Foam 22a
TECHNICAL DATA
Deluge foam/water system supplied by foam pump
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. Description
A Foam Deluge System Supplied by a Foam Pump is a standard deluge system capable of discharging foam/water solution automatically through any discharge device supplied from the deluge system piping. A deluge foam/water system with a hydraulically actuated Halar coated concentrate control valve consists of a Viking deluge valve (A) complete with standard deluge trim, detection and releasing devices on the water supply line, an In-line Balanced Proportioner Assembly (proportioning device) (B), which includes a concentrate controller, listed orifice plate, spool balancing valve and swing check valve, hydraulically actuated Halar coated concentrate control valve (C) on foam concentrate line, a foam concentrate atmospheric tank and trim, and foam concentrate agent. No formal approval as a system. Main component approvals listed below. Deluge Valve and Trim UL Listed - Guide VLFT FM - Automatic Water Control Valves In-line Balanced Pressure Proportioner (ILBP) UL Listed - Guide GFGV FM Approved - Low Expansion Foam Systems Halar Coated Concentrate Control Valve (CCV) UL Listed - Guide VLFT FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate UL Listed - Guide GFGV FM Approved - Low Expansion Foam Systems
2. LISTINGS AND APPROVALS
3. technical data
Refer to individual component technical data page. Refer to individual component technical data page. Refer to Tables 1 through 3.
Specifications:
Material Standards:
Ordering Information:
Viking Technical Data may be found on The Viking Corporations Web site at http://www.vikinggroupinc.com. The Web site may include a more recent edition of this Technical Data Page.
4. installation
A. Discharge Devices
Standard Spray Sprinklers (Open Type) Foam chambers Foam makers Oscillating Monitors & Nozzles Fixed Monitors and nozzles Spray Nozzles Listed discharge devices are tested with specific concentrates and may have different listed densities that what is listed in various NFPA standards. AR-AFFF foam concentrates are listed with specific discharge devices and the fuels they are to protect.
B. General Instructions and Warnings
1. Refer to the Warnings and General Notes on pages 2a-d in the Foam Design section of the Viking Foam Systems Engineering and Design Data book. 2. Refer to specific technical data sheets, acceptable installation standards, codes and Authority Having Jurisdiction for additional installation, operation, and maintenance instructions. 3. Inspections It is imperative that the system is inspected and tested on a regular basis. See Section 6 - Inspections, Tests, and Maintenance. 4. Warning Any system maintenance or testing that involves placing a control valve or detection system out of service may eliminate the fire protection of that system. Prior to proceeding, notify all Authorities Having Jurisdiction. Consideration should be given to employment of a fire patrol in the effected area. 5. The valve, trim and assembly must be installed in an area not subject to freezing temperatures or physical damage. Revised page replaces page Foam 22a-j, dated June 1, 2008. (Updated Release Trim and TrimPac Part Nos. in Table 2.)
Form No. F_011301
Foam 22b
Warning: Locate all portions of the foam/water system subject to freezing in a heated area. 1. Refer to the Special Notes section on page 20d and Warnings and General Notes on pages 2a-d in the Foam Design section of the Viking foam data book. 2. Install the deluge valve and trim (A) in accordance with Viking Engineering and Design Data book. 3. Install the proportioning device, ILBP assembly (B), in the riser at least 5 pipe diameters past the deluge valve. (The ILBP assembly must be installed 5 pipe diameters of straight piping past a valve or change of direction. The same 5 pipe diameters of straight pipe are required on the discharge side of the ILBP as well to ensure proper proportioning.) 4. Install foam solution test valve (7) and system isolation valve (8). These valves are required to facilitate annual foam proportioning tests. The system isolation valve (8) is in the normally open position when the system is in operation. The solution test valve (7) is in the normally closed position when the system is in operation. When the system is to be tested annually for proportioning, the system isolation valve (8) is closed to eliminate foam water solution from entering the system piping. The solution test valve (7) is opened once a flow rate is established in the riser. The solution test valve is normally sized the same size as the riser piping to accept the design flow of the system. The discharge of the solution test valve is normally piped to a test header with 2 angle valves to aid in controlling the discharge of foam solution. 5. Install the hydraulically actuated Halar coated concentrate control valve (C) and associated trim as indicated on trim charts or technical data pages. 6. A concentrate shut-off valve (3) located upstream of the Halar coated concentrate control valve (C) is required to isolate the Halar coated concentrate control valve (C) when setting up the system or when repairs are to be made to the foam/deluge system. 7. Install the foam pump skid assembly and atmospheric storage tank in accordance with manufacturers instructions. a. Install the foam pump skid and foam atmospheric storage tank. Install the concentrate piping from the discharge of the foam pump skid to the concentrate shut-off valve (3). Locate the concentrate shut-off valve as close as practical to the ILBP assembly. Note: Allow enough room around the foam pump and atmospheric storage tank for service. b. Allow access to atmospheric storage tank for filling from barrels of foam concentrate. c. All valves and devices should be located for easy access for operation and maintenance.
C. Design and Installation
D. Placing System in Service
1. Verify that the water supply control valve (1) is closed, then place deluge valve (A) in service. (See instructions on Viking Technical Data Sheet.) a. Open the system isolation valve (8) if closed. b. Close the solution test valve (7) if open. 2. Set the deluge valve release system according to the installation instructions for type of deluge system used. 3. Prime both the Viking deluge valve (A) and Halar coated concentrate control valve (C) by opening the priming valve on the deluge valve trim. Bleed off any air pressure trapped in the priming line (2) to the Halar coated concentrate control valve (C) by opening the 3-way pressure gauge valve (6). 4. Open the water supply control valve (1) after the deluge valve has been primed. There should not be any water flowing from trim outlets. If water is discharging from trim outlets, refer to Viking technical data pages for trouble shooting and proper installation of trim piping. 5. Place foam pumping system in service. The concentrate shut-off valve (3) will be in the closed position until foam pump system is placed in service. Foam concentrate pressure will be indicated on the foam concentrate pressure gauge (4) located upstream of the of the concentrate shut-off valve (3). Once pressure is indicated on concentrate pressure gauge (4), slowly open foam concentrate shut-off valve (3). 6. Once the foam concentrate shut-off valve (3) is opened, verify that foam concentrate is not passing by the Halar coated concentrate control valve (C) by opening the foam concentrate auxiliary drain valve (5). If foam concentrate appears, close the concentrate shut-off valve (3) immediately. If foam concentrate is passing by the Halar coated concentrate control valve (C), the valve is not seating and is most likely fouled. Debris must be removed from seat of Halar coated concentrate control valve (C). 1. For system and riser piping maintenance and service: a. Close the water supply control valve (1). b. Close the concentrate shut-off valve (3). c. Open all drain valves on deluge system.
E. Removing the System From Service
Foam 22c
d. Leave the system isolation valve (8) open. e. Refer to the instructions for removing the deluge valve (C) from service in the Viking Engineering and Design Data book. f. Perform maintenance and service on system and riser piping. g. If maintenance is required to be performed on concentrate piping, remove foam pump and foam jockey pump if applicable from service. Open concentrate drain valve to relieve pressure from concentrate supply piping. NOTE: If repairs or modifications are required on the foam concentrate supply piping, the deluge may be kept in service for protection, while repairs to the foam system concentrate piping are performed.
5. Operation
Actuation of the release system of the deluge system relieves the priming pressure of the deluge valve and the priming pressure present in the Halar coated concentrate control valve (C). Once the deluge valve (A) opens, water passes through the concentrate controller of the ILBP (In-Line Balanced Proportioner) (B). The foam pump will provide foam concentrate at a higher pressure than the water pressure passing through the riser. The pressures will be balanced by the spool balancing valve that is integral to the ILBP. The foam pump is normally started on a pressure loss in the concentrate piping line. The foam pump may also start through the water pressure switch on the deluge valve trim. If more than fifty feet of overhead concentrate piping is present on the discharge side of the foam pump or if any of the piping is installed underground, a means of checking the tightness of the piping is required per NFPA. This may necessitate a foam jockey pump to maintain the pressure on the concentrate line. Once water passes through the concentrate controller, foam concentrate is discharged into the concentrate controller through an orifice listed and approved for the foam concentrate to be utilized. The foam and water mix and create a foam/water solution. A foam blanket is created once it has discharged through the discharge device(s). A foam blanket is produced through one of two actions, agitation as what would happen when discharged through a standard sprinkler head, or aeration as what would happen when discharged through a foam chamber or foam maker. The foam blanket that is created by the discharge device is part of the listing or approval obtained with the foam concentrate testing. NOTICE: The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to recognized standards such as those produced by NFPA, LPC and VdS, which describe care and maintenance of sprinkler systems. In addition, the Authority Having Jurisdiction may have additional maintenance, testing and inspection requirements that must be followed. WARNING - Any system maintenance or testing that involves placing a control valve or detection system out of service may eliminate the fre protection of that system. Prior to proceeding, notify all Authorities Having Jurisdiction. Consideration should be given to employment of a fire patrol in the affected area. Inspections - It is imperative that the system is inspected and tested on a regular basis. The following recommendations are minimum requirements. The frequency of the inspections may vary due to contaminated or corrosive water supplies and corrosive atmospheres. In addition, the alarm devices or other connected equipment may require more frequent inspections. Refer to the technical data, system description, applicable codes, and Authority Having Jurisdiction for minimum requirements. Prior to testing the equipment, notify appropriate personnel. The Deluge Foam/Water System Supplied by Foam Pump is available through a network of domestic and international distributors. See the Viking Corp. web site for closest distributor or contact The Viking Corporation. For details of warranty, refer to Vikings current list price schedule or contact Viking directly.
6. INSPECTION, Tests, AND MAINTENANCE
7. Availability 8. guarantee
Foam 22d
Provide a minimum of 5 pipe diameters of straight pipe on the inlet and outlet of the concentrate controller (B) to minimize turbulence inside the concentrate controller. The combined total equivalent length of pipe, fittings and valves in both the water supply inlet piping and the foam concentrate discharge piping, must not exceed 50 equivalent feet (15.2 meters). This will allow both pipes to be the same size as the foam liquid inlet to the concentrate controller. Should the total equivalent length exceed 50 feet (15.2 meters), then refer to the Proportioning Equipment section of the foam data book for the method of calculating these pipe sizes. The Halar coated concentrate control deluge valve (C) and swing check valve must be connected adjacent to the concentrate controller using pipe nipples as short as possible. Figures 1 - 3 are general schematics of the required piping arrangement. Refer to the appropriate technical data page for specific information regarding the valve, tank, and related trim and devices. The technical information, statements, and recommendations contained in this manual are based on information and tests which, to the best of our knowledge, we believe to be dependable. It represents general guidelines only, and the accuracy or completeness thereof, are not guaranteed since conditions of handling and usage are outside our control. The purchaser should determine the suitability of the product for its intended use and assumes all risks and liability whatsoever in connection therewith. The Halar coated concentrate control deluge valve (C) does not require any trim, except for a priming line and water pressure gauge and 3-way valve from the main deluge valve (A) to the priming chamber of valve (C). Plug all the remaining valve trim outlets. Connect Halar coated concentrate control deluge valve (C) priming line to deluge valve (A) as shown on Figures 1 - 3. Refer to the Valves section of this data book to find the correct trim kit part number for the corresponding size of Halar coated foam concentrate control deluge valve (C) required.
SPECIAL NOTES
C. D. E.
G. A strainer is not required in the foam concentrate discharge piping of bladder tank systems per NFPA Standards.
Foam 22e
Figure 1
Foam 22f
Figure 2
Foam 22g
Figure 3
Foam 22h
For complete Deluge Foam/Water System Supplied by Foam Pump, select Deluge Valve and Trim, Release Trim, Foam Concentrate Control Valve and Trim, Foam Concentrate and ILBP Assembly, Controller, and Accessories.
DESCRIPTION NOMINAL SIZE PART NUMBER DATA PAGE NOMINAL PART DATA SIZE NUMBER PAGE Deluge Valves - Straight Through Flange Drilling Model F-1 Painted Red ANSI ANSI ANSI ANSI ANSI/Japan 218 a-j PN10/16 DNPN10/16 DNPN10/16 DNPN10 DNPN16 DNFlange Drilling Model F-2 Halar Coated ANSI 3 12015Q/B ANSI 4 11960Q/B ANSI 6 11962Q/B ANSI 8 11992Q/B PN10/16 DN80 12027Q/B 219 a-k PN10/16 DN100 11966Q/B PN10/16 DN150 11963Q/B PN10 DN200 11996Q/B PN16 DN200 12000Q/B Flange Drilling / Pipe O.D. Model F-1 Painted Red ANSI / 89 mm ANSI / 114 mm ANSI / 168 mm PN10/16 / 89 mm DN218 a-j PN10/16 / 114 mm DNPN10/16 / 165 mm DNPN10/16 / 168 mm DNFlange Drilling / Pipe O.D. Model F-2 Halar Coated ANSI / 89 mm 3 12019Q/B ANSI / 114 mm 4 11959Q/B ANSI / 168 mm 6 11961Q/B PN10/16 / 89 mm DN80 12644Q/B 219 a-k PN10/16 / 114 mm DN100 12645Q/B PN10/16 / 165 mm DN150 12641Q/B PN10/16 / 168 mm DN150 11961Q/B Pipe O.D. Model F-1 Painted Red 48 mm 1 / DN214 a-f 60 mm 2 / DN73 mm 2 / DN76 mm DN89 mm 3 / DN114 mm 4 / DN218 a-j 165 mm DN168 mm 6 / DN219 mm 8 / DNPipe O.D. Model F-2 Halar Coated 48 mm 1 / DN40 12127Q/B 60 mm 2 / DN50 12058Q/B 73 mm 2 / DN65 12404Q/B 76 mm DN80 12730Q/B 89 mm 3 / DN80 12023Q/B 219 a-k 114 mm 4 / DN100 11514Q/B 165 mm DN150 11911Q/B 168 mm 6 / DN150 11525Q/B 219 mm 8 / DN200 11118Q/B DESCRIPTION
Threaded
Flange/ Flange
Flange/ Groove
Deluge Valves - Angle Style Model & Pipe O.D. Model E-mm 1 / DN40 Model E-mm 2 / DN50 Model & Pipe O.D. Model E-mm 1 / DN40 Model E-mm 2 / DN50 Flange Drilling Model E-1 ANSI 3 ANSI 4 ANSI 6 ANSI/Japan 6 PN10/16 DN80 PN10/16 DN100 PN10/16 DN150 Flange Drilling Model E-2 ANSI 3 ANSI 4 ANSI 6 PN10/16 DN80 PN10/16 DN100 PN10/16 DN150 Flange Drilling / Pipe O.D. Model E-1 ANSI / 89 mm 3 ANSI / 114 mm 4 ANSI / 168 mm 6 PN10/16 / 89 mm DN80 PN10/16 / 114 mm DN100 PN10/16 / 168 mm DN150 Flange Drilling / Pipe O.D. Model E-2 ANSI / 89 mm 3 ANSI / 114 mm 4 ANSI / 168 mm 6 PN10/16 / 168 mm DN150
Painted Red a-h 05852C 210 a-h Halar Coated 09890Q/B 212 a-j 08361Q/B 213 a-j Painted Red 05912C 05909C 05906C a-h 08631 Halar Coated 08362Q/B 08363Q/B 08364Q/B 213 a-j 08862Q/B 08863Q/B 08864Q/B Painted Red 05835C 05839C 05456C 211 a-h 05456C Halar Coated 11064Q/B 11065Q/B 213 a-j 11001Q/B 11001Q/B
DESCRIPTION
PART DATA PAGE NUMBER Deluge Valves - Straight Through Pipe O.D. Model F-1 Painted Red NPT 48 mm 214 a-f NPT 60 mm NPT 65 mm 218 a-j BSP 48 mm DNBSP 60 mm DNPipe O.D. Model F-2 Halar Coated NPT 65 mm 2 12402Q/B 219 a-k NOMINAL SIZE
Groove/ Groove
Table 1
Foam 22i
DESCRIPTION NOMINAL SIZE PART NUMBER DATA PAGE MATERIAL PART NUMBER DATA PAGE RELEASE TRIM PACKAGES Pneumatic Release Galvanized b Use with Angle or Brass 10811 Straight Through Electric Release Valves Galvanized a Brass 10832 DESCRIPTION
Deluge Valve Trim Galvanized 1 / DN40 Use with Angle Style Valves 2 / DN/ DN/ DN/ DN/ DN/ DN/ DN65 Horizontal Use with Straight Through Valves Vertical 3 / DN/ DN/ DN/ DN/ DN/ DN/ DN/ DN/ DN/ DN/ DN200 14629-1 14630-1 14631-1 14632-1 14633-1 14635-1 14637-1 14638-1 14640-1 14643-1 14634-1 14636-1 14639-1 14641-1 14643-1 Brass 14629-2 14630-2 14631-2 14632-2 14633-2 14635-2 14637-2 14638-2 14640-2 14643-2 14634-2 14636-2 14639-2 14641-2 14643-a-c 239 e-g 240 a-c 241 a-c 242 a-c 235 e-g 239 e-g 240 e-g 241 a-c 242 e-g 227 a-c 225 a-c 226 a-c
NOMINAL SIZE Trimpac
PART NUMBER
DATA PAGE
Pneumatic Release Galvanized Includes Conventional Trim, Release Trim, and Flexible Hose Kit Brass Galvanized Brass Drain Package 1 / DN/ DN/ DN65 Use with TrimPac (above) 3 / DN/ DN/ DN/ DN200 11894-1 11894-2 11894-3 11894-3 11894-4 11894-4 11894-4 Refer to Trimpac Data Page 13788B-2 13788B-2B Electric Release 137887B-1 13787B-1B 244 a-s 245 a-t
DESCRIPTION Angle Style Threaded NPT Model & Pipe O.D. Model E-mm Model E-mm Pipe O.D. NPT 65 mm Pipe O.D. Groove/ Groove 48 mm 60 mm 73 mm
NOMINAL SIZE
NOMINAL SIZE Galvanized 1 / DN40
FOAM CONCENTRATE CONTROL VALVE HALAR COATED
FOAM CONCENTRATE CONTROL VALVE TRIM 12848-1 12848-1 12929-1 12848-2 12848-2 12929-2 61a-f
1 / DN/ DN50 Model F-Model F-/ DN/ DN/ DN65
09890Q/B 08361Q/B 61a-f 12402Q/B 12127Q/B 12058Q/B 12404Q/B
Use with Angle Style Valve
2 / DN50 Brass 1 / DN/ DN50 Galvanized 1 / DN/ DN50
Straight Through Threaded NPT
Use with Straight Through Valves
2 / DN65 Brass 1 / DN/ DN/ DN65
Table 2
Foam 22j
NOMINAL SIZE 1 / DN/ DN/ DN65
PART NUMBER 99S-0150 99S-0200 05497C
DATA PAGE 803 a-d
Foam CONCENTRATES AND ILBP Assemblies Foam concentrate Description Foam base PART CONCENTRATE NUMBER DATA PAGE ILBP Assembly Nominal Viking PART ILBP DATA size NUMBER PAGE 2 1% AFFF CFa-b F15006/A F15012/A F15018/A F15025/A F15032/A F15006/B F15012/B F15018/B F15025/B F15032/B F15006/C F15012/C F15018/C F15025/C F15032/C F15006/D F15012/D F15018/D F15025/D F15032/D F15006/E F15012/E F15018/E F15025/E F15032/E F15006/J F15012/J F15018/J F15025/J F15032/J F15006/H F15012/H F15018/H F15025/H F15032/H 171 a-d
Foam Concentrate Swing Check Valve
Foam Solution Test Valve 2 / DN/ DN80 Grooved Butterfly Valve 4 / DN/ DN/ DN/ DN/ DN80 Grooved Butterfly Valve 4 / DN/ DN/ DN/ DN/ DN80 OS & Y 4 / DN/ DN/ DN/ DN/ DN50 / DN15 / DN15 / DN15 / DN15 / DN15 01G-0250 01G-0300 01G-0400 01G-0600 01G-0800 01G-0250 01G-0300 01G-0400 01G-0600 01G-0800 8068A-0250 8068A-0300 8068A-0400 8068A-0600 8068A-0800 T595Y66-0150 T595Y66-06555A 03945A 01054A WBV-0150 WBV-0200 8068A-0250 8068A-0300 -
3% AFFF C303
3 Fa-b 3 Fa-b 3 Fa-b 3 Fa-b 8 2
System Isolation Valve 3% AFFF MS C301 MS
Water Supply Control Valve
3% - 6% AFFF @ 3% C363
Foam Concentrate Shut-Off Valve Ball Valve -
ACCESSORIES FOR FOAM/WATER SPRINKLER SYSTEMS Model D-1 PORV 1/8 / 3 mm Restricted Orifice Soft Seat Check Valve Y Strainer Ball Valve 287 a-b -
3% AR-AFFF CUG
3 Fa-b 3 Fa-b 8
2% Hi Ex C2
Concentrate Control Valve Priming Connection Pkg. Required to connect priming chamber Ball Valve Ball Valve OS & Y OS & Y 1 / DN/ DN/ DN/ DN80 foam concentrate shut off Valve
Table 3
Form No. F_011301 Revised page replaces page Foam 22a-j, dated June 1, 2008. (Updated Release Trim and TrimPac Part Nos. in Table 2.)
Tags
D5000 F2-1002 JMR838WFA Al II Bt GPS KRC-678 FC250SW MR314 Avsf 120 SD-T50w1 Guide 42PF7320A 1263turbo Cruiser FP71G- FAX-LAB 650 2405 SGH-J700G Intercept KD-LX330R A6025 C300 Auto Laserjet 1022 Vocal 300 Sims-bustin OUT BA 410 AT3205 RS21hftts Plcxf45 C-4040 Zoom SGH-C260B SGH-C161 TXP50S20E Rome-total WAR QB6120X S4115HII Xbox Live DVD-H1080R NA14VA1 19PFL3403 10 SP-F10M Clock Berlin 7040D Digitech BP80 Review YZ80-2000 - 2000 Streetpilot C310 EX-P700 SA-XR59 115HP-2001 EX-Z65 Finepix F410 MY600V Elna 6005 770E CH I845 KDC-3090RG KX-TG2422 VPC-HD1 DVP-NS999ES SD257WXC UE-32C6710 SHC8525 LN40R81B Alcatel 2412 MDX4400 AFD III SLV-X9N MD-MS722H 9800S HT33S 7 1 PEG-NR70V TL-SL2452WEB AZ1500 LP340B Travelmate-6000 JX20 Pura SX210 IS GDA-700 EL-2630P RX-V861 SDM-HS74P CQ-C3301 UN55B7000 DI620PE Mcintosh C42 FAE1025V CX7310 Voice KDL-46D3500 WF-1060 Aspire E600 Eazygo DVS400H GR-D70E ER3261BNS VDR-D150EF TI-5045SV
manuel d'instructions, Guide de l'utilisateur | Manual de instrucciones, Instrucciones de uso | Bedienungsanleitung, Bedienungsanleitung | Manual de Instruções, guia do usuário | инструкция | návod na použitie, Užívateľská príručka, návod k použití | bruksanvisningen | instrukcja, podręcznik użytkownika | kullanım kılavuzu, Kullanım | kézikönyv, használati útmutató | manuale di istruzioni, istruzioni d'uso | handleiding, gebruikershandleiding