Goodman Manufacturing IO-258B Condensing Unit
|
|
Bookmark Goodman Manufacturing IO-258B Condensing Unit |
About Goodman Manufacturing IO-258B Condensing UnitHere you can find all about Goodman Manufacturing IO-258B Condensing Unit like manual and other informations. For example: review.
Goodman Manufacturing IO-258B Condensing Unit manual (user guide) is ready to download for free.
On the bottom of page users can write a review. If you own a Goodman Manufacturing IO-258B Condensing Unit please write about it to help other people. [ Report abuse or wrong photo | Share your Goodman Manufacturing IO-258B Condensing Unit photo ]
Manual
Preview of first few manual pages (at low quality). Check before download. Click to enlarge.
Download
(English)Goodman Manufacturing IO-258B Condensing Unit, size: 278 KB |
Goodman Manufacturing IO-258B Condensing Unit
User reviews and opinions
No opinions have been provided. Be the first and add a new opinion/review.
Documents
CONDENSING UNIT
AIR CONDITIONING INSTALLATION & SERVICE REFERENCE Important Safety Instructions
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owners and installers responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage.
Goodman Manufacturing Company, L.P. 2005-North Loop West, Suite 400, Houston, TX 77092 www.goodmanmfg.com -or- www.amana-hac.com P/N: IO-258B Date: April 2006 tion and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. Should you have any questions please contact the local office of the EPA. If replacing a condensing unit or air handler, the system must be manufacturer approved and Air Conditioning and Refrigeration Institute (ARI) matched. NOTE: Installation of unmatched systems is strongly discouraged. Operating the unit in a structure that is not complete (either as part of new construction or renovation) will void the warranty.
WARNING
Hazards or unsafe practices could result in property damage, product damage, severe personal injury or death.
Installation Clearances
Special consideration must be given to location of the condensing unit(s) in regard to structures, obstructions, other units, and any/all other factors that may interfere with air circulation. Where possible, the top of the unit should be completely unobstructed; however, if vertical conditions require placement beneath an obstruction there should be a minimum of 60 inches between the top of the unit and the obstruction(s). The specified dimensions meet requirements for air circulation only. Consult all appropriate regulatory codes prior to determining final clearances. Another important consideration in selecting a location for the unit(s) is the angle to obstructions. Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance. Corner installations are strongly discouraged.
CAUTION
Hazards or unsafe practices which may result in property damage, product damage, personal injury or death.
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
ONLY individuals meeting the requirements of an Entry Level Technician as specified by the Air Conditioning and Refrigeration Institute (ARI) may use this information. Attempting to install or repair this unit without such background may result in product damage, personal injury, or death.
Shipping Inspection
Always keep the unit upright; laying the unit on its side or top may cause equipment damage. Shipping damage, and subsequent investigation is the responsibility of the carrier. Verify the model number, specifications, electrical characteristics, and accessories are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for transportation damage or installation of incorrectly shipped units.
NOT RECOMMENDED
C AA AA
OK! OK!
Codes & Regulations
This product is designed and manufactured to comply with national codes. Installation in accordance with such codes and/ or prevailing local codes/regulations is the responsibility of the installer. The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations. The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introducA AA AA
Minimum Airflow Clearance Model Type A B C Residential 10" 10" 18" Light Commercial 12" 12" 18"
AA 20" 24"
This unit can be located at ground floor level or on flat roofs. At ground floor level, the unit must be on a solid, level foundation that will not shift or settle. To reduce the possibility of sound transmission, the foundation slab should not be in contact with or be an integral part of the building foundation. Ensure the foundation is sufficient to support the unit. A concrete slab raised above ground level provides a suitable base.
To avoid possible explosion, use only returnable (not disposable) service cylinders when removing refrigerant from a system. Ensure the cylinder is free of damage which could lead to a leak or explosion. Ensure the hydrostatic test date does not exceed 5 years. Ensure the pressure rating meets or exceeds 400 lbs. When in doubt, do not use cylinder.
Rooftop Installations
If it is necessary to install this unit on a roof structure, ensure the roof structure can support the weight and that proper consideration is given to the weather-tight integrity of the roof. Since the unit can vibrate during operation, sound vibration transmission should be considered when installing the unit. Vibration absorbing pads or springs can be installed between the condensing unit legs or frame and the roof mounting assembly to reduce noise vibration.
Refrigerant Lines
The compressor POE oil for R-410A units is extremely susceptible to moisture absorption and could cause compressor failure. Do not leave system open to atmosphere any longer than necessary for installation.
Use only refrigerant grade (dehydrated and sealed) copper tubing to connect the condensing unit with the indoor evaporator. After cutting the tubing, install plugs to keep refrigerant tubing clean and dry prior to and during installation. Tubing should always be cut square keeping ends round and free from burrs. Clean the tubing to prevent contamination. Do NOT let refrigerant lines come in direct contact with plumbing, ductwork, floor joists, wall studs, floors, and walls. When running refrigerant lines through a foundation or wall, openings should allow for sound and vibration absorbing material to be placed or installed between tubing and foundation. Any gap between foundation or wall and refrigerant lines should be filled with a pliable silicon-based caulk, RTV or a vibration damping material. Avoid suspending refrigerant tubing from joists and studs with rigid wire or straps that would come in contact with the tubing. Use an insulated or suspension type hanger. Keep both lines separate and always insulate the suction line. These sizes are suitable for line lengths of 74 feet or less. If a run of more than fifty feet is required, refer to the Remote Cooling Service Manual or contact your distributor for assistance.
REFRIGERANT LINE LENGTH (Ft) Cond Unit Tons Suct Liq 0-24 25-49 Line Diameter (In. OD) Suct Liq Suct Liq 50-74***
Safe Refrigerant Handling
While these items will not cover every conceivable situation, they should serve as a useful guide.
To avoid possible injury, explosion or death, practice safe handling of refrigerants.
Refrigerants are heavier than air. They can "push out" the oxygen in your lungs or in any enclosed space.To avoid possible difficulty in breathing or death: Never purge refrigerant into an enclosed room or space. By law, all refrigerants must be reclaimed. If an indoor leak is suspected, throughly ventilate the area before beginning work. Liquid refrigerant can be very cold. To avoid possible frostbite or blindness, avoid contact and wear gloves and goggles. If liquid refrigerant does contact your skin or eyes, seek medical help immediately. Always follow EPA regulations. Never burn refrigerant, as poisonous gas will be produced.
To avoid possible explosion: Never apply flame or steam to a refrigerant cylinder. If you must heat a cylinder for faster charging, partially immerse it in warm water. Never fill a cylinder more than 80% full of liquid refrigerant. Never add anything other than R-22 to an R-22 cylinder or R-410A to an R-410A cylinder. The service equipment used must be listed or certified for the type of refrigerant used. Store cylinders in a cool, dry place. Never use a cylinder as a platform or a roller.
1 1/2 1/3 1/5 5/8 5/8 5/8 3/4 3/4 7/8 7/8
1/4 1/4 1/4 3/8 3/8 3/8 3/8
3/4 3/4 3/4* 3/4** 7/8** 1 1/1/8
3/8 3/8 3/8 3/8 3/8 3/8 3/8
3/4 3/4 7/8 7/8** 1 1/1/1/8
* 7/8" required for full ratings ** 1 1/8" required for full ratings *** Lines greater than 74 feet in length or vertical elevation changes more than 50 feet refer to the Remote Cooling Service Manual or contact your distributor for assistance.
Liquid Line Suction Line
1. The ends of the refrigerant lines must be cut square, deburred, cleaned, and be round and free from nicks or dents. Any other condition increases the chance of a refrigerant leak.
Mounting the evaporator coil above the condensing unit will require an inverted loop in the suction line adjacent or near the connection to the evaporator. The top of the loop must be slightly higher than the top of the coil.
2. Sweep the refrigerant line with nitrogen or inert gas during brazing to prevent the formation of copper-oxide inside the refrigerant lines. The POE oils used in R-410A applications will clean any copper-oxide present from the inside of the refrigerant lines and spread it throughout the system. This may cause a blockage or failure of the metering device. 3. After brazing, quench the joints with water or a wet cloth to prevent overheating of the service valve. 4. Ensure the filter drier paint finish is intact after brazing. If the paint of the steel filter drier has been burned or chipped, repaint or treat with a rust preventative. This is especially important on suction line filter driers which are continually wet when the unit is operating. NOTE: Be careful not to kink or dent refrigerant lines. Kinked or dented lines will cause poor performance or compressor damage. Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing. NOTE: Before brazing, verify indoor piston size by checking the piston kit chart packaged with indoor unit.
Mounting the condensing unit above the evaporator coil will require oil traps at equal intervals along the suction line. Install 1 oil trap for a height difference of 1525 feet between indoor and outdoor units. Install 2 oil traps for a difference of 26-50 feet, 3 for 51-100 feet, and 4 for 101-150 feet.
Insulation is necessary to prevent condensation from forming and dropping from the suction line. Armflex (or satisfactory equivalent) with 3/8 min. wall thickness is recommended. In severe conditions (hot, high humidity areas) 1/2 insulation may be required. Insulation must be installed in a manner which protects tubing from damage and contamination. Where possible, drain as much residual compressor oil from existing systems, lines, and traps; pay close attention to low areas where oil may collect. NOTE: If changing refrigerant types, ensure the indoor coil and metering device is compatible with the type of refrigerant being used; otherwise, the indoor coil must be replaced.
Leak Testing (Nitrogen or Nitrogen-Traced)
To avoid the risk of fire or explosion, never use oxygen, high pressure air or flammable gases for leak testing of a refrigeration system.
Burying Refrigerant Lines
If burying refrigerant lines can not be avoided, use the following checklist. 1. Insulate liquid and suction lines separately. 2. Enclose all underground portions of the refrigerant lines in waterproof material (conduit or pipe) sealing the ends where tubing enters/exits the enclosure. 3. If the lines must pass under or through a concrete slab, ensure lines are adequately protected and sealed.
To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 150 psig.
Pressure test the system using dry nitrogen and soapy water to locate leaks. If you wish to use a leak detector, charge the system to 10 psi using the appropriate refrigerant then use nitrogen to finish charging the system to working pressure then apply the detector to suspect areas. If leaks are found, repair them. After repair, repeat the pressure test. If no leaks exist, proceed to system evacuation.
Refrigerant Line Connections
IMPORTANT: To avoid overheating the service valve, TXV valve, or filter drier while brazing, wrap the component with a wet rag, or use a thermal heat trap compound as recommended by the compound manufacturer. Use a brazing alloy of 2% minimum silver content. Do not use flux.
System Evacuation
Condensing unit liquid and suction valves are closed to contain the charge within the unit. The unit is shipped with the valve stems closed and caps installed. Do not open valves until the system is evacuated.
REFRIGERANT UNDER PRESSURE!
Failure to follow proper procedures may cause property damage, personal injury or death.
1. Connect the vacuum pump with 250 micron capability to the service valves. 2. Evacuate the system to 250 microns or less using suction and liquid service valves. Using both valves is necessary as some compressors create a mechanical seal separating the sides of the system. 3. Close pump valve and hold vacuum for 10 minutes. Typically pressure will rise during this period.
5000 4500
VACUUM IN MICRONS
To avoid the risk of fire or equipment damage, use copper conductors.
NOTICE
Units with reciprocating compressors and non-bleed TXVs require a Hard Start Kit.
NO LEAKS NO CONDENSIBLES 6 MINUTES CONDENSIBLES OR SMALL LEAK PRESENT LEAK(S) PRESENT
The condensing unit rating plate lists pertinent electrical data necessary for proper electrical service and overcurrent protection. Wires should be sized to limit voltage drop to 2% (max.) from the main breaker or fuse panel to the condensing unit. Consult the NEC, CEC, and all local codes to determine the correct wire gauge and length. Local codes often require a disconnect switch located near the unit; do not install the switch on the unit. Refer to the installation instructions supplied with the indoor furnace/air handler for specific wiring connections and indoor unit configuration. Likewise, consult the instructions packaged with the thermostat for mounting and location information.
Three Phase Compressor Rotation
Use care when handling scroll compressors. Dome temperatures could be hot.
Three phase scrolls are power phase dependent and can compress in more than one direction. Verify proper rotation for three phase compressors by ensuring the suction pressure drops and discharge pressure rises when the compressor is energized. NOTE: When operated in reverse, a three phase scroll compressors is noisier and its current draw substantially reduced compared to marked values. To correct, disconnect power and switch any two leads at the unit contactor and re-observe.
If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to startup. If pressure rises above 1000 microns but holds steady below 2000 microns, moisture and/or noncondensibles may be present or the system may have a small leak. Return to step 2: If the same result is encountered check for leaks as previously indicated and repair as necessary then repeat evacuation.
High Voltage Connections
Route power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagram provided inside the control panel cover.
If pressure rises above 2000 microns, a leak is present.
Check for leaks as previously indicated and repair as necessary then repeat evacuation.
Low Voltage Connections
Condensing unit control wiring requires 24 Volt minimum, 25VA service from the indoor transformer. Low voltage wiring for twostage units depends on the thermostat used and the number of control wires between the indoor unit and the condensing unit. Route control wires through the low voltage port and terminate in accordance with the wiring diagram provided inside the control panel cover.
Electrical Connections
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death due to electric shock. Wiring must conform with NEC or CEC and all local codes. Undersized wires could cause poor equipment performance, equipment damage or fire.
Thermostat Single-Stage Heating with Single-Stage Cooling
Use refrigerant certified to ARI standards. Used refrigerant may cause compressor damage, and will void the warranty. Most portable machines cannot clean used refrigerant to meet ARI standards.
DEHUM TWIN
FURNACE OR AIR HANDLER
Violation of EPA regulations may result in fines or other penalties.
REMOTE *R is only used with models that have the Comfort Alert Module.
Operating the compressor with the suction valve closed will void the warranty and cause serious compressor damage.
Single-Stage Thermostat with Two Low Voltage Wires to Remote
NOTE: For two-stage condensing units, refer to the Installation Instructions supplied with the variable speed indoor units for field wiring connections.
YL0/Y1 W2
Final Charge Adjustment
The outdoor temperature must be 60F or higher. Set the room thermostat to COOL, fan switch to AUTO, and set the temperature control well below room temperature. After system has stabilized per startup instructions, check subcooling and superheat as detailed in the following section.
Thermostat Two-Stage Heating with Two-Stage Cooling
Fixed Orifice
YLO/YI
OD UNIT *R is only used with models that have the Comfort Alert Module.
To prevent personal injury, carefully connect and disconnect manifold gauge hoses. Escaping liquid refrigerant can cause burns. Do not vent refrigerant into the atmosphere. Recover all refrigerant during system repair and before final unit disposal.
1. Purge gauge lines. Connect service gauge manifold to base-valve service ports. Run system at least 10 minutes to allow pressure to stabilize. 2. Temporarily install thermometer on suction (large) line near suction line service valve with adequate contact and insulate for best possible reading. 3. Refer to the superheat table provided for proper system superheat. Add charge to lower superheat or recover charge to raise superheat.
SYSTEM SUPERHEAT
Am bient Condenser Inlet Tem p. (F Drybulb) Return Air Tem perature (F Drybulb) 35 37
Two-Stage Thermostat with Three Low Voltage Wires to Remote
System Start Up
Adequate refrigerant charge for a matching evaporator and 15 feet lineset is supplied with the condensing unit. NOTE: If lineset exceeds 15 feet in length, refrigerant should be added at.6 ounces per foot of liquid line. Open each valve only until the top of the stem is 1/8 from the retainer. To avoid loss of refrigerant, do not apply pressure to the retainer. 1. Break vacuum by fully opening liquid and suction base valves. 2. Set thermostat to call for cooling. Check indoor and outdoor fan operation and allow system to stabilize for 10 minutes for fixed orifices and 20 minutes for expansion valves.
Charge Verification
Do not overcharge system with refrigerant. Do not operate unit in a vacuum or at negative pressure. Failure to follow proper procedures may cause property damage, personal injury or death.
4. Disconnect manifold set, installation is complete.
Superheat Formula = Suct. Line Temp. - Sat. Suct. Temp.
SATURATED SUCTION PRESSURE TEMPERATURE CHART SATURATED SUCTION SUCTION PRESSURE TEMPERATURE F
PSIG R-48 R-410A 20 21
SATURATED LIQUID PRESSURE TEMPERATURE CHART LIQUID PRESSURE
PSIG 375 405
SATURATED LIQUID TEMPERATURE F
R-155 R-410A 112 118
Expansion Valve System
1. Purge gauge lines. Connect service gauge manifold to base-valve service ports. Run system at least 10 minutes to allow pressure to stabilize. 2. Temporarily install thermometer on liquid (small) line near liquid line service valve with adequate contact and insulate for best possible reading. 3. Check subcooling and superheat. Systems with TXV application should have a subcooling and superheat of F. a. If subcooling and superheat are low, adjust TXV to 9 3F then check subcooling. b. If subcooling is low and superheat is high, add charge to raise subcooling to 9 3F then check superheat. c. If subcooling and superheat are high, adjust TXV valve to 9 3F then check subcooling. d. If subcooling is high and superheat is low, adjust TXV valve to 9 3F superheat and remove charge to lower the subcooling to 9 3F. NOTE: Do NOT adjust the charge based on suction pressure unless there is a gross undercharge. 4. Disconnect manifold set, installation is complete.
Subcooling Formula = Sat. Liquid Temp. - Liquid Line Temp.
Troubleshooting Information
Complaint No Cooling Compressor and Condenser Fan will not start Unsatisfactory Cooling System Operating Pressures
Compressor runs - goes off on overload
System runs continuously - little cooling
SYMPTOM
Too cool and then too warm
POSSIBLE CAUSE DOTS IN ANALYSIS GUIDE INDICATE "POSSIBLE CAUSE"
Certain areas to cool others to warm
Compressor will not start - fan runs
Compressor cycles on overload
Not cool enough on warm days
Evaporator fan will not start
Condenser fan will not start
High suction pressure
Low suction pressure
Compressor is noisy
Test Method Remedy High head pressure Test Voltage Impact Fuse Size & Type Inspect Connection - Tighten Test Circuits with Ohmmeter Test Continuity of Overloads Test Continuity of Thermostat and Wiring Check Control Circuit with Voltmeter Test Capacitor Test Continuity of Overload Test Motor Windings Use Test Cord Test Continuity of Coil and Contacts Test Continuity of Coil and Contacts Test Control Circuit with Voltmeter Test Voltage Repair or Replace Test Motor Windings Check Resistance of Anticipator Test For Leaks, Add Refrigerant Replace Restricted Part Replace Line Replace Line Speed Blower, Check Duct Static Pressure Reduce Blower Speed Recover Part of Charge Recover Charge, Evacuate, Recharge Remove Obstruction to Air Flow Check Windows, Doors, Vent Fans, Etc. Relocate Thermostat Readjust Air Volume Dampers Refigure Cooling Load Replace Compressor Test Compressor Efficiency Test Compressor Efficiency Reset and Test Control Test Voltage Replace Valve Replace Valve Replace Valve Replace Valve Tighten Bulb Bracket Check Valve Operation Tighten Bolts
System will not start
Power Failure Blown Fuse Loose Connection Shorted or Broken Wires Open Overload Faulty Thermostat Faulty Transformer Shorted or Open Capacitor Internal Compressor Overload Open Shorted or Grounded Compressor Compressor Stuck Faulty Compressor Contactor Faulty Fan Relay Open Control Circuit Low Voltage Faulty Evaporator Fan Motor Shorted or Grounded Fan Motor Improper Cooling Anticipator Shortage or Refrigerant Restricted Liquid Line Undersized Liquid Line Undersized Suction Line Not Enough Air across Indoor Coil Too Much Air across Indoor Coil Overcharge of Refrigerant Noncondensibles Recirculation of Condensing Air Infiltration of Outdoor Air Improperly Located Thermostat Air Flow Unbalanced System Undersized Broken Internal Parts Broken Valves Inefficient Compressor High Pressure Control Open Unbalanced Power, 3PH Wrong Type Expansion Valve Expansion Valve Restricted Oversized Expansion Valve Undersized Expansion Valve Expansion Valve Bulb Loose Inoperative Expansion Valve Loose Hold-down Bolts
Low head pressure
For detailed service information refer to the Remote Condensing Unit Service manual.
CONDENSING UNIT
AIR CONDITIONING INSTALLATION & SERVICE REFERENCE Important Safety Instructions
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owners and installers responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage.
2005-2010 Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com -or- www.amana-hac.com P/N: IO-258J Date: May 2010 To register your Amana brand unit, go to www.amana-hac.com. Click on the word Warranty located on the top right of the home page. Next, click on the word Product Registration located on the left side of the Warranty page and complete the forms in the manner indicated on the Product Registration page. Product limited warranty certificates for models currently in production can be viewed at www.goodmanmfg.com or www.amana-hac.com. If your model is not currently in production or does not appear on the website, please contact your installing contractor or contact customer service (877-254-4729) to obtain a copy of your warranty certificate. Each product overview page contains a Product Warranty link; by clicking on it you will be able to view the limited warranty coverage for that specific product. To view warranty registration information, click on the Product Warranty text on the left navigation panel on the home page of each website. The Online Product Registration pages are located in this same section.
WARNING
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
Shipping Inspection
Always keep the unit upright; laying the unit on its side or top may cause equipment damage. Shipping damage, and subsequent investigation is the responsibility of the carrier. Verify the model number, specifications, electrical characteristics, and accessories are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for transportation damage or installation of incorrectly shipped units.
Important Note to the Owner regarding Product Warranty
Your warranty certificate is supplied as a separate document with the unit installed by your contractor. Read the limited warranty certificate carefully to determine what is and is not covered and keep the warranty certificate in a safe place. If you are unable to locate the warranty certificate please contact your installing contractor or contact customer service (877254-4729) to obtain a copy. To receive the 10-Year Parts Limited Warranty for Amana branded products, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec. Complete warranty details available at your local dealer or at www.amana-hac.com. To receive the 10-Year Parts Limited Warranty for Goodman branded products, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec. Complete warranty details available at your local dealer or at www.goodmanmfg.com. IMPORTANT: To register your Goodman brand unit, go to www.goodmanmfg.com. Click on the word Warranty located on the left side of the home page. Next, click on the word Product Registration located on the left side of the Warranty page and complete the forms in the manner indicated on the Product Registration page.
Codes & Regulations
This product is designed and manufactured to comply with national codes. Installation in accordance with such codes and/ or prevailing local codes/regulations is the responsibility of the installer. The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations. The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. Should you have any questions please contact the local office of the EPA. If replacing a condensing unit or air handler, the system must be manufacturer approved and Air Conditioning, Heating and Refrigeration Institute (AHRI) matched. NOTE: Installation of unmatched systems is strongly discouraged. Operating the unit in a structure that is not complete (either as part of new construction or renovation) will void the warranty.
Installation Clearances
Special consideration must be given to location of the condensing unit(s) in regard to structures, obstructions, other units, and any/all other factors that may interfere with air circulation. Where possible, the top of the unit should be completely unobstructed; however, if vertical conditions require placement be-
neath an obstruction there should be a minimum of 60 inches between the top of the unit and the obstruction(s). The specified dimensions meet requirements for air circulation only. Consult all appropriate regulatory codes prior to determining final clearances. Another important consideration in selecting a location for the unit(s) is the angle to obstructions. Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance. Corner installations are strongly discouraged.
Safe Refrigerant Handling
While these items will not cover every conceivable situation, they should serve as a useful guide.
Refrigerants are heavier than air. They can "push out" the oxygen in your lungs or in any enclosed space.To avoid possible difficulty in breathing or death: Never purge refrigerant into an enclosed room or space. By law, all refrigerants must be reclaimed. If an indoor leak is suspected, throughly ventilate the area before beginning work. Liquid refrigerant can be very cold. To avoid possible frostbite or blindness, avoid contact and wear gloves and goggles. If liquid refrigerant does contact your skin or eyes, seek medical help immediately. Always follow EPA regulations. Never burn refrigerant, as poisonous gas will be produced.
NOT RECOMMENDED
C AA AA
OK! OK!
Minimum Airflow Clearance Model Type A B C Residential 10" 10" 18" Light Commercial 12" 12" 18"
To avoid possible explosion: Never apply flame or steam to a refrigerant cylinder. If you must heat a cylinder for faster charging, partially immerse it in warm water. Never fill a cylinder more than 80% full of liquid refrigerant. Never add anything other than R-22 to an R-22 cylinder or R-410A to an R-410A cylinder. The service equipment used must be listed or certified for the type of refrigerant used. Store cylinders in a cool, dry place. Never use a cylinder as a platform or a roller.
AA 20" 24"
To avoid possible explosion, use only returnable (not disposable) service cylinders when removing refrigerant from a system. Ensure the cylinder is free of damage which could lead to a leak or explosion. Ensure the hydrostatic test date does not exceed 5 years. Ensure the pressure rating meets or exceeds 400 lbs. When in doubt, do not use cylinder.
This unit can be located at ground floor level or on flat roofs. At ground floor level, the unit must be on a solid, level foundation that will not shift or settle. To reduce the possibility of sound transmission, the foundation slab should not be in contact with or be an integral part of the building foundation. Ensure the foundation is sufficient to support the unit. A concrete slab raised above ground level provides a suitable base.
Rooftop Installations
If it is necessary to install this unit on a roof structure, ensure the roof structure can support the weight and that proper consideration is given to the weather-tight integrity of the roof. Since the unit can vibrate during operation, sound vibration transmission should be considered when installing the unit. Vibration absorbing pads or springs can be installed between the condensing unit legs or frame and the roof mounting assembly to reduce noise vibration.
Refrigerant Lines
CAUTION
The compressor POE oil for R-410A units is extremely susceptible to moisture absorption and could cause compressor failure. Do not leave system open to atmosphere any longer than necessary for installation.
Use only refrigerant grade (dehydrated and sealed) copper tubing to connect the condensing unit with the indoor evaporator. After cutting the tubing, install plugs to keep refrigerant tubing clean and dry prior to and during installation. Tubing should always be cut square keeping ends round and free from burrs. Clean the tubing to prevent contamination.
To avoid possible injury, explosion or death, practice safe handling of refrigerants.
Do NOT let refrigerant lines come in direct contact with plumbing, ductwork, floor joists, wall studs, floors, and walls. When running refrigerant lines through a foundation or wall, openings should allow for sound and vibration absorbing material to be placed or installed between tubing and foundation. Any gap between foundation or wall and refrigerant lines should be filled with a pliable silicon-based caulk, RTV or a vibration damping material. Avoid suspending refrigerant tubing from joists and studs with rigid wire or straps that would come in contact with the tubing. Use an insulated or suspension type hanger. Keep both lines separate and always insulate the suction line. These sizes are recommended for line lengths of 79 feet or less to obtain optimum performance. For alternate line sizing options or runs of more than 79 feet, refer to Remote Cooling Service Manual or TP-107 Long Line Set Application R-410A or contact your distributor for assistance.
RECOMMENDED INTERCONNECTING TUBING (Ft) Cond Unit Tons 0-24 Suct 25-49 Line Diameter (In. OD) Liq Suct Liq 50-79* Liq
Insulation is necessary to prevent condensation from forming and dropping from the suction line. Armflex (or satisfactory equivalent) with 3/8 min. wall thickness is recommended. In severe conditions (hot, high humidity areas) 1/2 insulation may be required. Insulation must be installed in a manner which protects tubing from damage and contamination. Where possible, drain as much residual compressor oil from existing systems, lines, and traps; pay close attention to low areas where oil may collect. NOTE: If changing refrigerant types, ensure the indoor coil and metering device is compatible with the type of refrigerant being used; otherwise, the indoor coil must be replaced.
Burying Refrigerant Lines
If burying refrigerant lines can not be avoided, use the following checklist. 1. Insulate liquid and suction lines separately. 2. Enclose all underground portions of the refrigerant lines in waterproof material (conduit or pipe) sealing the ends where tubing enters/exits the enclosure. 3. If the lines must pass under or through a concrete slab, ensure lines are adequately protected and sealed.
1 1/2 1/3 1/5
5/8 5/8 5/8 3/4 7/8 7/8 7/8
1/4 1/4 1/4 3/8 3/8 3/8 3/8
3/4 3/4 3/4 7/1/1/1/8
3/8 3/8 3/8 3/8 3/8 3/8 3/8
3/4 3/4 7/1/1/1/1/8
Refrigerant Line Connections IMPORTANT
To avoid overheating the service valve, TXV valve, or filter drier while brazing, wrap the component with a wet rag, or use a thermal heat trap compound. Be sure to follow the manufacturers instruction when using the heat trap compound. Note: Remove Schrader valves from service valves before brazing tubes to the valves. Use a brazing alloy of 2% minimum silver content. Do not use flux. Torch heat required to braze tubes of various sizes is proportional to the size of the tube. Tubes of smaller size require less heat to bring the tube to brazing temperature before adding brazing alloy. Applying too much heat to any tube can melt the tube. Service personnel must use the appropriate heat level for the size of the tube being brazed. Note: The use of a heat shield when brazing is recommended to avoid burning the serial plate or the finish on the unit. 1. The ends of the refrigerant lines must be cut square, deburred, cleaned, and be round and free from nicks or dents. Any other condition increases the chance of a refrigerant leak. 2. Sweep the refrigerant line with nitrogen or inert gas during brazing to prevent the formation of copper-oxide inside the refrigerant lines. The POE oils used in R-410A applications will clean any copper-oxide present from the inside of the refrigerant lines and spread it throughout the system. This may cause a blockage or failure of the metering device. 3. After brazing, quench the joints with water or a wet cloth to prevent overheating of the service valve. 4. Ensure the filter drier paint finish is intact after brazing. If the paint of the steel filter drier has been burned or chipped, 3
* Lines greater than 79 feet in length or vertical elevation changes more than 50 feet refer to the Rem ote Cooling Service Manual or contact your distributor for assistance.
NOTE: Line sets for VSC130181**, VSC130241**, and VSC130301** shall not exceed 75 feet.
repaint or treat with a rust preventative. This is especially important on suction line filter driers which are continually wet when the unit is operating. NOTE: Be careful not to kink or dent refrigerant lines. Kinked or dented lines will cause poor performance or compressor damage. Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing.
separating the sides of the system. 3. Close pump valve and hold vacuum for 10 minutes. Typically pressure will rise during this period.
If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to startup.
5000 4500
VACUUM IN MICRONS
NOTE: Before brazing, verify indoor piston size by checking the piston kit chart packaged with indoor unit.
1000 CONDENSIBLES OR SMALL LEAK PRESENT NO LEAKS NO CONDENSIBLES 6 MINUTES LEAK(S) PRESENT
Leak Testing (Nitrogen or Nitrogen-Traced)
To avoid the risk of fire or explosion, never use oxygen, high pressure air or flammable gases for leak testing of a refrigeration system.
To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 150 psig.
Pressure test the system using dry nitrogen and soapy water to locate leaks. If you wish to use a leak detector, charge the system to 10 psi using the appropriate refrigerant then use nitrogen to finish charging the system to working pressure then apply the detector to suspect areas. If leaks are found, repair them. After repair, repeat the pressure test. If no leaks exist, proceed to system evacuation.
If pressure rises above 1000 microns but holds steady below 2000 microns, moisture and/or noncondensibles may be present or the system may have a small leak. Return to step 2: If the same result is encountered check for leaks as previously indicated and repair as necessary then repeat evacuation. Check for leaks as previously indicated and repair as necessary then repeat evacuation.
If pressure rises above 2000 microns, a leak is present.
System Evacuation
Condensing unit liquid and suction valves are closed to contain the charge within the unit. The unit is shipped with the valve stems closed and caps installed. Do not open valves until the system is evacuated.
Electrical Connections
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death due to electric shock. Wiring must conform with NEC or CEC and all local codes. Undersized wires could cause poor equipment performance, equipment damage or fire.
REFRIGERANT UNDER PRESSURE!
Failure to follow proper procedures may cause property damage, personal injury or death.
NOTE: Scroll compressors should never be used to evacuate or pump down a heat pump or air conditioning system.
Prolonged operation at suction pressures less than 20 psig for more than 5 seconds will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seal.
1. Connect the vacuum pump with 250 micron capability to the service valves. 2. Evacuate the system to 250 microns or less using suction and liquid service valves. Using both valves is necessary as some compressors create a mechanical seal 4
To avoid the risk of fire or equipment damage, use copper conductors.
NOTICE
Units with reciprocating compressors and non-bleed TXVs require a Hard Start Kit.
The condensing unit rating plate lists pertinent electrical data necessary for proper electrical service and overcurrent protection. Wires should be sized to limit voltage drop to 2% (max.)
from the main breaker or fuse panel to the condensing unit. Consult the NEC, CEC, and all local codes to determine the correct wire gauge and length. Local codes often require a disconnect switch located near the unit; do not install the switch on the unit. Refer to the installation instructions supplied with the indoor furnace/air handler for specific wiring connections and indoor unit configuration. Likewise, consult the instructions packaged with the thermostat for mounting and location information.
Overcurrent Protection
The following overcurrent protection devices are approved for use. Time delay fuses HACR type circuit breakers These devices have sufficient time delay to permit the motorcompressor to start and accelerate its load.
Single-Stage Thermostat with Two Low Voltage Wires to Remote
NOTE: For two-stage condensing units, refer to the Installation Instructions supplied with the variable speed indoor units for field wiring connections.
YL0/Y1 W2
Three Phase Compressor Rotation
Use care when handling scroll compressors. Dome temperatures could be hot.
Three phase compressors are power phase dependent and can rotate in either direction. Verify proper rotation for three phase compressors by ensuring the suction pressure drops and discharge pressure rises when the compressor is energized. NOTE: When operated in reverse, a three phase scroll compressors is noisier and its current draw substantially reduced compared to marked values. To correct, disconnect power and switch any two leads at the unit contactor and re-observe.
Thermostat Two-Stage Heating with Two-Stage Cooling
YLO/YI
DEHUM TWIN
FURNACE OR AIR HANDLER
OD UNIT
Two-Stage Thermostat with Three Low Voltage Wires to Remote
High Voltage Connections
Route power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagram provided inside the control panel cover.
System Start Up
POSSIBLE REFRIGERANT LEAK To avoid a possible refrigerant leak, open the service valves until the top of the stem is 1/8 from the retainer.
When opening valves with retainers, open each valve only until the top of the stem is 1/8 from the retainer. To avoid loss of refrigerant, DO NOT apply pressure to the retainer. When opening valves without a retainer remove service valve cap and insert a hex wrench into the valve stem and back out the stem by turning the hex wrench counterclockwise. Open the valve until it contacts the rolled lip of the valve body. NOTE: These are not back-seating valves. It is not necessary to force the stem tightly against the rolled lip. NOTE: Power must be supplied to the 18 SEER outdoor units containing ECM motors before the power is applied to the indoor unit. Sending a low voltage signal without high voltage power present at the outdoor unit can cause malfunction of the control module on the ECM motor.
Low Voltage Connections
Condensing unit control wiring requires 24 Volt minimum, 25VA service from the indoor transformer. Low voltage wiring for twostage units depends on the thermostat used and the number of control wires between the indoor unit and the condensing unit. Route control wires through the low voltage port and terminate in accordance with the wiring diagram provided inside the control panel cover.
Adequate refrigerant charge for a matching evaporator and 15 feet lineset is supplied with the condensing unit. If line set exceeds 15 feet in length, refrigerant should be added at.6 ounces per foot of liquid line. Open the suction service valve first! If the liquid service valve is opened first, oil from the compressor may be drawn into the indoor coil TXV, restricting refrigerant flow and affecting operation of the system. After the refrigerant charge has bled into the system, open the liquid service valve. The service valve cap is the secondary seal for the valves and must be properly tightened to prevent leaks. Make sure cap is clean and apply refrigerant oil to threads and sealing surface on inside of cap. Tighten cap finger-tight and then tighten additional 1/6 of a turn (1 wrench flat), or to the following specification, to properly seat the sealing surfaces. 1. 3/8 valve to 5 - 10 in-lbs 2. 5/8 valve to 5 - 20 in-lbs 3. 3/4 valve to 5 - 20 in-lbs 4. 7/8 valve to 5 - 20 in-lbs Do not introduce liquid refrigerant from the cylinder into the crankcase of the compressor as this may damage the compressor.
Do not overcharge system with refrigerant. Do not operate unit in a vacuum or at negative pressure. Failure to follow proper procedures may cause property damage, personal injury or death.
Use refrigerant certified to AHRI standards. Used refrigerant may cause compressor damage. Most portable machines cannot clean used refrigerant to meet AHRI standards.
Violation of EPA regulations may result in fines or other penalties.
Operating the compressor with the suction valve closed will void the warranty and cause serious compressor damage.
1. Break vacuum by fully opening liquid and suction base valves. 2. Set thermostat to call for cooling. Check indoor and outdoor fan operation and allow system to stabilize for 10 minutes for fixed orifices and 20 minutes for expansion valves.
Final Charge Adjustment
The outdoor temperature must be 60F or higher. Set the room thermostat to COOL, fan switch to AUTO, and set the temperature control well below room temperature. After system has stabilized per startup instructions, check subcooling and superheat as detailed in the following section.
Fixed Orifice
Charge Verification
SYSTEM SUPERHEAT Return Air Te m pe rature ( 50%RH ) Am bient Condenser Inlet Tem pe rature Drybulb Wetbulb Drybulb Wetbulb Drybulb Wetbulb Drybulb Wetbulb Drybulb Wetbulb ( F Drybulb ) ----------8 --------------28 * 29 31
NOTE: * Charge 5 super he at, all othe r could be 2F
To prevent personal injury, carefully connect and disconnect manifold gauge hoses. Escaping liquid refrigerant can cause burns. Do not vent refrigerant into the atmosphere. Recover all refrigerant during system repair and before final unit disposal.
1. Purge gauge lines. Connect service gauge manifold to base-valve service ports. Run system at least 10 minutes to allow pressure to stabilize. 2. Temporarily install thermometer on suction (large) line near suction line service valve with adequate contact and insulate for best possible reading. 3. Refer to the superheat table provided for proper system superheat. Add charge to lower superheat or recover charge to raise superheat. 4. Disconnect manifold set, installation is complete. Superheat Formula = Suct. Line Temp. - Sat. Suct. Temp.
base-valve service ports. 2. Temporarily install thermometer on liquid (small) line near liquid line service valve with adequate contact and insulate for best possible reading. 3. Check subcooling and superheat. Systems with TXV application should have a subcooling of 5 to 7 F and superheat of 7 to 9 F. a. If subcooling and superheat are low, adjust TXV to 7 to 9 F superheat, then check subcooling. NOTE: To adjust superheat, turn the valve stem clockwise to increase and counter clockwise to decrease. b. If subcooling is low and superheat is high, add charge to raise subcooling to 5 to 7 F then check superheat. c. If subcooling and superheat are high, adjust TXV valve to 7 to 9 F superheat, then check subcooling. d. If subcooling is high and superheat is low, adjust TXV valve to 7 to 9 F superheat and remove charge to lower the subcooling to 5 to 7 F. NOTE: Do NOT adjust the charge based on suction pressure unless there is a gross undercharge. 4. Disconnect manifold set, installation is complete.
Subcooling Formula = Sat. Liquid Temp. - Liquid Line Temp.
Expansion Valve System
Single Speed Application 1. Purge gauge lines. Connect service gauge manifold tobase-valve service ports. Run system at least 10 minutes to allow pressure to stabilize. 2. Temporarily install thermometer on liquid (small) line near liquid line service valve with adequate contact and insulate for best possible reading. 3. Check subcooling and superheat. Systems with TXV application should have a subcooling of F and superheat of 7 to 9 F. a. If subcooling and superheat are low, adjust TXV to 7 to 9 F superheat, then check subcooling. NOTE: To adjust superheat, turn the valve stem clockwise to increase and counter clockwise to decrease. b. If subcooling is low and superheat is high, add charge to raise subcooling to 7 2F then check superheat. c. If subcooling and superheat are high, adjust TXV valve to 7 to 9 F superheat, then check subcooling. d. If subcooling is high and superheat is low, adjust TXV valve to 7 to 9 F superheat and remove charge to lower the subcooling to 7 2F. NOTE: Do NOT adjust the charge based on suction pressure unless there is a gross undercharge. 4. Disconnect manifold set, installation is complete. Subcooling Formula = Sat. Liquid Temp. - Liquid Line Temp. Two Speed Application Run the remote on low stage cooling for 10 minutes until refrigerant pressures stabilize. Follow the guidelines and methods below to check unit operation and ensure that the refrigerant charge is within limits. Charge the unit on low stage. 1. Purge gauge lines. Connect service gauge manifold to 7
NOTE: Check the Schrader ports for leaks and tighten valve cores if necessary. Install caps finger-tight.
SATURATE D LIQ UI D PR ES SU RE TE MP ER ATU RE CHART LIQ UID PRE S SURE
PSIG 625
S ATURATED S UCTIO N P RES S URE TEM P ERATURE CHART S UCTIO N P RES S URE
PSIG 170
S ATURATED LIQ UID TEM PE RATURE F
R -n /a n /a n /a n /a n /a n /a n /a n /a n /a n /a R- 410A 15 2
S ATURATED S UCTION TEM P ERATURE F
R-R-410A 60
Troubleshooting Information
Complaint No Cooling Compressor and Condenser Fan will not start Unsatisfactory Cooling System Operating Pressures
Compressor runs - goes off on overload
System runs continuously - little cooling
SYMPTOM
Too cool and then too warm
POSSIBLE CAUSE DOTS IN ANALYSIS GUIDE INDICATE "POSSIBLE CAUSE"
Certain areas to cool others to warm
Compressor will not start - fan runs
Compressor cycles on overload
Not cool enough on warm days
Evaporator fan will not start
Condenser fan will not start
High suction pressure
Low suction pressure
Compressor is noisy
Test Method Remedy High head pressure Test Voltage Impact Fuse Size & Type Inspect Connection - Tighten Test Circuits with Ohmmeter Test Continuity of Overloads Test Continuity of Thermostat and Wiring Check Control Circuit with Voltmeter Test Capacitor Test Continuity of Overload Test Motor Windings Use Test Cord Test Continuity of Coil and Contacts Test Continuity of Coil and Contacts Test Control Circuit with Voltmeter Test Voltage Repair or Replace Test Motor Windings Check Resistance of Anticipator Test For Leaks, Add Refrigerant Replace Restricted Part Replace Line Replace Line Speed Blower, Check Duct Static Pressure Reduce Blower Speed Recover Part of Charge Recover Charge, Evacuate, Recharge Remove Obstruction to Air Flow Check Windows, Doors, Vent Fans, Etc. Relocate Thermostat Readjust Air Volume Dampers Refigure Cooling Load Replace Compressor Test Compressor Efficiency Test Compressor Efficiency Reset and Test Control Test Voltage Replace Valve Replace Valve Replace Valve Replace Valve Tighten Bulb Bracket Check Valve Operation Tighten Bolts
System will not start
Power Failure Blown Fuse Loose Connection Shorted or Broken Wires Open Overload Faulty Thermostat Faulty Transformer Shorted or Open Capacitor Internal Compressor Overload Open Shorted or Grounded Compressor Compressor Stuck Faulty Compressor Contactor Faulty Fan Relay Open Control Circuit Low Voltage Faulty Evaporator Fan Motor Shorted or Grounded Fan Motor Improper Cooling Anticipator Shortage or Refrigerant Restricted Liquid Line Undersized Liquid Line Undersized Suction Line Not Enough Air across Indoor Coil Too Much Air across Indoor Coil Overcharge of Refrigerant Noncondensibles Recirculation of Condensing Air Infiltration of Outdoor Air Improperly Located Thermostat Air Flow Unbalanced System Undersized Broken Internal Parts Broken Valves Inefficient Compressor High Pressure Control Open Unbalanced Power, 3PH Wrong Type Expansion Valve Expansion Valve Restricted Oversized Expansion Valve Undersized Expansion Valve Expansion Valve Bulb Loose Inoperative Expansion Valve Loose Hold-down Bolts
Low head pressure
For detailed service information refer to the Remote Condensing Unit Service manual.
Units with rotary or reciprocating compressors and non-bleed TXVs require a Hard Start Kit.
THIS PAGE LEFT INTENTIONALLY BLANK
Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com
2005-2010 Goodman Manufacturing Company, L.P.
Tags
CAW7740N KH1508 ZR50 MC KDC-5021 N3000W Speedtouch 530 MCB275 TO PCB Psla4 Bose QC2 10X25B XSU-00750B AK77PRO Yamaha GW50 WV-TW2 BL-C131 DXZ735MP FX100 VK266 IC-32A CDX-GT517EE Meteo MG5140 RY49701 HL650U STR-DE335 IC-E880 XL2370-1 If-ED AG-DVX100P DSC-U20 Yamaha PB1 Coupe Stone Motorola Dext KCA-IP500 Version 9 Chariot WA137QA1 Startac 130 CC-VL500 Fostex X-14 Vitopend RDZ-D5 AL-800 840 Review Jet 335 DAV-C700 Er-5200 AVR-5803-AVR-5803A LE22A457c1C TR-66 42PF9630A MD-MT15 MD-SR50 AU517 2045E MDX-M690 Autofocus EL-1801P K7S41 WF-T7500TPT SGH-U900L Dslr-A900 CDX-R3000 FL7000 LT120 D3 GTA 480 CMT-SPZ70 FM30AH EL250 Cisco 7960 RTT2160 HTR-5930 4715Z 10400 SC-HT17 PDC 5070 International RC5 Altima-2005 S7110 HB406 SRA-540 C5030I X-session PRO Nawigacyjny CD YFS200M MX7517J LE40R77BD Watch J304 PNA 205 A-380 SGH-T429 Moto Z6W APC20 HM25E DVD 10 PT-LB30NTE DSM-380 Sporting
manuel d'instructions, Guide de l'utilisateur | Manual de instrucciones, Instrucciones de uso | Bedienungsanleitung, Bedienungsanleitung | Manual de Instruções, guia do usuário | инструкция | návod na použitie, Užívateľská príručka, návod k použití | bruksanvisningen | instrukcja, podręcznik użytkownika | kullanım kılavuzu, Kullanım | kézikönyv, használati útmutató | manuale di istruzioni, istruzioni d'uso | handleiding, gebruikershandleiding