Honeywell Micronik 200
|
|
Bookmark Honeywell Micronik 200 |
About Honeywell Micronik 200Here you can find all about Honeywell Micronik 200 like manual and other informations. For example: review.
Honeywell Micronik 200 manual (user guide) is ready to download for free.
On the bottom of page users can write a review. If you own a Honeywell Micronik 200 please write about it to help other people. [ Report abuse or wrong photo | Share your Honeywell Micronik 200 photo ]
Manual
Download
(English)
|
Honeywell Micronik 200
User reviews and opinions
| Mikayel |
10:17am on Tuesday, August 31st, 2010 ![]() |
| Horrible Honeywell 2-gal. Cool Moisture Humidifier is a loud, crudely designed white elephant. I returned it immediately! I got the Crane 2. Too Loud If you already have to turn the TV up to max to hear, you may not mind the blower on this unit. It overpowers a room. | |
| Amstaff |
11:17am on Tuesday, August 3rd, 2010 ![]() |
| Great Machine, I have had 2 of them for almost 3 years! These have been great machines for me. | |
| vcolombo |
10:57pm on Thursday, June 3rd, 2010 ![]() |
| I purchased this fan thinking it would blow me away....not quite. Its average at best. | |
| Miguel Lamy |
12:23pm on Tuesday, March 30th, 2010 ![]() |
| Not UV-proof This unit will become discolored from sunlight. There is no UV-protection on the plastic. | |
Comments posted on www.ps2netdrivers.net are solely the views and opinions of the people posting them and do not necessarily reflect the views or opinions of us.
Documents

HONEYWELL
R7426D MicroniK 200
UNIVERSAL INPUT CONTROLLER
INSTALLATION & START-UP INSTRUCTIONS
GENERAL
This document provides instructions and procedures for installing and starting up the Micronik 200 R7426D controller. No special tools are required for mounting and installation. The user interface and LC display allows accurate and easy parameter setting and output adjustment.
BEFORE INSTALLATION NOTE
Fig. 1. Temperature Controller Visually inspect equipment for shipping damage. Report any damage to the appropriate Honeywell representative. Refer to job drawings for specific installation information and mounting location. Verify the controller will be adequately separated from the main power supply, relays or other equipment which can possibly generate electromagnetic interference. Verify that the ambient temperature and the humidity at the controller will be within the limits of 0.50C (32.122F) and 5 to 95% rh. Use shielded wiring in areas with high EMI. All wiring should be separated from power lines by at least 150mm (6). Do not install controllers near frequency converters or other high frequency sources.
Contents
General... 1 Before Installation Note.. 1 Mounting... 1 Wiring.... 2 Power Supply and Grounding... 2 Configuration and Control Parameters.. 3 Configuration Settings.. 5 Parameter Settings and Adjustment. 6 Operating Overview... 9
MOUNTING
The controller can be mounted in an electric cabinet or an other suitable enclosure. It is suitable for back panel, DIN rail, wall or front panel mounting with an additional available front panel mounting frame. The mounting sequence of each as well as dimensions and panel cut-out is illustrated in the mounting instruction sheet EN1B-0202GE51 supplied with the controllers. If the compensation sensor signal (T3) is received from another controller (parallel connection of compensation sensor inputs), the jumper W303 must be cut before mounting the controller (see Fig. 2). This disconnects the sensor from the internal power supply.
7157 585
EN1B-0204GE51 R0403
R7426D UNIVERSAL INPUT CONTROLLER
WIRING
Screwless type, spring loaded terminals are provided on the controllers for wiring. These terminals are suitable for solid conductors as well as tinned or with multicore cable end, stranded wires up to 1.5mm2. To make a termination, push the wire into the terminal or insert a small screwdriver from the front of the controller into the spring-release hole and insert the wire. Check for proper connection by short pull on the wire. Wiring should be done only according to the actual job wiring diagrams or wiring diagrams shown in the mounting instruction sheet EN1B-0202GE51. The wiring to the CPA/SPA potentiometers is described in Table 1. All wiring must conform to local applicable codes, ordinances, and regulations. The maximum allowed wiring length per wire size are shown in Table 2.
Controller to CPA/SPA Potentiometer R7426D 43193982-001
Terminal 2 Terminal 4
Terminal 3 Terminal 1
Table 1. Terminal Connection
Jumper W303
State closed open
Description T3 supplied by this controller T3 supplied from another controller
Wiring run
Type of wires
Length max. 1.0mm2 1.5mm2
From controller to all input and output devices
local standard
Default jumper position = closed Only cut (open) jumper W303, if the T3 input is fed from another controller (parallel connection, max. 6 devices). This disconnects the T3 input from the internal power supply.
Table 2. Wire Dimensions
Fig. 2. Parallel Connection of Compensation Sensor T3
POWER SUPPLY AND GROUNDING
1. Refer to job drawings and verify correct supply voltage to transformer (230Vac) and controller (24Vac). 2. Connect line power conductors to transformer primary. Line power must be supplied from a breaker panel with dedicated controller circuit. Do not turn the line power on until all wiring has been checked against job drawings. 3. Connect transformers 24Vac secondary to the controller terminals 18 and 19. Connect one conductor to terminal marked 24V and the other to terminal marked 24V. If controllers are interconnected all terminals 19 must be connected to the same potential 24V level.
CONFIGURATION AND CONTROL PARAMETERS
Config. Par. No. Name Description Default Setting Actual Value
C.01 DIR/REVY1 Selects the output action of Y1 to adapt the valve or damper direction Dir Direct acting output signal Rev Reverse acting output signal C.05 CPATYP Selects the Control Point /SetPoint Adjustment type
Potentiometer range CPA/SPA range Sensor / Remote Setpoint Unit Type Numbers
2 C.06 YRange
internal 100k.0 100k.0
CPA: 10% CPA: 10% SPA: 0.100%
internal 43193982-001 43193982-001 1
Selects the output control range 0 2. 10Vdc 1 0. 10Vdc Enable / Disables the X1 sensor input to be used for both X1 and X2 inputs 0 X2 installed 1 X1 signal used for XX2 disabled Limitation type determines whether the limit function is low or high. 0 Low limit 1 High limit Sensor type determines automatic detection or manual selection of NTC sensor type 0 Auto detection TNTC sensor type T3 Control function 0 Direct control behaviour 1 Reverse control behaviour Sets the serial communication address, used for service or maintenance. 0 Min. 255 Max. Initiates the default programming. 0 No Defaultprogramming 1 Initiates Defaultprogramming
C.12 X2ext
C.13 LimTyp
C.14 Senstyp
C.15 Y1CTRF
C.22 Adr1)
C.23 DefProg
C.24 UStartPoint Start point (0%) of X1 and X2 span adjustment 0 Min. 10V Max. (resolution 0.1V) C.25 UEndPoint End point (100%) of X1 and X2 span adjustment 0 Min. 10V Max. (resolution 0.1V) C.26 OffDelay Off delay for On/Off output 0 Min. 60min Max. (resolution 1min)
actual value will not be changed during reset to default parameter
For detailed information of configuration parameters see chapter Configuration Settings. Table 3. Configuration Parameters R7426D
Control Par. No. Name
Description
Setting Low High Def.
Resolution
Actual Value
P.01 W1 P.02 Wlim P.03 Wcomp P.04 Wi P.05 Su P.06 Wcas P.07 Rcas P.08 Xp1 P.09 Xp2 P.12 tr11) P.13 tr2
Main setpoint for input X1 Limit setpoint (low or high) for input X2 Compensation changeover point for input T3 Winter compensation authority Summer compensation authority Submaster or cascade setpoint Cascade reset span adjustment Throttling range (main control loop) for X1 Throttling range (cascade or limit control loop) for X2 Reset time (main control loop) Reset time (cascade control loop) Start point for mid range shift of output Y1 Calibration of input X1 Calibration of input X2 Calibration of temperature sensor T3 Derivative decay time for P+I+D control
-5 -350 -350 Off, 1 1
40 +350 +50
0 Off 10 Off Off 1 0
0.2 0.5 0.5 0.5 0.5 10/0.5 10/0.5 0.5 0.1 0.1 0.0.1
% % C % % % % % % sec/min sec/min % % % K s -
Off,20sec 20min Off,20sec 20min -50 -20 -20 -0 +50 +20 +20 +5
P.15 Ystart P.17 X1Cal P.18 X2Cal P.19 T3Cal P.27 td P.28 vd
1) 2) 2)
Derivative amplification for P+I+D control
for tr > 2 min resolution = 0.5 min , for tr < 2 min resolution = 10 sec 0 = derivative function disabled Table 4. Control Parameters R7426A,B,C
For detailed information of control parameters see chapter Parameter Settings and Adjustment.
CONFIGURATION SETTINGS
All configuration parameters have to be set to select the correct control functions as required for the job application.
Direct - Reverse Action Dir/RevY1 (C.01)
The output action of the analog output must sometimes be reversed for a correct opening and closing direction of the valve or damper. This depends on whether the output controls a 2-way or 3-way valve or on the direction the damper shaft moves to open the damper (cw or ccw). It is only needed, if the actuator does not provide a direction selector switch, plug or similar. Note: The analog output signal Y1 can be displayed in the standard display mode. The selected action of signal Y1 does not influence the display indication.
Automatic identification of sensor type
Temperature range
Characteristics
Pt 1000 BALCO 500 NTC 20k
-30.+130C -30.+130C -30.+85C / -30.+130C1)
1000 at 0C 500 at 23.3C 20k at 25C
NTC sensor is detected automatically, if during power up the sensor temperature is within -30.+85C and Senstyp = 0. NTC sensor is selected manually, if Senstyp is set to 1. Table 5. Sensor Types
Control Point / Setpoint Adjustment CPATYP (C.05)
The control point or setpoint can be adjusted via the internal or an external potentiometer connected to the CPA/SPA input. The potentiometer type is selected by CPATYP (see Table 3).
Automatic identification of sensor type is selected, if Senstyp = 0 (default). After power up reset the controller detects automatically the type of sensor, which is connected to the temperature input T3. For a correct auto detection, it is necessary that the measured temperature is in the specified range (see Table 5).
Output Control Function Y1CTRF (C.15)
The R7426D controller performs direct control behaviour, if Y1CTRF is set to 0. A rise in the measured variable will increase the output value from 0.100% (direct acting). The control action must be reversed for reverse control behavior by setting Y1CTRF to 1. A rise in the measured variable will decrease the output value (100.0%). Note: The analog output signal Y1 with the selected control behavior is displayed in % in the standard display mode.
Output Control Range Selection YRange (C.06)
YRange is required to select the output control range (0.100%) to either 2.10Vdc (YRange = 0) or 0.10Vdc (YRange = 1).
Supply of Input Signal X2ext (C.12)
X2ext has to be set to 1, if the sensor input X1 is also used for high or low limit control. This interconnects the X1 and X2 input internally and the sensor has to be connected only to the X1 input. When using a limit sensor X2, the parameter X2ext has to be set to 0 (default). If sensor X2 is not used, the input has to be deactivated by setting X2ext to 2.
Serial Communication Address Adr(C.22)
The parameter Adr sets the serial communication address, used for controller start-up, service or maintenance purposes via the bus.
Limit Type LimTyp (C.13)
LimTyp allows the selection of high or low limit control. High limit control is performed if LimTyp = 1 and low limit control is performed if LimTyp = 0.
Default Programming DefProg (C.23)
Setting DefProg to 1 resets all control and configuration parameters to defaults (see Table 3 and Table 4). Default programming is indicated by a display of def. After default programming, the parameter DefProg is reset to 0.
Sensor Type Senstyp (C.14)
Three different sensor types can be used on input T3 with the controller (see Table 5).
Span Adjustment UStartPoint / UendPoint (C.24 / C.25)
The universal inputs X1 and X2 accept any analog inputs within the range of 0.10Vdc and provides an input span adjustment to match the range of the connected transmitters. The start / end point of the input span can be adjusted by the parameters UStartPoint / UendPoint and is converted to a 0.100% input range. The parameters UStartPoint and UEndPoint are common for both inputs X1 and X2.
Off Delay for On/Off Output (C.26)
The On/Off output is controlled by the Plant / System On/Off input and provides an Off switching output with adjustable delay time e.g. to operate the fan still for a certain time after humidification.
On/Off Input Controller Function On/Off Output: Delay
Reset Span Adjustment Rcas (P.07)
The reset span adjustment Rcas determines the reset effect in %, the submaster setpoint Wcas is altered, if the main input (X1) deviates by 50% of the throttling range Xp1.
Throttling Range Xp1 / Xp2 (P.08 / P09)
Throttling range Xp adjustment determines the controller variable change, required at the main sensor (X1) and limit or cascade sensor (X2) to operate the output device from full open (100%) to full closed (0%) or vice versa. Xp1 is the throttling range for the main control loop, Xp2 is the throttling range for limitation or cascade control (submaster control loop).
Application Sens. Xp1 Xp2 tr1 tr2 vd/td
On Off
Normal control Output Y1 = 0%
Off On: 0 min On Off: 0.60 min
The off time delay can be adjusted by the parameter OffDelay.
PARAMETER SETTINGS AND ADJUSTMENT
Main Setpoint W1 (P.01)
The main setpoint is either set by the parameter W1 (CPATYP = 0 or 1) or by the external setpoint potentiometer (CPATYP = 2).
R7426D Controller Main Control High or Low Limit Control Cascade Control Master Submaster X1 X2 x x x x x X1 X2 x x x x x x
High/Low Limit Setpoint Wlim (P.02)
For high or low limit control, the control parameter Wlim is used as setpoint. During limit control, the throttling range Xp2 and reset time tr2 are active. Limit control will be active only, if the X2 signal (X2ext = 0) is available or alternatively the sensor X1 (X2ext = 1) is used also for limit control. For cascade control the limit setpoint Wlim determines the control point at which the submaster setpoint (Wcas) maintains the limit value and is not shifted anymore by the master control loop. High or low limit control is in accordance with the parameter LimTyp (C.13).
Table 6. Throttling Range, Reset and Derivative Time Reference
Setting Guidelines for Proportional Band of P, P+I and P+I+D Control
To estimate the proportional band (throttling range Xp) for stable control under all different load conditions the control or correcting range Xh of the controlled variable by the final controlling element has to be known. This is the maximum difference in the controlled variable between the fully closed and fully open position of the final controlling element (e.g. valve). The proportional band Xp for discharge air control can be calculated by using the following rule-of thumb formula:
Xp = Xh 5
Submaster Setpoint Wcas (P.06)
The R7426D controller provides cascade control which uses two control loops, master and submaster to maintain the master setpoint CTRP1. Cascade control will be active, if sensor X2 is connected and the control parameter Wcas is set to any value other than Off. This adjustment sets the control point of the submaster control loop, cascade input (X2), at zero deviation of the master control loop. If the controlled input X1 deviates from the master setpoint CTRP1, the submaster setpoint Wcas is automatically altered (CTRP2). Cascade control is disabled, if the submaster setpoint Wcas is set to Off. Low limit of CTRP2 is performed if control parameter LimTyp = 0 and high limit of CTRP2 is performed if control parameter LimTyp = 1.
For room control the following rule-of-thumb formula can be used:
Xp = Xh 10
In P+I or P+I+D control the same proportional band can be used as for P control. The following rule-of-thumb formula are used for P+I control: Discharge air control Room control
Xp = Xp = Xh 4.5 Xh 8.10
The following rule-of-thumb formula are used for P+I+D control: Discharge air control Room control
Xp = Xp = Xh 5.6 Xh 10.12
Setting Guidelines for Reset Time of P, P+I and P+I+D Control
The reset time tr should be adjusted to 2.3 times of the response time Tu , which is the time interval between the beginning of a sustained disturbance (e.g. rapid step change of valve position) and the instant when the resulting change in the output signal reaches a specified fraction of its final steady-state value, either before overshoot or in the absence of overshoot. The response time Tu in discharge air control is normally in the range of 0.1 to 0.6min, which allows adjustments of the reset time tr in a range of 0.2 to 2min. In room control the response time Tu is in the range of 0.5 to 5min, which results in a setting of 1 to 15min.
Resetting Time tr1 / tr2 (P.12 / P13)
In the case of combined action including proportional and integral components (P+I control) the reset time (tr) is defined as the required time after which the integral part is equal to the change due to the proportional action for a predetermined step change in the input variable. See Fig. 3. The control parameter tr1 sets the reset time of the P+I main control loop. For limit or submaster cascade control (input variable X2) the control parameter tr2 sets the reset time of these control loops (see Table 6). If only proportional control is required parameter tr has to be set to Off.
Xw 0 t Y P + I controller P 100 P = X Xw %
Derivative Decay Time td and Amplification vd (P.27 / P.28)
The Proportional + Integral + Derivative (P+I+D) control adds the derivative function to P+I control to enhance the control behavior. The derivative function opposes any change and is proportional to the rate of change (derivative). If the controlled input X1 deviates from the master setpoint (CTRP1), the derivative function outputs a corrective action to bring the control variable X1 back more quickly than by integral action alone. The derivative amplification vd determines the effect of derivative action after a rate of change of the controlled input X1. The decay time td determines the decay of the control output Y1 after derivative action (see Fig. 3).
P %/s tr
tr Y P vd % P 100 P = X Xw % p td tr P + I + D controller
In main control and cascade control applications the control parameters td and vd determines the derivative function. In main control with limitation control these parameters determines the two derivative functions of main control and limitation control.
Setting Guidelines for Derivative Amplification and Decay Time of P+I+D Control
The proper setting depends on the time constants, e.g. the response time Tu , of the system being controlled. The parameter vd and td can be set in the following relation:
td = 0.42 Tu vd
Fig. 3. Step change response of P+I and P+I+D control Note: P+I+D control is available for main control and main control with limitation control. In cascade control the submaster is P+I+D controlled while the master is P+I controlled.
In other words, with derivative amplification vd set to 1, the decay time td should be set to approx. 0.42Tu or approx. (0.15.0.25)tr. The response time Tu in discharge air control is normally in the range of 0.1 to 0.6min, which allows adjustments of the decay time td in a range of 2.5 to 15sec.
Start Point Ystart (P.15)
The start point setting determines the relationship between the midrange shift of the output Y1 and the corresponded calculated control point. It is calibrated in %, e.g. r.h., and is the change (plus or minus) from the control point. In humidification and dehumidification control the start point has to be shifted by minus 50% of the proportional band Xp1. Example: Set YCTRF to 1, reverse control behavior Set Xp1 at 6% Set start Ystart at minus 3% With these settings, the humidifier valve will be fully closed, if the actual humidity value is equal to the calculated control point CTRP1 (zero deviation) and fully open at 6% r.h. below CTRP1. At 6% r.h. above CTRP1, the controller provides an output signal of plus 1200mV (100%) to fully open the cooling valve by the plant temperature controller for dehumidification. In P+I+D and P+I control the start point has to be set to the same value as for P control.
Summer (pos. compensatio n) Winter (neg. compensatio n)
Control Schedule
Room Humidity (X1)
50%rh 40%rh Aut Wi =
Outdoor Air Temp. (T3/Tcomp)
20C -15C
Throttling Range (XP)
5%rh 5%rh
X1 + Xp 100% = t Outside Air (40 - 50) + 5 100% = -14% 35
50%rh 60%rh Aut Su =
20C 35C
X1 Xp 100% = t Outside Air (60 - 50) - 5 100% = +33% 15
Compensation change-over at +20 C outdoor air temperature Note: With P+I and P+I+D control Xp = 0
Compensation Changeover Point Wcomp (P.03)
The control parameter Wcomp defines the start point of summer or winter compensation. Above the compensation changeover point (Wcomp) summer compensation and below Wcomp winter compensation is performed.
Table 7. Calculation of Summer/Winter Compensation
Calibration of Sensors X1CAL, X2CAL or T3CAL (P.17.P.19)
The controllers include a calibration setting and are factory calibrated. In case of an offset as a result of long wiring lengths the sensor inputs (X1, X2 and T3) can be adjusted separately by the control parameters X1CAL, X2CAL and T3CAL.
Summer / Winter Compensation Authority Su / Wi (P.04 / P.05)
These authority settings determine the reset effect (TComp) of the compensation sensor (T3) on the main setpoint W1 in percentages. To calculate winter and summer authority for e.g. humidity control, the throttling range has to be considered in proportional only control according to Table 7.
OPERATING OVERVIEW
Display and Operation Elements
The MicroniK 200 user interface is described in Fig. 4 Note: Pushing the + or - button increments/decrements values or scrolls through the parameter list: pushing one time: single step pushing without release: automatically inc./dec. or scroll after 3 sec pushing without release: fast automatically inc./dec. or scroll
Display
Controller Mode Off On
Engineering Units Value
Push Buttons Selection or Escape Parameter/Value Corfirmation
Changing Operating Modes
Fig. 5 shows the six operating modes. After power-up the controller version is displayed and the controller enters the standard display mode (Fig. 6). In this mode selected input or output values are displayed. The controller mode is permanently displayed by a corresponding icon (Fig. 4). Pushing the + and - button simultaneously for approximately 1 sec the controller leaves the standard display mode and enters the parameter/configuration selection mode (Fig. 7). This mode is used for application configuration and to select parameters for adjustment. Pushing the SET button the controller accepts the selected parameter or configuration no. and enters the adjustment mode (Fig. 8), which is used to adjust configuration/parameter values. After adjustment the controller returns to selection mode by pushing the SET or SEL button. Pushing the SEL button leads back to standard display mode.
SEL SET
Fig. 4. User Interface
Adjustment or Selection
Pushing the SET and SEL button simultaneously for approximately 1 sec the controller leaves the standard display mode and enters the output data selection mode (Fig. 9). Pushing the SET button enters the output adjustment mode (Fig. 10). This mode is used for manual override of the output value. The return to standard display mode is shown in Fig. 5.
Power up
Automatic Disp lay
Version: R7426D
Output Adjustment Mode
Output Select ion Mode
Standard Display Mode
and and for approx. Parameter/Config. Selection Mode 1 sec
Parameter/Config. Adjustment Mode
for approx. 1 sec
see Fig. 10
see Fig. 9
see Fig. 6
see Fig. 7
see Fig. 8
SET SET
Output Fixing no Output Fixing Release of Output Fixing
SET SEL Value Change
no Parameter
and and
Fig. 5. Operating Overview
Time Out
After approximately 10 min of inactivity (no button has been pressed: time out) each mode returns automatically to standard display mode. Inputs that have not been confirmed by the SET button are ignored by the controller and old parameter values will be retained.
Main Input X1
Displaying Actual Values
In the standard display mode one of six actual values, can be selected and displayed (Fig. 6) by pushing the SEL button. The icons of the permanently displayed controller mode are described in the following table: Controller Mode / Status Off On Off - icon Sun - icon
SEL SEL
Main Setpoint CTRP1
Limitation / Cascade Input X2
S ubmaster / Limit Setpoint CTRP2
Compensation Temperature T3
Output Y1 *)
The output data (Y1) are displayed between the following ranges:
Output type Control range Output range
0.10Vdc 2.10Vdc
0.100% 0.100%
0.120% 0.12V (Dir) -20.100% 12.0V (Rev) -25.125% 0.12V
Fig. 6. Standard Display Mode
Selecting Parameters
The parameter/configuration selection mode is used to select control and configuration parameters (Fig. 7) for adjustment. The displayed parameter no. corresponds with the number in Table 3 and Table 4. Default programming is indicated by a display of def. Pushing the + or - button scrolls through the parameter list. Pushing the SET button enters the adjustment mode.
Adjusting Configuration / Parameter Values
The adjustment mode is used to adjust configuration and parameter values (Fig. 8). In this mode the selected parameter no. is displayed and the corresponding value flashes. Pushing the + or - button increments or decrements the value of the selected parameter. Parameter ranges are shown in Table 3 and Table 4. An adjustment example is shown in Fig. 12. Pushing the SEL button retains the old parameter value. Pushing the SET button accepts the parameter value and returns to parameter/configuration selection mode.
Note: Control or Configuration Parameters which are not available are skipped.
Actual Parameter Value
Resetting Parameter Values to Default Values
Pushing simultaneously the + or - button during the power up or setting the control parameter DefProg (C.26) to 1 resets all control and configuration parameters to defaults (see Table 3 and and Table 4). Default programming is indicated by a display of def.
SET Value Change
Parameter
SEL Value Change
Fig. 7. Parameter/Configuration Selection Mode
to adjust Parameter Value
Fig. 8. Parameter/Configuration Adjustment Mode
Selecting Output Values
The output selection mode displays the output value and indicates the manual override (see Fig. 9). An activated manual override is indicated by a displayed F (fixed). Pushing the SET button enters the adjustment mode.
: Manual Override is active Without :
Manually Overriding Output Values
The output adjustment mode is used for manual override adjustment of the output value (see Fig. 10). In this mode the selected output no. is displayed and the actual output value flashes. Pushing the + or - button increments or decrements the value of the selected output for manual override purpose. The output range is displayed in correspondence with the nominal control range as shown in Fig. 6. To return to output selection mode three options are available: Pushing the SET-button after adjustment activates the manual override (fixing) of output value. Pushing the SEL button, causes that the output value is still determined by the control loop (no fixing). To release the manual override (fixed) of the output, enter output adjustment mode and push the + and - button simultaneously. Pushing the SEL button leads back to standard display mode.
Control Loop is active
Fig. 9. Output Selection Mode
Output Selection
to adjust Output Value Output Value Adjustment
Output Value Adjustment
Automatic display for approx. 1sec
Manual Override
No man ual Override
Release of Manual Override
Fig. 10. Output Value Adjustment for Manual Override
EN1B-0204GE51 R0403 12
Interpreting Error Messages
Different analog input errors can be identified by the controller (Error handling). The defective input (X1, X2, T3) will be displayed in the standard display mode (see Fig. 11) after the corresponding value is selected. Note: For the external CPA/SPA potentiometer input, no error message is indicated if the potentiometer or wiring is defective. In this case for control point or setpoint calculation the following values are used: for CPATYP 0 or 1 CPA value = 0 for CPATYP 2 SPA value = control parameter W1
Display after error identification during operation
Display if during power up no sensor is connected
Standard Display
and and and
: Main Sensor X1 is defective : Limitation or Cascade Sensor X2 is defective : Compensation Temperature Sensor T3 is defective
X1 and X2 is displayed in T3 is displayed in
Fig. 11. Error Handling
Push simultaneously for appr. 2sec
Parameter Adjustment Mode
Push until n eeded value is displayed
Parameter Selection Mode
This example describes the adjustment of the compensation change-over point Wcomp (P03).
Fig. 12. Adjustment Example
Automation and Control Solutions Honeywell AG Bblinger Strae 17 D-71101 Schnaich Phone: (49) Fax: (49) http://europe.hbc.honeywell.com
Subject to change without notice. Printed in Germany EN1B-0204GE51 R0403
Manufacturing location certified to
Tags
Travelmate 270 CH650M Samsung Q320 Plugin Rx-7020 Nokia 7160 BH-700 HS020GB Accent SPD-8 YDP-88 EAX600 4 6 KDL-32J5000 A7vivm Um 211 Scanmaker 5950 OT-255A X-press 150 YST-SW200 Dmcgh1K EWT10410W FC-30 Programmer AVS10 AJ3916 IR-FOX C IR2025I B3191-5-M- R DX-7111 P2015D A45-S250 - 2003 Nokia D211 PX-G920 Aw II Wbr-3600 Photosmart 1218 HT-TP33R Explorer-2005 Orea RTS HD7300 P3150 4000 PVR SR6300 TTR50-2007 Aficio 615C TDE4224W NAD 317 MS6200 LAV72330-W Easydrive TX209 AT-201 EB313HGA WM-EX2000 LX-300- Curve 8310 EN 1 GO 500 PC-D450 Story WS-65869 Perfection 1660 CX4080 TL-WN512AG FCV-1100L Vivicam 5386 XD221U Calculator XR-C5120 Phonefax 30 Couleur Bleu Stylus T20 Projectors K9N6pgm2 AVH-3200BT 2P Samsung T200 7145I Gev2 450 XC-W Combo Dvdr3390 UB1202FX 661 A 4360-140 HT-SF1100 Review SLV-X9D Domino WMA510 VGN-FS740-W ZBM762W Ar-1500L DCP-165C Cc-MT400 Daikin RKS Seiko 8F35 Eyebox EL-87 DP-4 Plus
manuel d'instructions, Guide de l'utilisateur | Manual de instrucciones, Instrucciones de uso | Bedienungsanleitung, Bedienungsanleitung | Manual de Instruções, guia do usuário | инструкция | návod na použitie, Užívateľská príručka, návod k použití | bruksanvisningen | instrukcja, podręcznik użytkownika | kullanım kılavuzu, Kullanım | kézikönyv, használati útmutató | manuale di istruzioni, istruzioni d'uso | handleiding, gebruikershandleiding
Sitemap
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101












