the PL Output. Output accepts + The PLlimits ONLY. devices that operate within SELV ALARM Silenceable Alarm Output This Voltage free contact can be used for the connection of devices which cannot be connected directly to NAC1 or NAC2. Operating principles: in Standby status, terminal [C] closes to terminal [NC]; in the event of an Alarm, terminal [C] will close to terminal [NO], as per programming (refer to ALARM Output under Outputs in the PROGRAMMING FROM A PC section). The ALARM Output will restore to standby when the Control panel resets. connect + DO NOTaudible orEN54 E, J or C rated devices (visual, telephone signalling devices) to the ALARM Output. If the NON-Silenceable option of the ALARM Output has been DISABLED (refer to ALARM Output under Outputs in the PROGRAMMING FROM A PC section), it will be possible to Silence (force to standby) this Output. The ALARM Output will hold standby status for the programmed Silence Time. If Alarm conditions are present when the Silence Time expires, the ALARM Output will re-activate. Up to 5 A can circulate on the ALARM Output.

ALARM ZONE 15:46 18/10/2004
The top line on the display will show the event (refer to the DESCRIPTIONS column in Table 2), the bottom line will show when the event occurred (Time and Date). 3. Use or to scroll up and down the event list, use to view the event details (see the DETAILS column in Table 2).

ZONE 01 Warehouse

4. Repeat the previous step to continue viewing or, press Esc to step back.
This section describes the warnings signalled on the Control panel LEDs and actions that can be taken during the various phases of a fire alarm.
The Ack./Evac., Silence and + be used during Access Level 2Reset buttons can only. Test ON (glowing) indicates that at least one Zone is in Test status. The zones in Test status can be viewed on the Disabled/Fault/Test LEDs. Disab. ON (glowing) indicates that at least one zone has been DISABLED, therefore, it will be unable to trigger ALARMS. The DISABLED zones can be viewed on the Zone Alarm LEDs. Telecom ON (glowing)indicates that the Dialler has been activated. Mains (GREEN) OFF indicates Mains failure. Mains failure may be due to local black-out in the area, if this is not the case, you must call your installer for service. IMPORTANT: The Control panel will be powered by the batteries during black-out, however, if Mains failure lasts for many hours the batteries may empty. Fault ON (glowing) indicates that one or more faults have been detected. The Fault types can be viewed on the respective LEDs. Logic Unit ON (glowing) indicates that the Control panel is blocked. Call your installer for service. 24V/24R Fast blinking indicates short-circuit. Call your installer for service. Battery ON (glowing) indicates that the batteries are low or disconnected, therefore, in the event of a black-out will be unable to power the Control panel. Allow the batteries to recharge for several hours, if the condition continues, you must call your installer for service. Ground ON (glowing) indicates a Ground fault. Call your installer for service. Periph. Fast blinking indicates communication trouble with the peripherals (Expander module, Extinguishment module, LCD Module, Repeater panel, Power station),. Call your installer for service. Mains (Amber) Normally Off. This LED will switch On in the event of Mains Failure. Mains Failure events in memory will be signalled by slow blinking. Silence ON (glowing) indicates that the Alarm signalling devices have been silenced by means of the Silence button. To re-enable the devices, press the Silence button again. Silenced devices will be re-enabled automatically in the event of a new ALARM.

Connect to the earth conductor

24V RS485 Repeater panel

Figure 17 Wiring diagram of a Repeater connection n Connecting Signalling Devices NAC1, NAC2 and ALARM outputs are for the alarm signalling device connections. NAC1 and NAC2 can be set up to signal pre-alarm and alarm conditions (refer to Outputs under PROGRAMMING FROM A PC). The wiring diagram in Figure 18 shows two warning lamps and the flasher of an outdoor signalling device (STROBE terminals) connected to NAC2, and two fire bells and the horn of an outdoor signalling device (HORN terminals) connected to NAC1. This type of connection makes it possible to diversify pre-alarm from alarm signalling. For example, NAC2 will not activate during the pre-alarm phase, whereas, NAC1 will activate every 6 seconds for 2 seconds. NAC1 and NAC2 will always be active during alarm status. 1/4 W resistor (109) must + A 3900 ohm,the [+] and [] terminals of be connected between the last de-
vice connected to NAC1 and NAC2. A 1N4007 diode (114) (or similar) must be connected between the [+] terminals of devices connected to NAC1 and NAC2 and the [+] terminals of the latter.
n Connecting a Repeater Connect the 24V, , + and M terminals to the respective terminals on the Main Board of the Control panel, as shown in Figure 17. length connected the + The maximum wirepanel must not exceed RS485 terminals of the Control 1000 metres. Connect the - terminal of the Repeater to the Main Earth wire.

Fire bell + 114

Warning lamp 114 +

FIRE ALARM

Figure 18 Wiring diagram of Signalling devices: 109) 3900 ohm, 1/4 W EOL Resistor (orange-white-red-gold); 114) 1N4007 Diode or similar

STROBE

Outdoor hornstrobe
Manual Extinguishment Control Buttons
Inhibit Extinguishment Control Buttons
n Connecting Extinguishment Modules The wiring diagram in Figure 19 shows an Extinguishment Module connected to the Control panel. The EM inputs (Manual Extinguishment) and IE inputs (Inhibit Extinguishment) accept Normally-Open control buttons with 680 ohm contact resistance. Wiring description: Connect a 3900 ohm, 1/4 W resistor (109) between terminal [NO] and terminal [C] of the last control button. The PS input accepts pressure switches with Normally-Open output and 680 ohm contact resistance. Wiring description: Connect a 680 ohm resistor (111) between one of the pressure switch terminals and the [+] terminal of the PS input. Connect (as near as possible to the last pressure switch connected to the PS input) a 3900 ohm, 1/4 W resistor (109) in parallel to the [+] and [] terminals of the PS input. Extinguishment Modules are unable to supply the high current draw required by Electrovalves, therefore, installation of an external Power Station is required. Wiring description: The Extinguishment Module is unable to supply the current draw of the PR and AE Outputs, therefore, it will be necessary to connect the 24P input to the Switching Power Supply of the Control panel, or to an external Power station. The PR output (Pre-Extinguishment) and AE output (Activated Extinguishment) accept signalling devices that operate at 24V. Wiring description: Connect (as near as possible to the last device connected to the output) a 3900 ohm, 1/4 W resistor (109) in parallel to the [+] and [] terminals of the output. Connect a 1N4007 diode or similar, between the positive inputs of the devices connected to the PR and AE, and the [+] terminals of the latter.

Reset Inhibit Time This is the amount of time that must elapse from the point at which the Extinguishment Module is enabled to the point at which the module may be reset. If the reset is performed during the Reset Inhibit Time, the Control panel will reset all systems (except for the activated Extinguishment Module) for a few seconds, after which it will return to an alarm condition. Accepted values: 0 to 30 minutes, steps of 1 minute. Default value: 0 minutes. n Zones This section will allow you to select the Zones which will activate the Extinguishment phase. n Manual Extinguishment Input This field will allow you to set up the Standby status of the Manual Extinguishment Input ([EM] terminals). Normally Closed If this option is DISABLED (at Default), there must be a 3900 ohm resistance across the [+] and [] terminals of the EM Input during Standby status. When this option is enabled, the resistor in standby must be 680 ohm. n Disable Extinguishment Input This field will allow you to set up the Standby status of the Disable Extinguishment Input ([IE] terminals). Normally Closed If this option is DISABLED (at Default), there must be a 3900 ohm resistance across the [+] and [] terminals of the IE input during Standby status. When this option is enabled, the resistor in standby must be 680 ohm. n Pressure Switch Input This field will allow you to set up the Standby status of the Pressure Switch Input ([PS] terminals). Normally Closed If this option is DISABLED (at Default), there must be a 3900 ohm resistance across the [+] and [] terminals of the PS input during Standby status. When this option is enabled, the resistor in standby must be 680 ohm.
Enrolling: Power Supply Stations
The Power Supply Stations page will allow you to enrol and set up Power Supply Stations, as follows. Enrol the Power Supply Stations (if installed). A tick () indicates that the respective Power Supply Station is part of the system. Description This 16 character field will allow you to assign a label to the respective Power Supply Station. For example, it may be useful to assign the name of the area where the device is located. The assigned label will identify the Power Supply Station in all the operations it is involved in.
Enrolling: Repeaters and LCD Modules
The Repeaters and LCD Modules page will allow you to enrol Repeater panels and LCD Modules, as follows. Enrol the Repeater panels and Display Modules (if installed). A tick () indicates that the respective device is part of the system. Description This 16 character field will allow you to assign a label to the respective device. For example, it may be useful to assign the name of the area where the device is located. The assigned label will identify the device in all the operations it is involved in.
n Thresholds This Control panel can detect whether its Zones are Shorted, Open or in Alarm status by measuring the voltage on the respective Zone terminals. The Thresholds are the voltage values that cause the Zones to switch from one status to another, as follows. Open/Standby The Control panel will consider the Zone in OPEN status when the voltage on its terminals exceeds the value programmed in this field. The Control panel will consider the Zone in STANDBY status when the voltage on its terminals ranges between value programmed in this field and the value programmed in the Standby/Auto.Alarm field. Standby/Auto.Alarm If the Call point Priority option has been ENABLED, the Control panel will consider the Zone ALARM status when the voltage on its terminals ranges between the value programmed in this field and the value programmed in the Auto.Alarm/Manual Alarm field. If the Call point Priority option has been DISABLED, the Control panel will consider the Zone ALARM status when the voltage on its terminals ranges between the value programmed in this field and the value programmed in the Manual Alarm/Short field. Auto.Alarm/Manual Alarm If the Call point Priority option has been ENABLED, the Control panel will consider the Zone in MANUAL ALARM status when the voltage on its terminals ranges between the value programmed in this field and the value programmed in the Manual Alarm/Short field. Manual Alarm/Short The Control panel will consider the Zone in MANUAL ALARM status when the voltage on its terminals is below the value programmed in this field. Changing the Default Thresholds: select the key button, then enter the new values (in accordance with the number and features of the zone connected devices).

Fault If you assign this event, the OC Output will activate when the system detects trouble, and will restore when the trouble clears. Reset If you assign this event, the OC Output will activate when the system generates Reset, and will remain active until Reset is completed. Disable If you assign this event, the OC Output will activate when Zones are Disabled, and will restore when the Zones are Re-Enabled. Test If you assign this event, the OC Output will activate when Zones are in Test status, and will restore when Test status ends. Double Knock If you assign this event, the OC Output will activate when TWO or more Zones generate Alarm, and will restore to standby when the Control panel Resets. one event, the OC Output will + If you assign more thanthe assigned events occurs, activate when one of and will Reset when ALL the assigned events end. n DL Output The Dialler Output ([DL] terminal) will activate when its programmed delay expires. The delay countdown will start when the Control panel generates Alarm status. a Call point (connec+ If the Alarm is triggered from point priority option ted to a Zone with the Call ENABLED), the DL Output will activate instantly. Alarm Signalling Delay This field will allow you to program the Dialler Output delay. Accepted values: 0 through 600 seconds (10 minutes), in steps of 10 seconds; Default setting: 60 seconds. Signalling Delay + The AlarmSilence phase. will be suspended during the

Panel Settings

The Panel Settings page will allow you to program the following parameters. n Day/Night Automatic Night to Day Mode If this option is ENABLED, the changeover from Night Mode to Day Mode will occur automatically at the set Time (refer to Night to Day Mode in this section). Automatic Day to Night Mode If this option is ENABLED, the changeover from Day Mode to Night Mode will occur automatically at the set Time (refer to Day to Night Mode in this section). Night to Day Mode This field will allow you to program when the Control panel must change from Night to Day Mode. This setting requires two digits for the Hour value and two for the Minutes value. Use 00 to 23 (00 = Midnight) to set the Hour value. Use 00 to 59 to set the Minutes value. Day to Night Mode This field will allow you to program when the Control panel must change from Day to Night Mode. This setting requires two digits for the Hour value and two for the Minutes value. Use 00 to 23 (00 = Midnight) to set the Hour value. Use 00 to 59 to set the Minutes value. n Reset The Control panel Reset operation is divided into two phases: Reset and Stabilization. During the Reset phase, the Control panel will interrupt the power supply to the devices connected to the Zones and the [24R] terminal. During the Stabilization phase, the Control panel will ignore the status of the Zones. Figure 27 The Panel Setting page

This process is necessary, as some devices signal trouble conditions for several seconds after power-up. The Reset section will allow you to program the Detector Reset and Stabilization Times. Detector Reset Time This field will allow you to program the length of the power interruption that will reset the Detectors. Accepted values: 0 through 15 seconds, in steps of 1 second. Default setting: 8 seconds. Detector Stabilization Time This field will allow you to program the length of time (necessary after Reset) that the system will ignore the Zone Status. Accepted values: 0 through 5 seconds, in steps of 1 second. Default setting: 2 seconds. n User Code The 4-digit User Code will allow access to Level 2 of the Control panel. Default setting: 1234 n Alarm Verification Time This field will allow you to program the Alarm verification window, that is, the time within which a Zone (with the Alarm Verification option ENABLED) must trigger two Alarm events in order for the system generate a Control panel Alarm. Accepted values: 10 through 600 seconds (10 minutes), in steps of 5 seconds Default setting: 60 seconds n Extinguishment Termination Code The Extinguishment Termination Code is a 4-digit number that allows the Extinguishment Time to be stopped for test purposes (refer to Testing The Extinguishment Module in the INSTALLING THE CONTROL PANEL section.
Type in the Extinguishment Termination Code than press the Disable Extinguish. button to stop the Extinguishment Time. Code + When the Extinguishment Terminationbeeps is entered, this will be acknowledged by 5 in ra-

Downloading

Once the operating parameters have been set up, they must be downloaded to the respective Control Panel, as follows. 1. Remove the screws 4 and open the Control panel. 2. Connect the jumper 65 to the first and second terminal pins on the 3-pin terminal strip marked PRG on the Main Board. All the Control panel LEDs will go OFF except for the Disab./Fault Telecom LED which will blink to indicate that the system is ready for programming via computer. 3. Connect the Control Panel serial port (67) to one of the PC serial ports, as follows: using a CVSER/9F9F link (accessory item), or a cable similar to the one in Figure 28a;, connect the Control Panel to the PC; if the PC serial port has 25 pins, use an ADSER/9M25F adapter (accessory item), or a cable similar to the one in Figure 28b. 4. Select the PC serial port used for connection with the Control panel, as follows: select Serial Ports from the Setup menu; select the serial port (Control Panel section); click or OK. 5. Select the parameters to be downloaded, as follows: select Control panel from the Setup menu; select the Control panel type from the Panel menu; select the respective firmware release from the Firmware menu; click OK.

2. Connect the jumper 65 to the first and second terminal pins on the 3-pin terminal strip marked PRG on the Main Board. All the Control panel LEDs will go OFF except for the Disab./Fault Telecom LED which will blink to indicate that the system is ready for programming via computer. 3. Press and hold the Disab./Fault Telecom key for at least 2 seconds. The green Mains LED will blink and the Amber Mains LED will go ON to indicate that the system is ready for programming via the Control panel. 4. Remove the cut-outs (for the LEDs), and insert the tabs of the Programming Overlay into the Zone label slots, as shown in Figure 29. 5. Press the Next Phase key 9 then select the group of parameters that you want to program: ZONES, TIMES; OUTPUTS; PANEL or VARIOUS (refer to the respective paragraph for details) or, if you want to program the Extinguishment Modules, press and hold (for at least 2 seconds) key 3 or key 6, respectively, Extinguishment Module nr. 1 and Extinguishment Module nr. 2 (refer to Programming Modules for details). The respective LED in column A will turn On to indicate the group of parameters concerned.
Exiting the Programming Session
Once programming has been completed, press key 9, then connect the jumper 65 to the second and third terminals on the 3-pin terminal strip marked PRG on the Main Board. The Control panel will Reset automatically. repositioning + Press the Next Phase key 9 beforenot be saved. the jumper, otherwise, the settings will
Accessing the Programming session
1. Remove the screws 4 and open the Control panel.

MODULES

VARIOUS PANEL OUTPUTS TIMES ZONES
M?2 x N.O. gas M640 sec M128 sec Alarm verific. M320 sec M M64 sec Detect missing M160 sec MOC output M32 sec NON silen. R M80 sec MALARM M16 sec Pre-alarm on R M40 sec MNAC2 Alarm M8 sec Test on NACs M20 sec MNAC1 Alarm M4 sec C Call-point alarm M10 sec MN NAC2 Pre-alarm M2 sec 4-20mA gas R out M5 sec bistable MN NAC1 Pre-alarm M1 sec B
Pre-alarm time Alarm User code Stabilization time Extinguish. time Verification time Reset Night mode NON silence. outs Man. pre-ext. t. DL output delay Double knock Date Configuration 2 Zones Next phase
Investigation time Pre-alarm Day mode Reset time Pre-exting. time Silence time Disablement Clock Configuration 1 Reset Inhibit t. Increase time Mains OFF delay Increase time Increase time Next Option Decrease time Next Output

Figure 34 The VARIOUS Programming Phase
n Configuration 1 (Key/LED 5) The LED will go On to indicate that the system is ready to start the programming procedure. Using the keys in columns E and F, configure the Control panel: if the LED is On, the respective Module is included in the configuration; if the LED is Off, the respective Module is NOT included in the configuration. During this phase, the keys and LEDs in columns E and F will operate in accordance with the options written in positive type: Exting. 1 = Extinguishment Module nr. 1 Exting. 2 = Extinguishment Module nr. 2 Expander 1 = Expander Module nr. 1 Expander 2 = Expander Module nr. 2 Power 1 = Power Station nr. 1 Power 2 = Power Station nr. 2 Power 3 = Power Station nr. 3 Power 4 = Power Station nr. 4 n Configuration 2 (Key/LED 7) The LED will go On to indicate that the system is ready to start the programming procedure. Using the keys in columns E and F, configure the Control panel: if the LED is On, the respective Module is included in the configuration; if the LED is Off, the respective Module is NOT included in the configuration. During this phase, the keys and LEDs in columns E and F will operate in accordance with the options written in negative type: LCD 1 = LCD Module nr. 1 LCD 2 = LCD Module nr. 2 LCD 3 = LCD Module nr. 3 LCD 4 = LCD Module nr. 4 Rep. 1 = Repeater panel nr. 1 Rep. 2 = Repeater panel nr. 2 Rep. 3 = Repeater panel nr. 3 Rep. 4 = Repeater panel nr. 4
The MODULES Programming Phase
Mode + The ActivationPC. may ONLY be programmed THROUGH A The MODULES LED will blink to indicate that the system is ready to program the parameters of the Extinguishment Modules. During this phase, the keys and LEDs will operate in accordance with the options preceded by in the panes on the Programming Overlay, see Figure 35. The LED (Exting. 1 or Exting. 2) corresponding to the Extinguishment Module concerned will blink to indicate that the system is ready to program the respective parameters. Press key 1 (Extinguish. Time), 2 (Pre-Exting. Time), 4 (Man. pre-Ext. T.), 5 (Reset Inhibit T.) or 7 (Zones) to select the parameter to be programmed, then read the relevant sub-section, or press key 9 (Next Phase) to go back to the ZONE Programming. n Extinguish. time (Key/LED 1) The LED will go On to indicate that the system is ready to start the programming procedure. Use the Increase Time option (Key 8) or Decrease Time option (Key 0), respectively, to increase or decrease the setting. The setting is achieved by adding together the values preceded by and , indicated by the LEDs in column B (e.g. if the 20 sec and 40 sec LEDs are On, the setting will be 60 seconds (20+40)). n Pre-exting. time (Key/LED 2) The LED will go On to indicate that the system is ready to start the programming procedure. Use the Increase Time option (Key 8) or Decrease Time option (Key 0), respectively, to increase or decrease the setting. The setting is achieved by adding together the values preceded by and , indicated by the LEDs in column B (e.g. if the 16 sec and 4 sec LEDs are On, the setting will be 20 seconds (16+4)).

27.6 0.06 (4) 0.1

Table 4 Description of terminals (Continues.)

DESCRIPTION

2 and 4 ZONE MAIN BOARDS SupervisedBypassable DIALLER Output: [DL] during Standby floating (5) on expiry of the Alarm Signalling Delay negative pull-down to 0 V PROGRAMMABLE AUXILIARY Output: [OC] during Standby terminal floating on verification of an associated event negative pull-down to 0 V 24 V POWER Output: [24V] Positive pull-up to 27.6 V on [24V] terminal [M] Negative pull-down to 0 V on [M] terminal RESETTABLE 24 V POWER Output: [24R] during Standby positive pull-up to 27.6 V on [24R] terminal [M] during Reset [24R] terminal floating; Negative pull down to 0 V on [M] terminal POWER LOSS Output: [PL] during Standby floating during power failure negative pull-down to 0 V Non-SupervisedSilenceable ALARM Output: ALARM Control panel in Standby [COM] terminal connects to [NC] and [NO] floats Control panel in Alarm the [COM] and [NO] terminals connect, in accordance with programming Non-SupervisedSilenceableBypassable FAULT Output: FAULT Control panel in Standby [COM] terminal connects to [NC] and [NO] floats in the event of Fault [COM] terminal connects to NO] and [NC] floats SupervisedSilenceableBypassable ALARM Output N. 1: NAC1 Panel in Standby negative pull-down to 0 V on [+] terminal; positive pull-up to 27.6 on [] terminal (6) Panel in Alarm positive pull-up to 27.6 on [+] terminal; negative pull-down to 0 V on [] terminal SupervisedSilenceableBypassable ALARM Output N. 2: NAC2 Panel in Standby negative pull-down to 0 V on [+] terminal; positive pull-up to 27.6 V on [] terminal (6) Panel in Alarm positive pull-up to 27.6 on [+] terminal; negative pull down to 0 V on [] terminal 8 ZONE MAIN BOARD RS485 Serial Port: Positive pull-up to 27.6 V on [24V] terminal; Negative pull-down to 0 V on [M] terminal; data on [+] and [] terminals
27.6 1(4) 0 27.6 1(4) 0 0 5

27.6 1(4) 27.6 1(4)

27.6 1(4) 0
Table 4 (.continued) Terminals Description (4) The sum of the currents absorbed by terminals [Z1], [Z2],., [Z8], [24V], [24R], [NAC1] and [NAC2] must not exceed: 1.5 A for the J424 control panel; 1 A for the J408 control panel. (5) The terminals [Z1], [Z2],., [Z8] and [DL], if not used, must be connected to negative using a 3900 ohm resistor. (6) Connect a 3900 ohm resistor between the [+] and [-] terminals of the NAC1 and NAC2 Outputs, if not used.

doc1

Trouble This Control panel can detect and signal the following Trouble: Input zone shorted or open; Supervised zone shorted or open; Control panel blocked; Output 24V or 24R shorted; Low battery, battery trouble or disconnected battery; Ground fault; Communication trouble with peripherals; Mains failure. Fault conditions will be signalled by: a slow intermittent beep (at 1 second intervals); glowing on the Fault LED; fast blinking on the LED of the component concerned (the Logic Unit LED will glow to signal Control panel blocked); activation of the Fault output (TROUBLE terminals); Negative pull-down to 0 V on OC terminal, that is, if it is programmed to signal Fault. The Fault output (TROUBLE terminals) and OC outputs (if duly programmed) will restore to standby automatically when fault conditions clear. Under certain circumstances, fault conditions may clear spontaneously, if this occurs, the event will be stored in the memory until the Control panel Resets. Stored Fault events will be signalled by: slow blinking on the LEDs of the component concerned. Silence This Control panel provides a Silence key which can be used to restore the Silenceable outputs to standby status: R1, R2,., R8 NAC1 and NAC2 ALARM TROUBLE Silence status will be signalled by: an audible signal (lasting 1 second) followed by a long pause (lasting 5 seconds); glowing on the Silence LED.
n Interface Visual Signalling The system status will be signalled on the Control panel LEDs as follows: GREEN indicates normal operating conditions; AMBER indicates specific operating modes (for example Day or Night mode), and/or Fault conditions; RED indicates Alarm conditions. Memory The Control panel will signal Alarm/Fault events until the system Resets, even if the event clears in the meantime. Stored events will be signalled by: slow blinking on the LED concerned. Display The J424 Control panel can house the J400-LCD Module. This module provides written information regarding the system status, and the cause of faults on inputs and outputs (short-circuit, interruption etc.).
Audible Signalling The Buzzer will signal the Control panel status as follows: Status Sound Pause Description Pre-alarm 0.5 s 0.5 s Intermittent beep Alarm 0.2 s 0.2 s Fast Intermittent beep Fault 1s 1s Slow Intermittent beep Long beep/Long pause Silence 1s 5s Reset Test 0.5 s 1s 0.1 s 3s Short beep/Short pause Long beep/Long pause
n Access to Signalling and Commands There are 4 access levels, in compliance with the Fire Safety Regulations in force. Access Level 1 Viewing: ALL persons can view the Control panel status. Access Level 2 Operating the system (PIN Code entered or Key turned in the Keyswitch): ONLY Key and PIN Code Users can operate the system. Access Level 3 Opening the Control panel: ONLY Qualified persons with authorization are allowed to open the Control panel door (requires removal of the screws) for maintenance purposes. Access Level 4 Repairing or replacing the PCB: ONLY the Manufacturer should be allowed to repair or replace the PCB. n Power Supply The power supply system of the J424 and J408 Control panels complies with EN54-4. Both models are powered by the Mains (230 V, 50 Hz): the J408 model has Switching Power Supply which supplies up to 1.5 A at 27.6 V; the J424 model has Switching Power Supply which supplies up to 2.5 A at 27.6 V; Both models can house two 12 V batteries which, when connected in series, will supply 24 V to the Control panel and peripherals in the event of black-out, and will also provide any pickup currents which exceed the maximum current supplied by the Switching Power Supply. Power Supply: the J408 model can house two 7 Ah batteries (YUASA NP 7-12 FR model or similar flame class UL94-V2 or higher); the J424 model can house two 17 Ah batteries (YUASA NP 17-12 FR model or similar flame class UL94-V2 or higher). This Control panel can detect, signal and store in memory the following power faults: shorted 24V or 24R outputs (24V/24R LED); Low battery, Battery fault or Battery disconnected (Battery LED), Ground fault (Ground LED) and Mains failure (Mains LED). Disconnected fault + The Batteryof up to 1 minute. Themay be signalled with a delay Mains fault will be signalled when the programmed delay expires.

Zone Alarm Alarm Fault Logic Unit 24V/24R Battery Ground Periph. Mains Reset

Zone Alarm

Silence

Night Mode

Pre-al. Test Disab. Telecom Mains

Ack./Evac.

Disab./Fault NAC

0.0 8-424JILBMCASM

Disab./Fault Telecom
Disabled/Fult/Test Zone Alarm
Disabled/Fult/Test Zone Alarm Esc
Disab. Buzzer Zone Alarm Zone Alarm

Li v e

Disabled/Fult/Test

Disable

Disable ON Fault Electrovalve PreExt. Manual Disab. Ext. Ext. Pres. Switch Logic Unit Extinguish. Manual Automatic Extinguish. Extinguish. ON Fault Electrovalve Pre Ext. Manual Disab. Ext. Ext. PresSwitch Logic Unit Extinguish.
Manual Automatic Extinguish. Extinguish
Figure 1 Front view of the J424 Control panel J424 (a), J408 Control panel (b) and J400-REP Repeater (c)

0. 0 8-8 04JIENMCA SM

Disabled/Fault/Test

Disab. Buzzer

Disable ON Fault Electrovalve Pre Ext.

0.0 8-80 4JILBMCASM

Manual Disab. Ext. Ext.

Pres. Switch

Logic Unit

Extinguish.

Manual Automatic Extinguish. Extinguish.
Fault Logic Unit 24V/24R Battery Ground Per iph. Mains Reset

Pre-al. Test Disab.

0.a PER-004JILBMCASM

Telecom Mains

Disabled/Fault/Test Zone Alarm
Esc Disabled/Fault/Test Zone Alarm

400 REP

29 Figure 2 Maximum configuration of the J424 Control panel

C ON CN

TROUBLE NAC1 NAC2

+ V RS485 24

31 NO NC

B+ L B GND

OC DL PL

GND +V

F 6.3A/25V

F 3.15A/25V

Description of Parts
This section describes the components of the J424 and J408 Control panels, and J400-REP Repeater. Unless otherwise stated, the numbers in boldface in this Manual refer to the Tables ands Diagrams in this section. The parts identification numbers in the diagrams go clockwise. The white numbers refer to parts which are common to several of the system devices, therefore, are described the first time they are encountered only.
Description Surface Cable conduit entry Zone label slots Display Door screws Keyswitch (Access Level 2) Display module (accessory item) Expander Control board (LEDs and keys) of Expander no. 2 (accessory item for J424) Flat cable (accessory item for J424): for the Expander Control board connection Main Control board (LEDs and keys) of zones 1 through 8 Expander Control board (LEDs and keys) of zones 9 through 16 (accessory item for J424) Flat cable: for the Main Control Board connection (zones 1 through 8) Anchor screw locations Main board (2, 4 or 8 zones) Chased cable conduit entry Flat cable (accessory item for J424): for the Expander Control board connection

Description of the Control keys
The Control panel keys can be activated by Keyswitch and PIN Code Users ONLY (Access level 2 Key tur-
ned in keyswitch or PIN Code entered refer to Access to Signalling and Commands), unless otherwise stated.
Key DESCRIPTION Silence This key can be used to restore the Silenceable outputs to standby status (terminals [NAC1], [NAC2], [DL], [TROUBLE], [ALARM if duly programmed] and [Rn if duly programmed]. Silence status will be held until the Silence key is pressed again or, if the Control panel is operating in Night Mode, until the Night mode Silence time expires or until a new Alarm/Trouble condition is detected. Ack./ Evac. This key can be used to refresh the Pre-Alarm Time or trigger an Alarm: For all persons on the premises: If this key is pressed for over 5 seconds during Pre-Alarm Time, the system will generate an alarm. For Key and PIN Code Users ONLY (Access level 2): If this key is pressed during Pre-Alarm Time, the remaining Pre-Alarm Time will be refresh with the programmed Investigation Time. If it is pressed for over 5 seconds during Pre-Alarm Time, the system will generate an alarm. Reset This key can be used to reset the Fire detectors and restore all outputs to standby status (Supervised/Silenceable outputs, NON-Supervised/Non-Silenceable outputs and Alarm zone outputs). Disab. Buzzer This key can be used to disable the buzzer. The buzzer will be re-enable if any kind of event occurs. Night Mode This key can be used to switch from Day to Night Mode. Disab./Fault This key can be used to disable the Bypassable Fire alarm outputs (terminals [NAC1] and [NAC2]). NAC Disab./Fault This key can be used to disable the Telephone device output (terminal [DL]) Telecom Test This key can be used to test the zones, buzzer and LEDs. If this key is pressed (when the Control panel is functioning as intended), all the LEDs will Glow and the buzzer will emit a continuous beep. For Access level 2 Users ONLY: If this key is pressed with the Disable key of a zone (z1, z2,., z24) it will activate the respective zone test phase. z1 z24 These keys can be used to disable their respective zones. Disabled zones will provide visual signalling of fire and fault conditions but will not activate any outputs or store events in Memory. Disable This key can be used to disable the Extinguishment function. Extinguish. Disable This key can be used to disable the Manual Extinguishment function. If this function is disabled, it Manual will not be possible to activate Extinguishment function via the EM input. Extinguish. Disable This button can be used to disable the Automatic Extinguishment function. If this function is disaAutomatic bled, the zones will not be unable to activate Extinguishment. Extinguish. Table 2 Description of keys

9. After power up, set the Address of the Display Module (if installed), as described in the Display Module section under PROGRAMMING FROM THE CONTROL PANEL.
ONLY when: no more than 30 devices are connected to each zone; no more than 3 Gas detectors are connected to the Control panel; no more than 512 devices IN ALL are connected to the Control panel.
n Main Board Terminals [24V] [M] Auxiliary Power Supply Power supply for devices that function at 24 V, protected by a resettable fuse, has battery backup. Operating principles Positive pull-up to 27.6 V on the [24V] terminal; Negative pull-down to 0 V on the [M] terminal. If the current draw on the [24V] terminal exceeds 1 A, the system will interrupt the power supply to the terminal and signal Fault on the 24V/24R LED (fast blinking). The system will restore power to the terminal when the current draws drops below 1 A. [24R] [M] Resettable Auxiliary Power Supply Resettable Power supply for devices that function at 24 V, protected by a resettable fuse, has battery backup. Operating principles Positive pull-up to 27.6 V on the [24R] terminal; Negative pull-down to 0 V on the [M] terminal. If the current draw on the [24R] terminal exceeds 1 A, the system will interrupt power to the terminal, and will signal Fault on the 24V/24R LED (fast blinking). The system will restore power to the terminal when the current draws drops below 1 A. The system will interrupt power from terminal [24R] during Reset, therefore, this power source can be used to power devices that reset when the power supply is interrupted. OC Programmable Auxiliary Output This Output can be programmed to signal one or more of the following events: Alarm Pre-alarm Fault Reset Disable Test Double Knock
If a zone triggers an Automatic Alarm during Day Mode, the Control panel will initialize the Pre-alarm phase. If a zone triggers an Automatic Alarm during Night Mode, the Control panel will generate an instant Alarm. If a zone triggers a Manual Alarm whether in Day or Night Mode, the Control panel will generate an instant Alarm. If a zone Shorts or Opens, the Control panel will generate a Trouble warning. Each Reset operation will interrupt the power supply to all zones for the programmed Detector Reset Time. [M] Detector negative [R1]. [R8] Silenceable/Repeat Outputs Each zone provides a Repeat Output for selective intervention purposes (to close Fire doors, to limit signalling to the Zone concerned, etc.).

EVENTS

DETAILS None None None None Zone no. + Description Extinguishment Mod. nr. Power Supply Stat. nr. Power Supply Stat. nr. Power Supply Stat. nr. None Power Supply Stat. nr. Power Supply Stat. nr. Power Supply Stat. nr. Power Supply Stat. nr. None Power Supply Stat. nr. None Zone no. + Description Zone no. + Description None Extinguishment Mod. nr. None None Enabled/Disabled Extinguishment Mod. nr. Extinguishment Mod. nr. Extinguishment Mod. nr. Extinguishment Mod. nr. Extinguishment Mod. nr. Extinguishment Mod. nr. None None None Extinguishment Mod. nr. Extinguishment Mod. nr. Extinguishment Mod. nr. None None/Pow.SupStat.nr. None Extinguishment Mod. nr. Extinguishment Mod. nr. Night/Day Enabled/Disabled None None None None Power Supply Stat. nr. Power Supply Stat. nr. Power Supply Stat. nr. Power Supply Stat. nr. Extinguishment Mod. nr. Extinguishment Mod. nr. Extinguishment Mod. nr. Extinguishment Mod. nr. Peripheral type and nr. Extinguishment Mod. nr. Device type+Number
DESCRIPTION 24R output shorted 24R output previously shorted 24V output shorted 24V output previously shorted Zone no. is in Alarm status Automatic Extinguishment of Extinguishment Mod. nr. re-enabled Charger of Power Supply Stat. nr. not operating properly Charger of Power Supply Stat. nr. previously not working Batteries of Power Supply Stat. nr. disconnected Panel batteries empty, malfunctioning or disconnected Batteries of Power Supply Stat. nr. empty or disconnected Batteries of Power Supply Stat. nr. low Batteries of Power Supply Stat. nr. previously disconnected Batteries of Power Supply Stat. nr previously low Panel batteries previously empty, malfunctioning or disconnected Batteries of Power Supply Stat. nr. empty or disconnected Buzzer disabled Zone no. disabled A detector connected to zone no. is missing Dialler Output active Automatic Extinguishment of Extinguishment Mod. nr.i disabled Dialler connections interrupted or shorted Dialler connections interrupted or shorted The Dialler Output has been disabled/enabled EM Input of Extinguishment Mod. nr. activated EM Input of Extinguishment Mod. nr. shorted or open EM Input of Extinguishment Mod. nr. previously shorted or open EV Output of Extinguishment Mod. nr. activated EV Output of Extinguishment Mod. nr. shorted or open EV Output of Extinguish. Mod. nr. previously shorted or open Evacuation command executed Control panel ground fault restored Control panel leakage to Earth IE Input of Extinguishment Mod. nr. activated IE Input of Extinguishment Mod. nr. shorted or open IE Input of Extinguishment Mod. nr. previously shorted or open Investigation Done Mains failure to Control panel/Power Supply Stat. nr. The Control panel/Power Supply Stat. nr. powered from Mains EM Input of Extinguishment Mod. nr. disabled EM Input of Extinguishment Mod. nr re-enabled Control panel switched from Night to Day Mode One of the Alarm outputs has been disabled/enabled Alarm device connections interrupted or shorted Alarm device connections interrupted or shorted Alarm device connections interrupted or shorted Alarm device connections interrupted or shorted O1 Output of Power Supply Stat. nr shorted O1 Output of Power Supply Stat. nr shorted O2 Output of Power Supply Stat. nr shorted O2 Output of Power Supply Stat. nr shorted Extinguishment Mod. PR, EV and AV outputs disabled Extinguishment Mod. PR, EV and AV outputs re-enabled PR Output of Extinguishment Mod. nr. activated PR Output of Extinguishment Mod. nr. shorted or open The device concerned missing or faulty PR Output of Extinguish. Mod. nr. previously shorted or open The device concerned previously missing or faulty

ZONE 01 Warehouse

4. Repeat the previous step to continue viewing or, press Esc to step back.
+ The Reset button can be used during Access Level 2 only.
Test ON indicates that at least one Zone is in Test status: check the Disabled/Fault/Test LEDs of the zones in order to check which zones are in Test status, and call assistance. Disab. ON indicates that at least one zone is disabled, and cannot generate fire alarms: check the Zone Alarm LEDs of the zones in order to check which zones are disabled. Telecom ON indicates that the devices assigned to fire alarm signalling via telephone have been activated.
Mains (GREEN) If OFF check for local black-out, otherwise call assistance; power to the control panel is guaranteed by the incorporated batteries. If mains failure lasts for many hours, the standby batteries will run-down. Fault ON indicates that one or more faults are present: check the other LEDs to find out which faults are concerned. Logic Unit ON indicates that the Control panel is blocked: call assistance. 24V/24R Fast blinking indicates shorted 24V or 24R output: call assistance. Battery ON indicates either no batteries present or low batteries, and in the event of a black-out cannot guarantee proper functioning of the control panel; wait several hours to see if they recharge, otherwise, call assistance. Ground If ON call assistance. Periph. Fast blinking indicates communication trouble with peripheral (Expander module, Extinguishment module, LCD Module, Repeater panel, Power station): call assistance. Mains (RED) As for the GREEN Mains LED, except that it is fast blinking during mains failure, and has a memory. Silence ON indicates that the SILENCEABLE devices have been silenced: to re-enable press the Silence button. Silenced devices will re-enable automatically at the next alarm status. The + vel 2Silence button can be used during Access Leonly. Ack./Evac. ON indicates that the programmed Investigation time is running. Reset ON indicates that Reset operation cannot be carried out: press the Silence button. The + vel 2Silence button can be used during Access Leonly. Night Mode ON indicates NIGHT Mode functioning. If the Silence button is pressed during NIGHT mode the SILENCE status will be held for the programmed Night mode Silence time. OFF indicates DAY Mode functioning. If the Silence button is pressed during DAY Mode the SILENCE status will be held until the Silence button is pressed again. The + vel 2Silence button can be used during Access Leonly.
Disab./Fault NAC ON indicates that the SUPERVISED/SILENCEABLE devices assigned to fire signalling have been bypassed. Fast blinking indicates that the SUPERVISED/SILENCEABLE devices assigned to fire signalling are unable to function: call assistance. Disab./Fault Telecom ON indicates that the devices assigned to fire signalling via telephone have been disabled. Fast blinking indicates that the devices assigned to fire signalling via telephone are unable to function: call assistance. Zone Alarm ON indicates that the corresponding zone is in alarm status. Check for false alarm, if there is real danger spread the alarm; otherwise, press the Reset button to stop signalling.

n Connecting Gas Detectors This Control panel accepts Gas detectors with Normally Open Outputs (NO) and 4-20 mA gas detectors. NO Output Connect Gas detectors with Normally Open Outputs (NO) as per Figure 16a. Operating principles: Terminal [A] (the Detector Alarm Output) will connect to terminal [] when the concentration of gas in the area exceeds the preset safety threshold. Wiring description: Using a 680 ohm resistor (111), connect terminal [A] to the zone terminal. Connect terminal [+] (the Detector Power input) to a power source that can be interrupted for the required reset time (see terminal [24R] on the Main Board). Terminal [P] (the Detector Pre-Alarm Output) is not shown in the wiring diagram. The Repeat Output of the zone can be set up to interrupt the gas flow in the event of an alarm (wiring as per Figure 16a see terminal [R4]). If zone Z4 generates an alarm (or pre-alarm when the Pre-Alarm on R Output option is ENABLED), terminal [R4] will pull down to 0 V (negative) thus activating the relay which in turn will latch the Switching Power supply to the Electrovalve. current draw provi+ The by an externalof Electrovalves must bePower ded power source (e.g. BXM Station).
ZRZero ohm call-point 112 111

NO output detector

Figure 15 Wiring diagram of 3 detectors with Normally-Open Outputs and a Call point with zero ohm contact resistance: 109) 3900 ohm, 1/4 W EOL resistor (orange-white-red-gold); 111) 680 ohm resistor; 112) 680 ohm resistor (necessary when Call-point priority option is DISABLED) or 270 ohm resistor when Call-point Priority option is ENABLED).
4 - 20 mA Gas detectors 4 - 20 mA Gas detectors can be connected to terminals [Z1] ONLY on the Main Board and Expander Module, as per Figure 16b. Operating principles The current draw of terminal [S] varies from 4 to 20 mA in accordance with the concentration of gas present in the area. Wiring description The [] terminal is the negative power terminal. Connect a 470 ohm, 2 W (113) between terminal [S] and terminal [] of the detector. Connect [+] terminal (positive power input) to a power source that can be interrupted for the required reset time (see terminal [24R] on the Main Board).
n Connecting Signalling Devices NAC1, NAC2 and ALARM outputs are for the alarm signalling device connections. NAC1 and NAC2 can be set up to signal pre-alarm and alarm conditions (refer to Outputs under PROGRAMMING FROM A PC). The wiring diagram in Figure 18 shows two warning lamps and the flasher of an outdoor signalling device (STROBE terminals) connected to NAC2, and two fire bells and the horn of an outdoor signalling device (HORN terminals) connected to NAC1. This type of connection makes it possible to diversify pre-alarm from alarm signalling. For example, NAC2 will not activate during the pre-alarm phase, whereas, NAC1 will activate every 6 seconds for 2 seconds. NAC1 and NAC2 will always be active during alarm status. 1/4 W resistor (109) must + A 3900 ohm, the [+] and [] terminals of be connected between the last de-

+ Terminal [Z1] accepts ONE 4 - 20 mA Gas detector ONLY.
If you are connecting a 4 - 20 mA Gas detector to terminal [Z1] of an Expander Module, remove the Jumper (62) (marked GAS on the PCB), and ENABLE the Gas Detector option of the respective zone (i.e. Zone nr. 1 for the Main Board, Zone nr. 9 for Expander Module nr. 1, zone nr. 17 for Expander Module nr. 2).
vice connected to NAC1 and NAC2. A 1N4007 diode (114) (or similar) must be connected between the [+] terminals of devices connected to NAC1 and NAC2 and the [+] terminals of the latter.
24R 4 - 20 mA gas detector

A P A P

Z1 R1 113
NO output gas detector Gas electrovalve 24 V relay

Powe supply station O2

Figure 16 Wiring diagram of a Gas detector with Normally-Open Output (a) and a 4 - 20 mA Gas detector (b): 109) 3900 ohm, 1/4 W EOL Resistor (orange-white-red-gold); 111) 680 ohm resistor; 113) 470 ohm resistor, 2 W
Connect to the earth conductor

24V RS485 Repeater panel

Figure 17 Wiring diagram of a Repeater connection n Connecting a Repeater Connect the 24V, , + and M terminals to the respective terminals on the Main Board of the Control panel, as shown in Figure 17. connected the RS485 + The maximum wire lengthpanel must not exceed terminals of the Control 1000 metres. Connect the - terminal of the Repeater to the Main Earth wire.

Fire bell + +

Fire bell 109

Warning lamp 114 +

FIRE ALARM
Figure 18 Wiring diagram of Signalling devices: 109) 3900 ohm, 1/4 W EOL Resistor (orange-white-red-gold); 114) 1N4007 Diode or similar

STROBE

Outdoor hornstrobe
n Connecting Extinguishment Modules
Manual Extinguishment Control Buttons
A The J400-EXT Extinguishment Mo109
dule IS NOT an IMQ-SECURITY SYSTEMS listed product.
Inhibit Extinguishment Control Buttons
The wiring diagram in Figure 19 shows an Extinguishment Module connected to the Control panel. The EM inputs (Manual Extinguishment) and IE inputs (Inhibit Extinguishment) accept Normally-Open control buttons with 680 ohm contact resistance. Wiring description: Connect a 3900 ohm, 1/4 W resistor (109) between terminal [NO] and terminal [C] of the last control button. The PS input accepts pressure switches with Normally-Open output and 680 ohm contact resistance. Wiring description: Connect a 680 ohm resistor (111) between one of the pressure switch terminals and the [+] terminal of the PS input. Connect (as near as possible to the last pressure switch connected to the PS input) a 3900 ohm, 1/4 W resistor (109) in parallel to the [+] and [] terminals of the PS input. Extinguishment Modules are unable to supply the high current draw required by Electrovalves, therefore, installation of an external Power Station is required. Wiring description: The Extinguishment Module is unable to supply the current draw of the PR and AE Outputs, therefore, it will be necessary to connect the 24P input to the Switching Power Supply of the Control panel, or to an external Power station. The PR output (Pre-Extinguishment) and AE output (Activated Extinguishment) accept signalling devices that operate at 24V. Wiring description: Connect (as near as possible to the last device connected to the output) a 3900 ohm, 1/4 W resistor (109) in parallel to the [+] and [] terminals of the output. Connect a 1N4007 diode or similar, between the positive inputs of the devices connected to the PR and AE, and the [+] terminals of the latter.

Outputs

The Outputs page controls the pulse pattern for Pre-Alarm (Alert) and/or Alarm (Evacuate) signalling on the NAC1 and NAC2 outputs, and Alarm (Evacuate) signalling on the ALARM output. The pattern is represented by a series of bells, each bell representing a second. The configuration of the RED and WHITE backgrounds (for On and Off respectively e.g. all RED indicates continuously On) determines the respective pulse pattern. For example, the output devices (connected to NAC1and NAC2) can be configured to have one audible output for Pre-Alarm (Alert) and a different audible output for Alarm (Evacuate), thus allowing users to distinguish between the two conditions, as follows. n NAC1 Output Pre-Alarm pattern The bell chart will allow you to program the Pre-Alarm (Alert) pattern of NAC1. Bell on RED background = Output ON for 1 second; Crossed Bell on WHITE background = Output OFF for 1 second. Pre-Alarm Default setting: NAC1 will turn ON for 2 seconds then turn OFF for 6 seconds. Alarm pattern To be set up in the same way as the Pre-Alarm pattern of NAC1 but for the Alarm pattern. Default setting: NAC1 is continuous. n NAC2 Output Pre-Alarm pattern To be set up in the same way as the Pre-Alarm pattern of NAC1 but for the Pre-Alarm pattern of NAC2. Pre-Alarm Default setting: NAC2 WILL NOT ACTIVATE during the Pre-Alarm Time. Alarm pattern To be set up in the same way as the Alarm pattern of NAC1 but for the Alarm pattern of NAC2. Default setting: NAC2 is continuous. n ALARM Output Alarm Pattern To be set up in the same way as NAC1 but for the Alarm pattern of the ALARM Output. Default setting: the Alarm Output is continuous. NON-Silenceable If this option is ENABLED, the ALARM Output cannot be SILENCED.
The Gas Detector option can be ENABLED ONLY for Zones 1, 9 and 17, respectively, the [Z1] terminals on the Main Board, and on Expander nr. 1 and Expander nr. 2.
n Times Pre-Alarm Time This field will allow you to program the delay between the Zone Alarm and the Control panel Alarm. seconds of + If several Zones trigger Alarms withingenerate an one another, the Control panel will
Alarm when the shortest Pre-Alarm Time of all the Zones concerned expires.
Accepted values: 0 to 300 seconds (5 minutes), in steps of 10 seconds. Default setting: 60 seconds. Investigation Time This field wilI allow you to program an interval that will override the Pre-Alarm Time. This interval will allow users time to investigate fire alerts. It will be applied when the Ack/Evac. key is pressed for less than 5 seconds at Access Level 2 (Keyswitch ENABLED or PIN Code entered). Accepted values: 0 to 300 seconds (5 minutes), in steps of 10 seconds Default value: 60 seconds.
n OC Output Events This section will allow you to assign one or more of the following events to the OC Output ([OC] terminal), as follows. Alarm If you assign this event, the OC Output will activate when the Control panel generates an Alarm, and will restore to standby when the Control panel Resets. Pre-Alarm If you assign this event, the OC Output will activate when the Control panel generates Pre-Alarm, and will restore to standby when the Control panel generates an Alarm. Fault If you assign this event, the OC Output will activate when the system detects trouble, and will restore when the trouble clears. Reset If you assign this event, the OC Output will activate when the system generates Reset, and will remain active until Reset is completed. Disable If you assign this event, the OC Output will activate when Zones are Disabled, and will restore when the Zones are Re-Enabled. Test If you assign this event, the OC Output will activate when Zones are in Test status, and will restore when Test status ends. Double Knock If you assign this event, the OC Output will activate when TWO or more Zones generate Alarm, and will restore to standby when the Control panel Resets. more than + If you assignwhen one ofone event, the OC Output will activate the assigned events oc-

n DL Output The Dialler Output ([DL] terminal) will activate when its programmed delay expires. The delay countdown will start when the Control panel generates Alarm status. a Call point (connec+ If the Alarm is triggered from point priority option ted to a Zone with the Call ENABLED), the DL Output will activate instantly. Alarm Signalling Delay This field will allow you to program the Dialler Output delay. Accepted values: 0 through 600 seconds (10 minutes), in steps of 10 seconds; Default setting: 60 seconds. Signalling Delay + The AlarmSilence phase. will be suspended during the

Panel Settings

The Panel Settings page will allow you to program the following parameters. n Day/Night Automatic Night to Day Mode If this option is ENABLED, the changeover from Night Mode to Day Mode will occur automatically at the set Time (refer to Night to Day Mode in this section). Automatic Day to Night Mode If this option is ENABLED, the changeover from Day Mode to Night Mode will occur automatically at the set Time (refer to Day to Night Mode in this section). Night to Day Mode This field will allow you to program when the Control panel must change from Night to Day Mode. This setting requires two digits for the Hour value and two for the Minutes value. Use 00 to 23 (00 = Midnight) to set the Hour value. Use 00 to 59 to set the Minutes value.
curs, and will Reset when ALL the assigned events end.
Figure 25 The Outputs page
Day to Night Mode This field will allow you to program when the Control panel must change from Day to Night Mode. This setting requires two digits for the Hour value and two for the Minutes value. Use 00 to 23 (00 = Midnight) to set the Hour value. Use 00 to 59 to set the Minutes value. n Reset The Control panel Reset operation is divided into two phases: Reset and Stabilization. During the Reset phase, the Control panel will interrupt the power supply to the devices connected to the Zones and the [24R] terminal. During the Stabilization phase, the Control panel will ignore the status of the Zones. This process is necessary, as some devices signal trouble conditions for several seconds after power-up. The Reset section will allow you to program the Detector Reset and Stabilization Times. Detector Reset Time This field will allow you to program the length of the power interruption that will reset the Detectors. Accepted values: 0 through 15 seconds, in steps of 1 second. Default setting: 8 seconds. Detector Stabilization Time This field will allow you to program the length of time (necessary after Reset) that the system will ignore the Zone Status. Accepted values: 0 through 5 seconds, in steps of 1 second. Default setting: 2 seconds. n User Code The 4-digit User Code will allow access to Level 2 of the Control panel. Default setting: 1234 Figure 26 The Settings page

n Alarm Verification Time This field will allow you to program the Alarm verification window, that is, the time within which a Zone (with the Alarm Verification option ENABLED) must trigger two Alarm events in order for the system generate a Control panel Alarm. Accepted values: 0 through 600 seconds (10 minutes), in steps of 5 seconds Default setting: 30 seconds n Night Mode Silence Time This parameter determines how long the Control panel will hold Silence status during Night Mode. Accepted values: 0 through 600 seconds (10 minutes), in steps of 5 seconds Default setting: 60 seconds n Mains Failure Signalling Delay This parameter determines how long the Control panel will wait before signalling a Mains Failure event. Accepted Values: 0 through 9999 minutes (6 days, 22 hours, 39 minutes), in steps of 1 minute. Default Setting: 0 minutes.
A The IMQ SECURITY SYSTEMS approval applies
ONLY when the Mains Failure delay is set at 30 minutes or less.
n Date/Time This field is for the current date and time.

Downloading

Once the operating parameters have been set up, they must be downloaded to the respective Control Panel, as follows. 1. Remove the screws 4 and open the Control panel. 2. Connect the jumper 65 to the first and second terminal pins on the 3-pin terminal strip marked PRG on the Main Board. All the Control panel LEDs will go OFF except for the Disab./Fault Telecom LED which will blink to indicate that the system is ready for programming via computer. 3. Connect the Control Panel serial port (67) to one of the PC serial ports, as follows: using a CVSER/9F9F link (accessory item), or a cable similar to the one in Figure 27a;, connect the Control Panel to the PC; if the PC serial port has 25 pins, use an ADSER/9M25F adapter (accessory item), or a cable similar to the one in Figure 27b. 4. Select the PC serial port used for connection with the Control panel, as follows: select Serial Ports from the Setup menu; select the serial port (Control Panel section); click or OK. 5. Select the parameters to be downloaded, as follows: select Control panel from the Setup menu; select the Control panel type from the Panel menu; select the respective firmware release from the Firmware menu; click OK.
6. To download a specific page: click the DWLoad button on the page in question. To Download several pages: select the required page from the Pages menu, right click, Select (a on the page Icon indicates that it will be downloaded); repeat the procedure for all the required Pages; right click again then select DWLoad.

Figure 32 The Panel Programming Phase
4. Go back to step 1 to program another Output option or, press the Next phase key 9 to go to the following Programming Phase (see Column A).
The PANEL Programming Phase
The PANEL LED will blink to indicate that the system is ready to program the User Code, Day and Night Mode Times and current Time and Date. During this phase, the keys and LEDs will operate in accordance with the options preceded by in the panes on the Programming Overlay, see Figure 32. 1. Using the keys in columns C and D, select the parameter you want to program (refer to the respective paragraph for details) or, press the Next phase key 9 to go to the following Programming Phase (see Column A). n User Code (Key/LED 1) The LED will go On to indicate that the system is ready to start the programming procedure. Using keys 0 through 9, type in a 4 digit User Code. The LED will go Off after entry of the fourth digit (indicating that the User Code has been accepted). n Day Mode (Key/LED 2) The LED will go On to indicate that the system is ready to start the programming procedure. Using keys 0 through 9, type in the Time when the changeover from Night to Day Mode must occur. Enter two digits for the Hour (00 to for Midnight) and two for the Minutes (00 to 59). The LED will go Off after entry of the fourth digit (indicating that the setting has been accepted). n Night Mode (Key/LED 4) The LED will go On to indicate that the system is ready to start the programming procedure. Using keys 0 through 9, type in the Time (formatted as per Day Mode) when the changeover from Day to Night Mode must occur. The LED will go Off after entry of the fourth digit (indicating that the setting has been accepted).
M640 sec M M128 sec Alarm verific. M320 sec M M64 sec Detect missing M160 sec MOC output M32 sec Silen. Out R M MALARM M16 sec Pre-alarm on R M MNAC2 Alarm M8 sec Test on NACs M MNAC1 Alarm M4 sec C Call-point alarm M NAC2 Pre-alarm MN M2 sec Gas detector M5 sec NAC1 Pre-alarm MN M1 sec B Pre-alarm time Alarm User code Stabilization time Extinguish. time Verification time Reset Night mode Silenceable outs Activation zones DL output delay Double knock Date Configuration 2 Next phase Refresh time Pre-alarm Day mode Reset time Silence time Disablement Clock Configuration 1 Increase time Mains off delay Increase time Increase time Next Option Decrease time Next Output
n Clock (Key/LED 5) The LED will go On to indicate that the system is ready to start the programming procedure. Using keys 0 through 9, type in the current Time (format as per Day Mode). n Date (Key/LED 7) The LED will go On to indicate that the system is ready to start the programming procedure. Using keys 0 through 9, enter the respective two digits for the Day (00 to 31), Month (00 to 12) and Year (00 to 99). The LED will go Off after entry of the last digit (indicating that the setting has been accepted). Wrong entries will be signalled by an audible error signal. n Mains Off Delay (Key/LED 8) The LED will go On to indicate that the system is ready to start the programming procedure. Using keys 0 through 9, type in the length of time the Control panel must wait before signalling a Mains Failure event. Enter four digits (0000 through 9999 minutes). The LED will go Off after entry of the last digit (indicating that the Mains Off Delay has been accepted). Wrong entries will be signalled by an audible error signal.

 

Tags

Review GR-D93 XL4600DL DV-440 Vivicam 3315 W400SE MZ-33 WHP 465 LV3767 M740E Wizzle AG401 KH 8090 M-3100U GR-D375U Shenmue AND Bass CD1401B-57 HP 6500 FW780P-21S T 1030 RX-V540 Convertible 2005 RS261mdpn FX500B Charlotte HV3 Revenge LN40A550 TX-34P300K BD-7181W DV8400 500-T Nuvi 250 WT46S512BY Series PD-04 SA-VE525 1064 D Ericsson T20S RC-1082 UX-67 PDP-507XA GSA-E20N Fasttrack 47LH70 ICF-C743L 2 1 D-NE730 M1350 LG U900 Management 4 05 CDX-CA530X Server DMC-TS2 ADP8322 L3100 DZ-GX5100E 8800 DPF I30 CW SCX-5315F Grimlock WD-1248 CT-17 Description Turnamat S TCR Id-1 SHE43C-shu42 Scanmaker 8700 206 207 YZF-R6-2003 RC-591 Client DSC-W300 UE-37C5100QW L1915S JA-83K Audiobahn AEQ8 FE-X42 PEG-TJ27 E1 M5 2000 CK136T Walking PUP Bronco-1996 MZ-E700 Junior ALL-IN-ONE XD435U ICD-S7 Dect1222S-02 Router 108 BDZ-L95 Coolpix P3 MC-7684B WV-CP480 Suunto T6C Cndv-90MT Elite X800 Pcie SP0802N-R TX-SR602

 

manuel d'instructions, Guide de l'utilisateur | Manual de instrucciones, Instrucciones de uso | Bedienungsanleitung, Bedienungsanleitung | Manual de Instruções, guia do usuário | инструкция | návod na použitie, Užívateľská príručka, návod k použití | bruksanvisningen | instrukcja, podręcznik użytkownika | kullanım kılavuzu, Kullanım | kézikönyv, használati útmutató | manuale di istruzioni, istruzioni d'uso | handleiding, gebruikershandleiding

 

Sitemap

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101