Heating Controller SDC Remote Heating Controller DHC
PARAMETER LIST
EN0B-0565GE51 R0308
SDC / HDC
Contents
21 Software version.... 5 Access to the technician / OEM area... 5 "Hydraulics" menu (HYDRAULIC)... 6 "System parameters" menu (SYSTEM)... 11 "Hot-water circuit" menu (DHW)... 14 "Direct heating circuit" menu (UNMIXED CIRC)... 18 "Mixed heating circuit 1 / 2" (MIX.VALVE - 1 / MIX.VALVE - 2) menus.. 21 "Heat generator" menu (HEAT GENER... 25 "District hot water" menu (DIST.HEATING)... 30 "Return increase" menu (RETURN CONTR).. 32 "Solar" menu (SOLAR).... 33 "Solid" menu (SOLID FUEL)... 35 "Buffer" menu (BUFFER)... 36 "Total flow regulation" menu (MAIN SUPPLY)... 38 "Cascading" menu (CASCADE).... 39 "Data bus" menu (BUS)... 40 "Relay test" menu (RELAY TEST ).... 41 "Error messages" menu (ALARM)... 42 "Error messages 2" menu (ALARM 2).. 43 "Sensor calibration" menu (SENSOR ADJ.).. 44 Log..... 45
Software version
Pos: 1 /156-Honeywell/Softwareversion/Softwareversion @ 0\m od_1207134342657_6.doc @ 9090
This documentation is valid for software version V 3.0 of your control device. The software version is displayed after switch-on for approx. 8 s. If you are using an older software version, please contact your heating technician.
Pos: 2 /156-Honeywell/Zugang zum Fachm ann- / OEM Bereich/Zugang zum Fachmann- /OEM-Bereich @ 0\m od_1206968314048_6.doc @ 8770
Access to the technician / OEM area
Entering a technician or OEM code enables additional setting options in the parameter menu. The technician code is: 1234. For access to the OEM area, please ask your field-service contact partner. Procedure: Press the and buttons simultaneously. The first number of the 4-digit code flashes. Set the first code number by turning the input button. Press the input button. The second number flashes. Enter all remaining code numbers as described in Steps 2 and 3. After entering the last code number, the controller is enabled for the respective area (technician or OEM). Press and hold the rotary button longer than 3 seconds. You reach the menu-selection level and can enter / modify parameters. Pressing the button jumps back to the previous selection.
Pressing the button, pressing and holding the input button longer than 3 seconds or waiting until the set info time expires causes a jump back to the basic display.
Pos: 3 /156-Honeywell/Menue_Hydraulik/Menue_Hydraulik @ 0\m od_1206968369001_6.doc @ 8786
"Hydraulics" menu (HYDRAULIC)
The parameters in this menu refer to the general system hydraulics and the functions and configuration of the programmable inputs and outputs for the respective system components. Representative of many individual settings, the applications are only defined by the 1st parameter of this setting table. Example: The controller is to cover system No 0202. Provided that the controller features enough relays, parameter 01 must be set to value 0202.
Parameter 01 02
Designation Hydraulic schematic
Setting range / Setting values 0, 0101, 0102,. n No function Hot-water charging pump Circulating pump Electric heating rod No function Direct heating circuit controlled by weather conditions Mixed heating circuit controlled by weather conditions Constant regulator Fixed-value regulator Return maintenance Mixed heating circuit as continuous hot-water pre-regulator (district heating) Hot-water pre-regulator (district heating)
Factory setting 0 1
Setting
Hot-water charging OFF pump output 5
Mixed heating circuit 1 output
Parameter 04 05
Designation Mixed heating circuit 2 output
Setting range / Setting values
Factory setting
For setting values, see parameter No function Direct heating circuit pump Circulating pump Electric heating element Constant regulation Feeder pump Boiler circuit pump 1 Boiler circuit pump 2 Group alarm Time switch Solar charging pump Cooling switchover Hydraulic buffer relief 2
Direct heating OFF circuit pump output 25 27
Parameter 06
Designation Variable output 1
Setting range / Setting values OFF 27 No function Circulating pump Electrical heating circuit Bypass pump Feeder pump Boiler circuit pump 1 Boiler circuit pump 2 Group error message Solar charging pump Buffer charging pump Solid fuel charging pump Stratified tank charging pump (DHC) Solar charging switchover Cooling switchover Primary pump Hydraulic buffer relief
Factory setting OFF
Variable output 2
For setting values, see parameter 06
Parameter 08
Designation Variable input 1
Setting range / Setting values OFF No function Outside sensor 2 Heat generator sensor 2 Tank sensor 2 Buffer sensor 2 Request contact External error message input Return maximum limit of mixed heating circuit 1 Return maximum limit of mixed heating circuit 2 Return sensor of bypass pump External heat generator cutoff External switching modem External information Total flow sensor Collector return sensor District hot-water stratified tank charge sensor Exhaust gas sensor Solids buffer sensor Buffer sensor 1 Hygrostatic switch-off Room sensor NTC 20 of direct heating circuit Room sensor NTC 20 of mixed heating circuit 1 Room sensor NTC 20 of mixed heating circuit 2
Parameter 09
Designation Variable input 2
Setting range / Setting values For setting values, see parameter 08; does not include setting value 16 (exhaust gas sensor), however For setting values, see parameter 08; does not include setting value 16 (exhaust gas sensor), limit sensor of district heating VFB, however OFF, ON
Variable input 3
Indirect return lifting via mixed heating circuit
Pos: 4 /156-Honeywell/Menue_System parameter/Menue_Systemparameter @ 0\m od_1206968455345_6.doc @ 8802
"System parameters" menu (SYSTEM)
The parameters in this menu refer to general limit parameters and specification values in the heating system used.
Parameter Language selection**
Designation Language selection
This menu contains all parameters required to program the hot-water circuit, except the switch time programs.
Parameter Hot water
Designation Hot water at night
Setting range / Setting values 10C to normal hot-water temperature OFF No legionella protection Mon to Legionella protection on Sun specified day of week ALL Legionella protection every day
Factory setting 40 OFF
Legio Legionella protect protection day ion day
Legionella protection time Legionella protection temperature
00:00. 23:00 hours 10 C to setting value of parameter 06 Hot-water circuit temperature sensor Hot-water circuit temperature controller (thermostat)
02:00 65
Transducer for hot- 1 water circuit 2
Maximum 20C to heat generator maximum temperature limit temperature for hot water circuit If parameter 07 = 7: 20 to 90C. In automatic mode, from hotwater circuit minimum temperature.
Parameter 07
Designation Hot-water circuit operating mode
Setting range / Setting values Parallel operation Priority operation Conditional priority Parallel operation based on weather conditions Priority operation with intermediate heating Priority isolating circuit External operation Conditional parallel operation for mixed heating circuit (DHC only) No discharge protection Discharge protection activated
Factory setting 2
Tank discharge protection Temperature increase of heat generator with hotwater circuit charging Switching differential of hotwater circuit
OFF ON
0. 50 K Difference between hot-water circuit charging temperature and hot-water circuit setpoint temperature 2. 20 K Value of hot-water circuit switching differential. Symmetrical effect around the hot-water circuit setpoint
Hot-water charging 0. 60 min pump follow-up time
Parameter 12
Designation Circulation pump switching time program
Setting range / Setting values AUTO Active hot-water circuit time program P1, direct heating circuit P2, direct heating circuit P3, direct heating circuit P1, mixed heating circuit 1 P2, mixed heating circuit 1 P3, mixed heating circuit 1 P1, mixed heating circuit 2 P2, mixed heating circuit 2 P3, mixed heating circuit 2 P1, hot-water circuit P2, hot-water circuit P3, hot-water circuit
Factory setting AUTO
Economy interval pause of circulating pump Economy interval cycle (period duration) Circulating pump
0. setting value of parameter Switch-on interval while the circulating pump is running 1. 60 min 20
Normal operation Switched off during hotwater circuit charging
Parameter 17
Designation Behaviour of heat generator during follow-up time
Setting range / Setting values AUTO Setpoint at heat generator depending on demand Heat generator off during follow-up time of solar charging pump
Pos: 6 /156-Honeywell/Menue_Direktheizkreis/Menue_Direktheizkreis @ 0\m od_1206968634235_6.doc @ 8834
"Direct heating circuit" menu (UNMIXED CIRC)
This menu contains all parameters required to program the unmixed heating circuits, except the switching time programs.
Parameter Heating curve Reduced
Designation Slope
Setting range / Setting values OFF, 0.02 to 3.50
Factory setting 1.5
Reduced operation ECO RED UFH RAD CON V OFF
Switch-off operation Lowering operation Under floor heating Radiator Convector heater Display of heat generator temperature, room sensor off, operation active Display of room temperature, room sensor active, operation active Display of room temperature, room sensor active, operation disabled Display of room temperature, room sensor off, operation active
ECO RAD
HeatHeating system ing system
Room connection (in conjunction with room sensor)
Room factor
OFF 10. 500 % RC Influence active
Room controller active OFF 10
Heating limit Room frostprotection limit
OFF, 0.5 to 40 K 5. 30C
Parameter 09 10
Designation Room thermostat function Assignment of outside sensor
Setting range / Setting values OFF, 0.5 to 5 K 0 Regulation to average value (outside sensor 1 + outside sensor 2) Regulation to outside sensor 1 Regulation to outside sensor 2
Factory setting OFF 0
11 Constant temperature setpoint Minimum temperature limit Maximum temperature limit
10. 95C
10C to setting value of parameter 13 Setting value of parameter 12 to Setting value of parameter 30 in "Heat generator" menu (OEM maximum limit)
Temperature 5. 20 K increase of heating circuit Extended pump over-run Screed function 0. 60 min OFF Functional heating Screed-drying heating
Direct heating circuit = OFF
Room control C-factor (SDW 30 only) Room control Tn (SDW 30 only) Holiday operating mode Room setpoint ramp
1. 100
5. 240 min STBY RED Standby Lowering operation
35 STBY OFF
OFF, 0.5 to 60 K/h
Parameter 41
Designation Switch-on optimisation
Setting range / Setting values OFF 3 Adaption off Adaption on Adaption restart
Heating circuit name
Min. pre-heat time Max. pre-heat time Min. jump back temperature Without room sensor Pre-heat time at 0C Lowering ramp Heating circuit name
0. setting value of parameter 43 Setting value of parameter 42 to 30 h 0. 30C 0. 10C 0. 30 h 0. 500 % 00000. ZZZZZ
Pos: 7 /156-Honeywell/Menue_Mischheizkreis_1+2/Menue_Mischheizkreis_1+2 @ 0\m od_1206968849516_6.doc @ 8850
"Mixed heating circuit 1 / 2" (MIX.VALVE - 1 / MIX.VALVE - 2) menus
These menus contain all parameters required to program the mixed heating circuit, except the switching time programs.
Reduced operation ECO RED UFH RAD CONV OFF
Switch-off operation Lowering operation Floor heating Radiator Convector heater Display of heat generator temperature, room sensor off, operation active Display of room temperature, room sensor active, operation active Display of room temperature, room sensor active, operation disabled Display of room temperature, room sensor off, operation active
HeatHeating system ing system 03 Room connection (in conjunction with room sensor)
OFF 10. 500 % RC Influence active Room controller active
Heating limit
OFF, 0.5 to 40 K
Parameter 10
Designation Room frostprotection limit Room thermostat function Assignment of outside sensor
Setting range / Setting values 5. 30 C OFF, 0.5 to 5 K 0 Regulation to average value (outside sensor 1 + outside sensor 2) Regulation to outside sensor 1 Regulation to outside sensor 2
Factory setting 10 OFF 0
11 Constant temperature setpoint (only if output was set to constant regulator) Minimum temperature limit Maximum temperature limit
Temperature 5. 20 K increase of heating circuit Follow-up time of pump Screed function 0. 60 min OFF Functional heating Screed-drying heating
Mixed heating circuit = OFF
17 18* 19* 20* 22
Return maximum temperature limit P part XP Sampling time Ts I part Tn
10. 90 C 1. 50 %/K 1. 600 s 1. 600 s
Parameter 21* 22*
Designation Actuator runtime Actuator end position function
Setting range / Setting values 10. 600 s Continuous control signal in end position Control signal suppressed at end position (actuator deenergised)
Factory setting 120 1
Room control Cfactor (SDW 30 only) Room control Tn (SDW 30 only) Holiday operating mode Room setpoint ramp Cooling temperature of mixed heating circuit Spread of hotwater circuit preregulator Offset valve position of hotwater circuit preregulator Switch-on optimisation
35 STBY OFF OFF
OFF, 0.5. 60 K/h OFF, 18 to 24
2. 20 K
0. 100 %
OFF 3 Adaptation off Adaptation on Adaptation restart
Minimum pre-heat time
0. setting value of parameter 43 0.5
Parameter 47 Heating circuit name
Designation Maximum pre-heat time Min. jump back temperature Without room sensor Pre-heat time at 0 C Lowering ramp Heating circuit name
Setting range / Setting values Setting value of parameter 42 to 30 h 0. 30 C 0. 10 C 0. 30 h 0. 500 % 00000. ZZZZZ
Factory setting 100
Pos: 8 /156-Honeywell/Menue_Waermeerzeuger/Menue_Waermeerzeuger @ 0\m od_1206968927001_6.doc @ 8866
"Heat generator" menu (HEAT GENER.
The parameters in this menu refer to the type of the respective heat generator and the associated specific control functions.
Parameter 01
Designation Design
Setting range / Setting values OFF 5 Without heat generator Oil/gas - one stage Oil/gas - two stages Oil/gas - 2 x one stage Modulating burner Open Therm No start-up protection Unlimited start-up protection Start-up protection controlled by weather conditions Start-up protection disconnected
Start-up protection (not if parameter 01 = OFF)
OFF 1 2
Minimum temperature limit (not if parameter 01 = OFF) Maximal temperature limit (not if parameter 01 = OFF) Limit mode minimum limit (not if parameter 01 = OFF)
5C to setting value of parameter 04
38 (5 with automatic operation) 80
Setting value of parameter 03 to setting value of parameter 30 (OEM maximum limit) 3 Minimum limit based on request Limited minimum limit Unlimited minimum limit
Designation Sensor operating mode
Setting range / Setting values 3 Burner switch-off in case of defect External burner switchoff Burner enable in case of defect
Minimum burner runtime Burner switching differential I Burner switching differential II (not if parameter 01 = 2) Connection delay stage II Boiler start-up relief stage II
0. 20 min One stage: 2. 30 K Two stages: 2. (setting value of parameter 09 0.5 K) (setting value of parameter 08 + 0.5) to 30 K
0. 60 min (0 = 10 s) Unlimited enable during start-up relief Time-out during start-up relief Two-stage hot-water circuit charge (with delay of full-load stage) Two-stage hot-water circuit charge (unlimited) One-stage hot-water circuit charge (partial stage only)
Storage charge 12 stages
Parameter 13
Factory setting 0
Lead time of boiler 0. 10 min circuit pump or parallel heat generator enable (only with appropriate configuration in the "Hydraulics" menu) Follow-up time of 0. 60 min boiler circuit pump (only with appropriate configuration in the "Hydraulics" menu) Follow-up time of 0. 60 min feeder pump (only with appropriate configuration in the "Hydraulics" menu) Exhaust gas OFF temperature monitoring (only 0. 60 with appropriate min configuration in the "Hydraulics" menu) SLT Display of exhaust gas temperature only Heat generator lock if limit value is exceeded for set time Heat generator lock if limit value is exceeded
50. 500C Exhaust gas limit value (only with appropriate configuration in the "Hydraulics" menu)
Parameter 19*
Designation Modulation of proportional range XP Modulation of sampling time Ts Modulation of adjustment time Tn Modulation of runtime Modulation of start time Modulation of start power Outside temperature lock (not if parameter 01 = OFF) Base load increase Minimum temperature limit of heating circuits (only if parameter 02 = 3) Switching differential of minimum temperature limit of heating circuits (only if parameter 02 = 3)
Setting range / Setting values 0.1. 50 %/K
Factory setting 5
20* 21* 22* 23* 24* 25
1. 600 s 1. 600 s / C 5. 600 s 0. 900 s 0. 100 % OFF, 20 to +30 C
70 OFF
0. 60 K 5 C to setting value of parameter 03
Parameter 29
Designation Heat generator forced discharge
Setting range / Setting values OFF 3 Discharge to process water tank Discharge to heating circuits Discharge to buffer tank
30* 31* 37
OEM maximum limit Full-load regulation Power limit for heating Power limit for hot water Burner counter mode (counter of operating hours) Outside temperature lock, inverse Resetting of burner start counter and operating hours of stage 1 (not if parameter 01 = OFF) Resetting of burner start counter and operating hours of stage 2 (not if parameter 01 = 2 or 01 = OFF)
Setting value of parameter 03 to 130 C OFF, 0.5 to 10 50. 100 % 50. 100 % AUTO Feedback only Free counter
110 OFF AUTO
OFF, 20 to +30 C
RESET ST-1
RESET ST-2
Pos: 9 /156-Honeywell/Menue_Fernwaerm e/Menue_Fernwaerm e @ 0\mod_1206969020110_6.doc @ 8882
"District hot water" menu (DIST.HEATING)
The parameters in this menu refer to the type of the respective district hot-water station and the associated specific control functions.
Designation Increase Maximum limit of flow temperature setpoint Minimum district heating valve stroke Secondary flow boost Adjustment time Runtime of district heating valve 1 Runtime of district heating valve 2 Maximum return temperature setpoint Application point variable district heating return temperature Maximum return temperature setpoint with hot water circuit charge
Setting range / Setting values OFF, 10 to 50 K 10. 130 C
Factory setting 0 90
0. 50 %
06 07* 08*
0,1. 30 %/K 0. 60 min 10. 1800 s 10. 1800 s 0. 100 C
OFF, 20 to 10 C
0. 100 C
Parameter 11*
Designation Return limit of district heating valve
Setting range / Setting values 0 Temperature (parameters 12 through 15 are not displayed) Volume flow and temperature (parameters 12 through 14 are not displayed) Heat output and temperature (parameters 13 through 15 are not displayed)
12* 13* 14* 15*
Calibration of heat output Calibration of volume flow Maximum heat output Maximum volume flow
1. 9999 1. 9999 1. 9999 kW 0,01. 99.99 m3/h
9999 99.99
Pos: 10 /156-Honeywell/Menue_Ruecklaufanhebung/Menue_Ruecklaufanhebung @ 0\mod_1206969068626_6.doc @ 8898
"Return increase" menu (RETURN CONTR)
The parameters in this menu refer to special settings with regard to the increase in return temperature with heat generators. Enabling occurs only with corresponding activation in the "Hydraulics" menu.
Parameter 03
Return temperature 10. 95C setpoint Switch-off differential Follow-up time of pump 1. 20 K 0. 60 min
Pos: 11 /156-Honeywell/Menue_Solar/Menue_Solar @ 0\m od_1206969135766_6.doc @ 8914
"Solar" menu (SOLAR)
The parameters in this menu refer to special settings with regard to the solar applications. Enabling occurs only with corresponding activation in the "Hydraulics" menu.
Designation Switch-on differential Switch-off differential Minimum runtime of solar charging pump Collector maximum temperature Buffer maximum temperature limit Operating mode
Setting range / Setting values (Setting value of parameter 02 + 3 K) to 30 K 2 K to (setting value of parameter K) 0. 60 min
Factory setting 3
OFF, 70 to 210C 20. 110C Priority operation Parallel operation Priority operation of hotwater circuit Priority operation of buffer
210 75
Heat generator cycle inhibitor (only if parameter 06 = 1) Solar priority parallel switchover Heat balance
OFF, 0.5 to 24 h
OFF, 1 to 30 K OFF No heat balancing Heat balancing via flowthrough calculation Heat balancing via pulse input
OFF OFF
Parameter 14 15
Designation Reset heat balance Volume flow Density of medium Heat capacity of medium Final switch-off temperature Test cycle of solar charging switchover Switchover temperature
Setting range / Setting values SET by pressing the input button 0. 30 L/min or L/pulse 0.8. 1.2 kg/L 2. 5 KJ/kgK OFF, 90 to 210 C 1. 60 min
Factory setting 0 1.05 3.10
20. 110 C
Pos: 12 /156-Honeywell/Menue_Feststoff/Menue_Feststoff @ 0\m od_1206969179876_6.doc @ 8930
"Solid" menu (SOLID FUEL)
The parameters in this menu refer to special settings with regard to solids regulation. Enabling occurs only with corresponding activation in the "Hydraulics" menu.
Parameter 05
Designation Minimum temperature Maximum temperature Switch-on differential Switch-off differential Heat generator cycle inhibitor
Setting range / Setting values 20. 80 C 30. 100 C (Setting value of parameter 04 + 3 K) to 20 K 2 K to (setting value of parameter K) OFF, 2 to 180 min
Pos: 13 /156-Honeywell/Menue_Puffer/Menue_Puffer @ 0\m od_1206969217376_6.doc @ 8946
"Buffer" menu (BUFFER)
Designation Minimum temperature Maximum temperature Boiler temperature increase Buffer switching differential Forced discharge
5 C to setting value of parameter Setting value of parameter 01 to 95 C 10 to 80 K 1 to 70 K OFF In process water tank In heating circuits ON 2 OFF
Follow-up switchon differential Follow-up switchoff differential Buffer start-up protection
OFF, (setting value of parameter 07 + 2 K) to 50 K 1 K to (setting value of parameter K) OFF ON No start-up protection Start-up protection active No discharge protection Discharge protection active
Buffer discharge protection
Designation Buffer operating mode
Setting range / Setting values 1 Heating circuit charge regulation and hot-water circuit Heating circuit charge regulation without hot-water circuit Heating circuit and hot-water circuit discharge regulation Heating circuit discharge regulation without hot-water circuit Charge regulation with hot-water circuit switchover Discharge regulation for heat generator
Follow-up time of buffer charging pump 0. 60 min
Pos: 14 /156-Honeywell/Menue_Summenvorlaufregelung/Menue_Summenvorlaufregelung @ 0\mod_1206969262720_6.doc @ 8962
"Total flow regulation" menu (MAIN SUPPLY)
The parameters in this module refer to special settings with regard to total flow regulation. This selection is only available if a total flow sensor is configured on one of the variable inputs (see the "Hydraulics" menu, parameters 08, 09 or 10).
Parameter 01 03
Designation Regulation Regulation
Setting range / Setting values 0. 50 %/K 1. 600 s
Factory setting 5 180
Pos: 15 /156-Honeywell/Menue_Kaskadierung/Menue_Kaskadierung @ 0\m od_1206969304407_6.doc @ 8978
"Cascading" menu (CASCADE)
The parameters in this menu refer solely to the parameters that are associated with the cascading of multiple heat generators. This selection is only available if multiple heat generators exist in the control system.
Designation Switching differential Connection delay Switch-off delay Switchover power of stage sequence Stage reversal Guidance stage Peak-load stage
Setting range / Setting values 0.5. 30 K 0. 200 min 0. 60 min 10. 100 % OFF, 1 to 250 h 1. maximum number of stages OFF, 2. maximum number of stages All heat generators are numbered consecutively within the cascade. The total quantity determines the maximum number of stages.
Factory setting OFF 1 OFF
Switchover of base OFF, ON load with grouping Quick hot-water connection OFF, 1. maximum number of stages
Pos: 16 /156-Honeywell/Menue_Datenbus/Menue_Datenbus @ 0\mod_1206969341954_6.doc @ 8994
"Data bus" menu (BUS)
The parameters in this menu refer solely to the parameters that are associated with the data bus.
Designation Central device address Bus authorisation SDW 30 of direct heating circuit Bus authorisation SDW 30 of mixed heating circuit 1 Bus authorisation SDW 30 of mixed heating circuit 2
Setting range / Setting values 10, 20, 30, 40, 2 Expanded access authorisation Simple access authorisation Expanded access authorisation Simple access authorisation Expanded access authorisation Simple access authorisation
Factory setting 10 1
Pos: 17 /156-Honeywell/Menue_Relaistest/Menue_Relaistest @ 0\mod_1206969390188_6.doc @ 9010
"Relay test" menu (RELAY TEST )
In this menu, the relays contained within the central device can be selected via the input button and checked for operation.
Heat generator test Different relay switching sequence depending on the set heat generator Direct heating circuit pump test Mixed heating circuit pump 1 test Mixer motor 1 test Mixed heating circuit pump 2 test Mixer motor 2 test Storage charging pump test Variable output 1 test Variable output 2 test System OFF-ON-OFF OFF-ON-OFF STOP-OPEN-CLOS OFF-ON-OFF STOP-OPEN-CLOS OFF-ON-OFF OFF-ON-OFF OFF-ON-OFF Display of sensor value by pressing the input button
Pos: 18 /156-Honeywell/Menue_Stoermeldungen/Menue_Stoermeldungen1 @ 0\m od_1206969445079_6.doc @ 9026
OFF OFF STOP OFF STOP OFF OFF OFF
"Error messages" menu (ALARM)
Error messages that occur are displayed in this menu. The fault memory can hold max. 20 messages, which can be displayed individually.
Parameter 05. 20 21*
Designation Error message 1 Error message 2 Error message 3 Error message 4 Error message 5
Setting range / Setting values Last error message Last error message but one Last error message but two Last error message but three Last error message but four First error message
Factory setting "Display" "Display" "Display" "Display" "Display"
Error message 20 Reset error messages * OEM
"Display"
Pos: 19 /156-Honeywell/Menue_Stoermeldungen/Menue_Stoermeldungen2 @ 0\m od_1206969471860_6.doc @ 9041
"Error messages 2" menu (ALARM 2)
Only in conjunction with heat generator interface Error messages triggered by an automatic stoker are displayed in this menu. The fault memory can hold max. 20 messages, which can be displayed individually. For this purpose, parameter 28 in the "System parameters" menu must be set to ON.
Parameter 03 04. 20 21*
Designation Error message 1 Error message 2 Error message 3 Error message 4 Error message 20 Reset error messages
Setting range / Setting values Last error message Last error message but one Last error message but two Last error message but three First error message SET by pressing the input button * OEM
Pos: 20 /156-Honeywell/Menue_Fuehlerabgleich/Menue_Fuehlerabgleich @ 0\mod_1206969622157_6.doc @ 9057
Factory setting "Display" "Display" "Display" "Display" "Display"
"Sensor calibration" menu (SENSOR ADJ.)
In this menu, all sensors connected to the central device can be corrected by 5 K based on the factory calibration value.
Parameter 03 04
Designation Outside sensor Heat generator sensor Hot-water sensor Flow sensor of mixed heating circuit 1 Flow sensor of mixed heating circuit 2 Collector flow sensor Buffer sensor of collector Sensor of variable input 1 Sensor of variable input 2 Sensor of variable input 3
Setting range / Setting values 5. +5 K 5. +5 K 5. +5 K 5. +5 K
Factory setting 0 0
5. +5 K
5. +5 K 5. +5 K 5. +5 K 5. +5 K 5. +5 K
Room sensor SDW 5. +5 K 10 of direct heating circuit Room sensor SDW 5. +5 K 10 of mixed heating circuit 1 Room sensor SDW 5. +5 K 10 of mixed heating circuit 2
Pos: 21 /156-Honeywell/Protokoll/Protokoll @ 0\m od_1206969686157_6.doc @ 9072
Weekly switching program
Object: Mon (1) Cont. circuit Time Setpoint Opt. Tue (2) Cont. circuit Time Setpoint Opt. Wed (3) Cont. circuit Time Setpoint Opt. Thu (4) Cont. circuit Time Setpoint Opt. Fri (5) Cont. circuit Time Setpoint Opt. Sat (6) Cont. circuit Time Setpoint Opt. Sun (7) Cont. circuit Time Setpoint Opt.
===== Ende der Stckliste =====
Set by:
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Srl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Automation and Control Solutions Honeywell House Arlington Business Park Bracknell, Berks, RG12 1EB Phone (44) Fax (44) http://honeywell.com/uk Printed in Germany All rights reserved. Subject to change without notice. EN0B-0565GE51 R0308 Art. 30

Hot-water temperature greater than 60 C... 21 Connection of accessory parts... 22 Maintenance and cleaning... 22
Installation.... 22 Connection assignment.... 23 4.1 With wall base for heating / district heating applications.. 25
Selection of parameter presettings for a hydraulic unit.. 27 Applications.... 27 Technical data.... 28 7.1 7.2 General.... 28 Sensor resistance values... 29 7.2.1 7.2.2 7.3 7.4 NTC 20... 29 PT 1000.... 29
Sensor measurement ranges.... 30 Digital inputs... 30
Software version
Pos: 15 /156-Honeywell/Montage/Wandmontage @ 0\m od_1205908505416_258.doc @ 4809
This documentation is valid for software version V 3.0 of your control device. The software version is displayed after switch-on for approx. 8 s. If you are using an older software version, please contact your heating technician.
Pos: 2 /156-Honeywell/Sicherheitshinweise/Sicherheitshinweise @ 0\mod_1207134414454_6.doc @ 9105
Safety instructions
Intended use The SDC / DHC Smile family of controllers was designed for the sole purpose of regulating and controlling hot-water, heating and district heating systems (including hot-water production) that do not exceed a maximum flow temperature of 120 C.
Requirements for start-up ATTENTION The heating system must be complete and filled with water so that the pumps do not run dry and the heating boiler is not damaged. The control equipment must be installed in accordance with the installation instructions. All electrical connections (voltage supply, burner, mixer motor, pumps, sensor wiring etc.) must be carried out by the technician in accordance with the applicable VDE regulations and correspond with the circuit diagrams. If floor heating is connected, a limiting thermostat must also be installed in the flow line after the heating circuit pump. This switches off the pumps at excessive flow temperatures. Before starting up the controller, have the heating technician check all requirements listed above.
The current time and date are already set at the factory and are backed up by a battery. The time switch functions based on a basic program and the control functions are preset for common heating systems with lowtemperature boilers.
Power supply Do not disconnect the controller from the mains supply! The battery for saving all individualised data is otherwise unnecessarily strained. The frost-protection function of the controller is deactivated.
Connection conditions All electrical connection work may only be carried out by qualified personnel!
Cable cross-sections 1.5 mm2 for all cables carrying 230 V (power supply, burner, pumps, actuator). 0.6 mm2 for bus cables (recommended type J-Y(St)Y 2 x 0.6). 0.5 mm2 for sensors, selectors and analog signal cables.
Maximum cable lengths Sensor, selector and analog inputs We recommend using cables no longer than 200 m. Longer connection lines could be used, but increase the risk of interference. Relay outputs Unlimited cable length. Bus connections Max. length of 100 m from the first bus subscriber to the last one (incl. wall modules).
Cable installation Install cables for sensors apart from the cables carrying 230 V! Branch boxes in the sensor cable must be avoided!
Grounding and zeroing Local regulations on the connection of equipment must be observed!
Hot-water temperature greater than 60 C ATTENTION Note that there is a danger of scalding at all hot-water drawoff points (kitchen, bathroom etc.) in the following cases. Add sufficient cold water in these cases.
Automatic antilegionella mechanism
When the automatic anti-legionella mechanism is activated, the hot water is automatically heated to the anti-legionella temperature (65 C at the factory) on the selected day and at the selected time to kill any legionella bacteria found in the hot-water tank. In the manual mode / emission measurement operating mode, the hot water is heated up to the highest possible boiler temperature, as the burner and all pumps are switched on and the mixer is opened fully. There is an acute danger of scalding at all connected hot-water draw-off points! Add sufficient cold water or switch off the hot-water loading pump (at the switch of the pump, if present). Heating and hot water are in unregulated continuous operation. This operating mode is for special use by the chimney sweep for emission measurement or if the controller is defective. The high hot-water temperatures can be prevented, however, by setting the boiler thermostat to a max. boiler temperature of approx. 60 C.
Manual mode / Emission measurement
Installation
Connection of accessory parts WARNING According to VDE 0730, a separator for each mains terminal is to be provided in the voltage supply to the control equipment. Observe the local regulations regarding grounding and zeroing. As soon as the mains voltage is applied to terminals 21, 22, 2, 6, 12 and 18, headers X3 and X4 can also carry mains voltage. If the heating circuit and hot-water loading pumps do not have an On / Off switch, but manual switch-on and switch-off capability is still desired, the appropriate switches must be installed by the customer. All accessory parts (sensors, selectors etc.) are to be connected to the respective circuit diagram.
Maintenance and cleaning The controller is maintenance-free. The device can be cleaned externally with a moist (not wet) cloth.
Pos: 3 /156-Honeywell/Montage/Montage @ 1\mod_1208507648076_6.doc @ 11070 Fehler ! Ungltiger Eigenverweis auf Textmarke. Page 19 Fehler! Ungltiger Eigenverweis auf Textmarke. Page 19
See 8 Montage / Installation, pg. 31.
Pos: 4 /156-Honeywell/Montage/Anschlussbelegung @ 1\mod_1207648415963_6.doc @ 10035
Connection assignment
Pos: 5 /156-Honeywell/Montage/Netzseitiger_Anschluss @ 1\mod_1207648423572_6.doc @ 10067
Mains-side connection
No. Connection 19 Heat generator relay output (T2), stage 1; for district heating controllers, district heating valve CLOSED Heat generator relay input (T1), stage 1; for district heating controllers L1 Direct heating circuit pump Not occupied Hot-water loading pump L1 / 230 V Mixer motor 1 OPEN Mixer motor 1 CLOSED Mixed heating circuit pump 1 Variable output 1 Variable output 2 L1 / 230 V Mixer motor 2 OPEN Mixer motor 2 CLOSED Mixed heating circuit pump 2 Stage 2 (T7); for district heating controllers, district heating valve OPEN* Heat generator relay output (T8), stage 2 Heat generator relay input (T6), stage 2; for district heating controllers L1 Burner operating hour counter, stage 2 23
No. Connection 22 * Burner operating hour counter, stage 1 N / 230 V L1 / 230 V mains connection
with district heating controllers
Pos: 6 /156-Honeywell/Montage/Fuehler-/Datenbus-Anschluss @ 1\mod_1207648419728_6.doc @ 10051
Sensor / data bus connection
No. Connection Common sensor ground Bus side A Bus side B Outside sensor Heat generator sensor/Boiler sensor Hot-water sensor Mixed heating circuit 1 flow sensor Variable input 1 Variable input 2 Variable input 3 Mixed heating circuit 2 flow sensor Collector flow sensor (solar application, PT 1000) Collector return sensor (solar application) Pulse input OpenTherm A OpenTherm B
Pos: 7 /156-Honeywell/Montage/Wandsockel_fuer_Heizungs-Fernheizungsanwendungen @ 1\m od_1207648426072_6.doc @ 10083
With wall base for heating / district heating applications
Bridge for district heating controllers OPEN CLOSED Brief description Meaning
T2B A, Bus A Data bus connection A T2B B, Bus B Data bus connection B AF WF / KF SF VF1 VE1 VE2 VE3 VF2 KVLF KSPF IMP T1 Outside sensor, GND connection on X5 Heat generator sensor, GND connection on X5 Tank sensor, GND connection on X5 Mixed heating circuit 1 flow sensor, GND connection on X5 Variable input 1, GND connection on X5 Variable input 2, GND connection on X5 Variable input 3, GND connection on X5 Mixed heating circuit 2 flow sensor, GND connection on X5 Collector flow sensor, GND connection on X5 Collector tank/buffer sensor, GND connection on X5 Pulse input, GND connection on X5 Burner connection (T1), stage 1; for district heating controllers L1 25
Brief description T2
Meaning Burner connection (T2), stage 1; for district heating controllers, district heating valve V1 CLOSED, N on X9, PE on X10 Burner connection (T6), stage 2; for district heating controllers L1 Burner connection (T7), stage 2; for district heating controllers, district heating valve V1 OPEN Burner connection (T8), stage 2 Direct heating circuit pump, connections N and PE on X9 / X10 Tank loading pump, connections N and PE on X9 / X10 Mixed heating circuit 1 pump, connections N and PE on X9 / X10 Mixer open - mixed heating circuit 1, connections N and PE on X9 / X10 Mixer closed - mixed heating circuit 1, connections N and PE on X9 / X10 Variable output 1, connections N and PE on X9 / X10 Variable output 2, connections N and PE on X9 / X10 Mixed heating circuit 2 pump, connections N and PE on X9 / X10 Mixer open - mixed heating circuit 2, connections N and PE on X9 / X10 Mixer closed - mixed heating circuit 2, connections N and PE on X9 / X10 Ground terminals bridged for sensor inputs Neutral wire bridged for connected pumps / mixers 230 V mains connection PE conductor bridged for connected pumps / mixers
T6 T7 T8 DKP SLP MKP1 MK1 OPEN MK1 CLOSED VA1 VA2 MKP 2 MK2 OPEN MK2 CLOSED GND N L1 PE
Selection of parameter presettings for a hydraulic unit
Pos: 8 /156-Honeywell/Montage/Auswahl_von_Parameter-Voreinstellungen_ fuer_eine_Hydraulik @ 1\m od_1207648506291_6.doc @ 10099
In the state of delivery, each controller type covers multiple hydraulic units. Each hydraulic unit can be changed or expanded by changing and/or adding parameters. A hydraulic unit is selected with parameter 01 in the "Hydraulics" menu. The corresponding inputs and outputs are assigned automatically based on the hydraulics schematic. This function simplifies the setting of a documented hydraulic unit considerably. Additional applications can be covered by setting the individual parameters. Where necessary, the parameters are also specified in these mounting instructions. A description of how to access parameter settings can be found in the parameter list.
Operation
Operating in- Menu formation Hydraulics preselection
Pos: 9 /156-Honeywell/Montage/Applikationen @ 1\m od_1208507778701_6.doc @ 11085
Enter schematic, e.g. 0201
"Hydraulics"
Applications
See chapter 9 Heizungs-Applikationen / Heating applications pg. 35 and chapter 10 Fernheizungs-Applikationen / District heating applications pg. 55.
Pos: 10 /156-Honeywell/Montage/Technische_Daten_Allgem ein @ 1\m od_1207651393978_6.doc @ 10115
Technical data
7.1 Mains connection voltage Rated frequency Power consumption Pre-fuse Contact load of the output relays Bus interface Max. bus length Power supply via bus Ambient temperature Storage temperature Degree of protection
General 230 V +6 % / 10 % 50. 60 Hz max. 5.8 VA max. 6.3 A slow-blowing 2 (2) A For the connection of external devices (wall device, PC, modem or gateway) 50 m 12 V/150 mA 0. +50C 25. +60C IP 30
Protection class as per II EN 60730 Protection class as per III EN 60529 Radio protection EC conformity Housing dimensions Housing material EN 55014 (1993) 89/336/EEC 144 x 96 x 75 mm (W x H x D) ABS with static inhibitor Interference resistance EN 55104 (1995)
Connection technology Plug-in screw terminal connections
Pos: 11 /156-Honeywell/Montage/Fuehler-Widerstandswerte (1) @ 1\m od_1207651435572_6.doc @ 10163
Sensor resistance values NTC 20 For outside sensor (OT), heat generator sensor (BLRS/BS), tank sensor (DHWS), mixed heating circuit 1 flow sensor (VF1), mixed heating circuit 2 flow sensor (VF2), variable input 1 (VI-1) (setting not for exhaust gas sensor), variable input 2 (VI-2), variable input 3 (VI-3), collector tank/buffer sensor (SBUS).
k 220.6 195.4 173.5 154.2 137.3 122.4 109.2 97.56 87.30 78.23
C 16 18
Pos: 12 /156-Honeywell/Montage/Fuehler-Widerstandswerte (2) @ 1\m od_1207651438666_6.doc @ 10179
k 70.20 63.04 56.69 51.05 46.03 41.56 37.55 33.97 30.77 27.90 PT 1000
k 25.34 20.00 15.88 12.69 10.21 8.258 6.718 5.495 4.518 3.734
k 3.100 2.587 2.168 1.824 1.542 1.308 1.114
For variable input 1 (VI-1) (setting of exhaust gas sensor), collector flow sensor (SPFS) C k 1000.00 1039.02 1077.93 1093.46 1116.72 1155.39 1193.95 1232.39 1270.72 1289.84 C 120 130
Pos: 13 /156-Honeywell/Montage/Fuehler-Messbereiche @ 1\mod_1207651432947_6.doc @ 10147
k 1308.93 1327.99 1347.02 1366.03 1385.00 1403.95 1422.86 1441.75 1460.61 1498.24
k 1535.75 1573.15 1610.43 1647.60 1684.65 1721.58 1758.40 1831.68 1904.51 1976.86
k 2048.76 2120.19 2191.15 2261.66 2331.69 2401.27 2470.38 2641.12 2811.00
7.3 Designation Outside sensor Heat generator sensor Flow sensor 1 Flow sensor 2 Tank sensor Collector flow sensor Collector tank / buffer sensor Variable input VI-1*) Variable input VI-2 Variable input VI-3
Sensor measurement ranges Brief description AF KF VF1 VF2 SF KVLF KSPF VE1 VE2 VE3 Sensor type NTC 20 NTC 20 NTC 20 NTC 20 NTC 20 PT 1000 NTC 20 NTC 20 PT 1000 NTC 20 NTC 20 Measurement range 50 C to 90 C 50 C to 120 C 50 C to 120 C 50 C to 120 C 50 C to 120 C 50 C to 210 C 50 C to 120 C 50 C to 120 C 50 C to 500 C 50 C to 120 C 50 C to 120 C
*) Depending on the selection of the assigned function. PT 1000 e.g. for exhaust gas sensor connection.
Pos: 14 /156-Honeywell/Montage/Digitaleingaenge @ 1\mod_1207651398760_6.doc @ 10131
7.4 Designation Impulse metering unit
Digital inputs Brief description Imp Input type Extra-low voltage 230 V 230 V Measurement range 10 Hz OFF, ON OFF, ON
Burner stage 1 operating BZ1 hour counter Burner stage 2 operating BZ2 hour counter
Pos: 15 /156-Honeywell/Montage/Wandmontage @ 0\m od_1205908505416_6.doc @ 4811
Montage / Installation
Wandmontage / Wall installation
Pos: 16 /156-Honeywell/Montage/Schaltschrankeinbau @ 0\m od_1205908625447_258.doc @ 4818
Schaltschrankeinbau / Panel mounted installation
Pos: 17 /156-Honeywell/Montage/Heizungs-Applikationen @ 1\m od_1207652042056_258.doc @ 10210
Heizungs-Applikationen / Heating applications
Pos: 18 /156-Honeywell/Montage/Uebersicht_Heizungs-Applikationen @ 1\mod_1207652275338_258.doc @ 10226
bersicht / Overview Hydraulik Hydraulics Typ Type SDC 3-10 SDC 7-21 SDC 9-21 SDC 12-31 SDC 12-x SDC 12-31 Seite Page 40 42
Kesselfolge mit 1 x SDC 3-40 Heizkreisen und Warmwasserkreis / Boiler sequence with heating circuits and hot-water circuit 0404 0405
Pos: 19 /156-Honeywell/Montage/0101/SDC3-10 @ 1\m od_1207652435353_258.doc @ 10242
SDC 3-40 SDC 9-21 SDC 9-21 SDC 12-31
Hydraulik 0101 (SDC 3-10) / Hydraulics 0101 (SDC 3-10)
X38 GND BUS A BUS B AF WF SF 21 22
X3 T2 T1 DKP S LP L17 18
X12 Bus B GND GND GND GND GND GND GND GND GND GND GND 11 12
X 6 Bus A AF WF SF 11
X7 T10 11
X8 T2 DKP S LP 13
X9 N N N N N N N N N N N N N 13
X 10 PE PE PE PE PE PE PE PE PE PE PE PE PE
Pos: 20 /156-Honeywell/Montage/0201/SDC9-21 @ 1\m od_1207652467791_258.doc @ 10258
Hydraulik 0201 (SDC 7-21) / Hydraulics 0201 (SDC 7-21)
X38 GND BUS A BUS B AF WF SF V F1 RLF22
X3 T2 T1 DKP SLP L1 M K1 M K1 P17 18
X6 Bus A AF WF SF VF 1 RLF10 11
X8 T2 DKP SLP M K1 M K1 P12 13
Pos: 21 /156-Honeywell/Montage/0202/SDC9-21 @ 1\m od_1207652468275_258.doc @ 10274
Hy 0201-6_06
Hydraulik 0202 (SDC 9-21) / Hydraulics 0202 (SDC 9-21)
DKP MK SLP
===== Ende der Stckliste =====
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Srl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Automation and Control Solutions Honeywell GmbH Bblinger Strasse Schnaich / Germany Phone (49) 01 Fax (49) 493 http://ecc.emea.honeywell.com Gedruckt in Deutschland Alle Rechte und nderungen vorbehalten MU1H-0207GE51 R0308 Art. 30
Automation and Control Solutions Honeywell House Arlington Business Park Bracknell, Berks, RG12 1EB Phone (44) Fax (44) http://honeywell.com/uk Printed in Germany All rights reserved. Subject to change without notice.
Tags
SA-706 BHP452Z 8HP-2004 Server LE32B652 GZ-MG155E Biotec 30 I845 Darbuka CDM-105 MP OPL C5950 Syncmaster 740N MC2660E-M WV-NP244 FTK113 C18AHR Classic F210X PT-L701U 20UX143 Programchart DV-SR84RU Radio 9004 CTC VS-1880 2009 R2 WD-1025FB CDX-GT647UI HSU-12HEK03 R2 CT-S210 II FZ6-S-2006 T 9357 ICF-C233L RY46501B MRP-T306 HTR-5230 CD723-00 Bizhub 222 IEL9115-RF 08 BMW 3 SPP-A450 LE40R73BD MV730I HBN5055AUC Optoma H30 CBX-300 TH-42PX8E DVP721VR WF-42P1 HTK2360MT MX 11 XR-30X LE46C650 Explorist GC KW-AVX810 Tango DX-610 HT-M700H Aficio 6010 PT-D5500E Deskjet 843C DLS R4 Aspire 1300 Lexmark Z730 20HF5234 10 RX-V795 Gigashot K GU19wdvdt CLP-220 3d LS-T246CEL 3dforce2MX-32TV T7400 7700GX Underdark RC7723W Xl DUO Multiverb III SP-A600B EWF12470W LH-T6000 Review GPS 100 Date 1974 SD110 DPL590 MG15fxmsdm H5360 Cabriolet Diablo Motorola S605 LV989 TX-32LXD85 Navigon 8410 DJ-X10 540 Live AV-R700 26PFL5322 MP15Q
manuel d'instructions, Guide de l'utilisateur | Manual de instrucciones, Instrucciones de uso | Bedienungsanleitung, Bedienungsanleitung | Manual de Instruções, guia do usuário | инструкция | návod na použitie, Užívateľská príručka, návod k použití | bruksanvisningen | instrukcja, podręcznik użytkownika | kullanım kılavuzu, Kullanım | kézikönyv, használati útmutató | manuale di istruzioni, istruzioni d'uso | handleiding, gebruikershandleiding
Sitemap
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101