Regin Optigo OP10-230
|
|
Bookmark Regin Optigo OP10-230 |
About Regin Optigo OP10-230Here you can find all about Regin Optigo OP10-230 like manual and other informations. For example: review.
Regin Optigo OP10-230 manual (user guide) is ready to download for free.
On the bottom of page users can write a review. If you own a Regin Optigo OP10-230 please write about it to help other people. [ Report abuse or wrong photo | Share your Regin Optigo OP10-230 photo ]
Manual
Preview of first few manual pages (at low quality). Check before download. Click to enlarge.
Download
(English)Regin Optigo OP10-230, size: 2.9 MB |
Regin Optigo OP10-230
User reviews and opinions
| cpelz |
11:07pm on Monday, November 1st, 2010 ![]() |
| Because my Windows98 vintage HP inkjet finally crapped out I picked up the HL-2170W from Best Buy for $109 yesterday. This is probably one of the easiest printer setups I have ever done. After following the instructions on the included cd. | |
| Lorenzo68 |
7:28pm on Monday, September 20th, 2010 ![]() |
| I got it for my home office, to replace an inkjet that was slow & dried up from infrequent use. This printer was easy to add to our network and has been working very well. Quality product, have not had issues with paper jams and its very quiet. | |
| nicky1 |
3:17am on Wednesday, September 15th, 2010 ![]() |
| I ordered the refurbished model. So far it has been a good printer. Brother is the best for the $. Looked like a great deal for under $100, so I purchased it, after two weeks they refunded my money because UPS lost it, so now if I want it. | |
| collier |
8:45pm on Tuesday, August 24th, 2010 ![]() |
| I found this printer to be a happy medium (for pricing, capabilities and options) between the cheaper and more expensive laser printers. It will lie about the amount of toner left. | |
| smudge |
11:34am on Tuesday, August 17th, 2010 ![]() |
| The Brother HL-2170W Laser Printer is the first LASER PRINTER that I have purchased. I bought it because I wanted to be done with ink expense. | |
| mrotekc |
6:08am on Tuesday, August 17th, 2010 ![]() |
| Good SOHO priner. Wireless is great feature as you can put it anywhere. Compact Design,Easy Setup,Easy To Use,Fast Print Time,Sharp detail | |
| gjwerler |
3:23am on Sunday, July 25th, 2010 ![]() |
| I use this laser for everyday printing and I print maybe 2500 pages per year. I have not owned it long. I have to print out a lot of documents for school, and this printer is great for what I have to do. The detail is very nice, print time is fast. was easy to set up. Used the network cable to set up the desktop pc and hook up the wireless connection to laptop. So far so good. | |
| Hary_mn |
5:26pm on Monday, June 14th, 2010 ![]() |
| Here is how to setup the wireless: This instr... Fast Printer and great print quality Horrible instrctions to setup the wireless I have had this printer about 9 months and I ... This printer is fast. Its toner replacements last a long time and are cheap if you shop online. I go to law school and this printer is great ... Fast, doesnt take up a lot of space, network card could not get wireless to work | |
| DCIN |
4:12pm on Thursday, March 25th, 2010 ![]() |
| Much faster and easy ... installed as network printer in 10 min build quality, compatibility, design, Easy Installation/Good Instructions. | |
Comments posted on www.ps2netdrivers.net are solely the views and opinions of the people posting them and do not necessarily reflect the views or opinions of us.
Documents
O P T I G O
R E A D Y - S T E A D Y - G O
Optigo OP10 Manual
Copyright AB Regin, Sweden, 2010
DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no warranties as regards the contents of this manual and users are requested to report errors, discrepancies or ambiguities to Regin, so that corrections may be made in future editions. The information in this document is subject to change without prior notification. The software described in this document is supplied under license by Regin and may be used or copied only in accordance with the terms of the license. No part of this document may be reproduced or transmitted in any form, in any fashion, electronically or mechanically, without the express, written permission of Regin. COPYRIGHT AB Regin. All rights reserved. TRADEMARKS Optigo is a registered trademark of AB Regin. Some product names mentioned in this document are used for identification purposes only and may be the registered trademarks of their respective companies.
August 2010 Document revision: 2010-08-27
Table of contents
Chapter 1 About the manual
More information
Chapter 2 Introduction to Optigo
Optigo controllers Optigo OP10
Chapter 3 Technical data Chapter 4 Installation and wiring
Installation Wiring Supply voltage Inputs and outputs
Chapter 5 Control modes
Control modes 1, 2 and 3 Control mode 4, Radiator circuit control with outdoor curve Control mode 5
Chapter 6 Display and encoder
The Basic level The 3 second level The 10-second level Display symbols
Chapter 7 Setpoint Chapter 8 Alarm handling Chapter 9 Clock and scheduler
Real time clock Scheduler, general Scheduler, control modes 1, 2 and 3
Menus 0.1 0.8 Menu 0.9, Override Menu OK
Scheduler, control mode 4
Menus 0.1 0.8 Menu 0.9, Setback Menu OK
Chapter 10 Configuration
Menus 1.0 5.0 Menus X.1 Output type (control modes 1, 2, 3 and 4) (where X depends on your choice of alternative above) Menu X.A Menus X.2 Output signals (control modes 1, 2, 3)
Menus X.3 Neutral zone (Control modes 1, 2 and 3) Menus X.4 P-band Menus X.5 I-time Menus X.6 Damper minimum position (Control modes 1, 2 and 3) P-band room temperature influence (control mode 3) 0C temperature boost (Control mode 4) Dfactor (control mode 5) Menus X.7 Universal input UI1 (Control modes 1, 2, 3) Pump exercise (Control mode 4) Periodic overheating (Control mode 5) Menus X.8 Startpoint for outdoor compensation, S.P (Control mode 2) Supply air min limit (Control mode 3) Low temperature setpoint (Control mode 4) Menus X.9 Maximum compensation, CMP (Control mode 2) Supply air max limit (Control mode 3) High temperature setpoint (Control mode 4) Menu X.E Menu I/O Menu OK
Storage of settings Reset to factory setting
Chapter 11 Index
This manual describes the controller Optigo OP10 and OP10-230. It is applicable to program revisions from R20. Make sure that you always follow the safety regulations in the documentation to prevent risk of fire, electric shock and personal injury.
More information on OP10 can be found in: Optigo controllers Sales brochure for Optigo controllers Optigo product instruction
The information is available for download from Regins homepage, www.regin.se.
Optigo OP10 user manual
Optigo controllers
Optigo is a range of pre-programmed, configurable controllers that can be set to handle everything from temperature control or humidity control to CO2 control or pressure control. The Optigo series comprises two different types, OP5 and OP10. OP5 has 5 inputs/outputs and can be configured to control Temperature, CO2, Humidity or Pressure. From revision 18, there is a new analogue input for connection of an external PT1000 setpoint device for control mode 1 (Temperature control). OP10 has 10 inputs/outputs and can be configured to control Temperature (ventilation control with heating and cooling), Water-heated radiator heating with outdoor temperature dependent control-curve or Domestic hot-water control. From revision 20, there is a new analogue input for connection of an external PT1000 setpoint device for control modes 1-4. OP10 is available in two versions, OP10 with 24 V AC supply voltage and OP10-230 with 230 V AC supply voltage. Mounting Optigo is designed primarily for DIN-rail mounting but can also be screw-mounted to any suitable surface.
OP5 and OP10
Optigo OP10
Optigo OP10 is a pre-programmed, configurable controller. It has been designed with the main intention of replacing a number of Regins Aqualine controllers. All configuration and normal handling is done using the display and the knob on the front. Optigo OP10 has Control modes 2 analogue inputs, PTanalogue input for an external setpoint device, PT1000 (from R20) 1 universal input, PT1000 or digital 2 digital inputs 3 digital outputs 2 analogue outputs, 010 V DC
In- and Outputs
Optigo OP10 is pre-programmed with a choice of 5 different control modes: Supply air control Outdoor temperature compensated supply air control Cascade connected room / extract air temperature control Radiator circuit control Domestic hot water control
Internal clock
Optigo OP10 has a built-in week-base real time clock with a number of different scheduler alternatives.
Chapter 3 Technical data
Supply voltage. OP10-230: 230 V AC; +10 / -15%; OP10: 24 V AC; 15%. 50/60 Hz Power consumption....6 VA Running mode Climatic conditions according to IEC 721-3-3... Class 3k5 Ambient temperature... 0.50C Ambient humidity....Max 95% RH Mechanical requirements according to IEC721-3-3...Class 3M3 Vibration... IEC60068-2-6, Test FC, vibration Sinusoidal Shock...IEC60068-2-27, Test Ea Transport Climatic conditions according to IEC 721-3-2... Class 2k3 Ambient temperature... -20.+70C Ambient humidity....Max 95% RH Mechanical requirements according to IEC721-3-2...Class 2M2 Vibration... IEC60068-2-6, Test FC, vibration Sinusoidal Shock...IEC60068-2-27, Test Ea Free fall.... IEC60068-2-27, Test Ed Storage Climatic conditions according to IEC 721-3-1... Class 1k3 Ambient temperature.... -20.+70C Ambient humidity....Max 95% RH Terminals..Disconnectable, lift type for cable cross-section 2.5 mm2 Protection class.... IP00 Material casing... Polycarbonate, PC Colour Cover..... Silver Bottom part....Dark gray Weight... OP10-230: 370g; OP10:215 g incl. terminals Dimensions..122 (7 modules) x 120 x 64 mm (WxHxD incl. terminals) LVD, Low Voltage Directive This product conforms with the requirements of European LVD standard EN61010-1. EMC emissions an immunity standard This product conforms with the requirements of European EMC standards CENELEC EN 61000-6-1 and EN 61000-6-3 and carries the CE mark Inputs AI.... Resolution: 10 bit A/D AI1....PT1000-sensor, range 580C AI2... PT1000-sensor, range -30+50C SPI... PT1000 setpoint device, range 040C UI AI.... PT1000, range 080C or DI... Closing potential-free contact AGND....Reference for AI UI+....Reference for UI DI... Closing potential-free contact DI+....Reference for DI
Outputs AO... 010 V DC; 8 bit D/A short-circuit protected DO1 and DO2 (OP10). Triac controlled, 24 V AC, 0.5 A continuous (connected to G0) DO1 and DO2 (OP10-230). Triac controlled, 24 V AC, 0.16 A continuous with internal trafo.. (connected to G0) DO3... Change-over (SPDT) relay 230 V AC, 1000 VA GDO...Reference for DO1 and DO2. 24 V AC output Other data Display.. Numeric / graphic. Background illumination.
Setpoints
Range Temperature supply air room tap hot water External setpoint P-band I-time D-factor Cascade factor Minimum at cascade Maximum at cascade Damper minimum limit Start of outdoor compensation Outdoor compensation at -20C outdoor temp Supply temperature (water-heated radiator heating) at -20C outdoor temperature at 20C outdoor temperature Frost protection Shutdown mode 10.80C 10.50C 1080C 040C 099C 0990 s 099C 099C 099 -3050C -1010C 099C 099C 7C (fixed) 25C (fixed) Factory setting 21C 21C 55C 15C 60 s 10 10C 5C 60C 20C
Accessories Temperature sensors..PT1000 sensors, for example:TG-R5/PT1000, TG-KH/PT1000 Setpoint device... PT1000, e.g. TG-R4/PT1000 or TBI-PT1000 Casing....EK216 The accessories are available from Regin. For more detailed information, see product sheets and instructions which are available at www.regin.se.
Chapter 4 Installation and wiring
Installation
Optigo is intended to be installed and handled by professional personnel. The installation should conform to the requirements of installation category 3 and pollution degree 2. There are a number of mounting alternatives: DIN-standard casing (minimum 7 modules) Cabinet, either on a DIN-rail or, using the two screw-pockets provided, by being screwed to any suitable flat surface in the cabinet The controller can also be mounted in a cabinet door or other control panel, using a suitable front-mounting kit Observe that there is a risk of electric shock on contact with terminals 1-3 and 10-12. Mount Optigo in a DIN-casing or similar where it can be used without risk of electric shock. The casing should provide at least 6 mm insulation from connected cables and terminals 1-3 and 10-12. Optigo should be protected against overload by a fuse in the installation. Since the maximum load is 1000 VA, a fuse of 6 A is suitable. Circuit breaker and fuse: The controller should be connected to a circuit breaker so the power supply to the controller can be cut. Place this breaker close to the controller where it is easy for the operator to reach. It should be clearly marked as a circuit breaker for the controller.
For installations which are connected to 230 V AC: -
Wiring
This section only describes general rules and technical limitations concerning the wiring. In chapter 5 there are specific wiring diagrams for the different control modes. Choose the one suitable for the application on hand. It is important to make sure that the wiring is correctly done, in accordance with the instructions given in this manual and in accordance with local legislation for this type of installation.
Supply voltage
OP10-230: 230 V AC +10%, -15%, 50/60 Hz. 6 VA OP10: 24 V AC 15%, 50/60 Hz. 6 VA If the Optigo OP10 (24V supply model only) and actuators connected to it share transformer, it is essential that the same transformer-pole is used as reference for all the equipment. Failure to do so will prevent the equipment from functioning as intended and may also lead to damages.
Inputs and outputs
All AGND terminals are interconnected and also connected to G0.
Analogue inputs AI
The analogue inputs must refer to an AGND terminal. AI1 and AI2 are for PT1000 temperature sensors only. AI1 has a temperature range of 084C. AI2 has a temperature range of -30+54C. SPI is only intended for a PT1000 setpoint device, the range is 0.40C.
Digital inputs DI
The digital inputs must refer to DI+ on terminal 41. The digital inputs may only be wired to voltage-free contacts. Any external voltage applied to a digital input may harm the unit.
Universal input UI
The universal input can, depending on the choice of application, be made to act as either an analogue input or as a digital input. When used as an analogue input it is for PT1000 temperature sensors. The input then has a range of 0+84C UI must refer to UI+ on terminal 43.
Analogue outputs
Analogue outputs must refer to a AGND terminal or directly to G0. If the Optigo OP10 (24V supply model only) and actuators connected to it share transformer, it is essential that the same transformer-pole is used as reference for all the equipment. Failure to do so will prevent the equipment from functioning as intended and may also lead to damages.
Digital outputs
The two digital outputs DO1 (terminal 14) and DO2 (terminal 15) are triac controlled. The triacs are internally connected to G0. Each triac can handle 24 V AC, 500 mA. The outputs cannot be used to drive DC relays. When DO1 and DO2 are used for 3-point control DO1 will always be increase signal (open valve) and DO2 always decrease signal (close valve) The outputs should normally refer to GDO on terminal 13. GDO is internally connected to G and supplies 24 V AC. In OP10 GDO can deliver the necessary 2 x 500 mA.
13 GDO G0 G0
In OP10-230 however, the internal transformers capacity restricts the current on GDO to approx. 165 mA. For more power an external transformer must be used. Wire the transformer according to the following figure. The two 500 mA fuses are important to prevent possible overloading of the triacs.
13 GDO 14 G0 G0 Agnd 15 20
500mA 24 V AC
230 V AC
Optigo can be configured to any one of the following control modes.
1. Supply air temperature control. The supply air temperature is kept at the setpoint value by controlling the output signals on AO1 and AO2. A single PI control loop is used.
2. Supply air temperature control with outdoor compensation. The supply air temperature is kept at the setpoint value by controlling the output signals on AO1 and AO2. A single PI control loop is used. The setpoint is automatically adjusted according to the outdoor temperature.
3. Cascade connected, room temperature influenced, supply air control. The room temperature is controlled by means of adjustments in the supply air temperature, depending on the room temperature. A cascade controller with a room temperature and supply air temperature sensor is used. The supply air temperature is minimum and maximum limited.
4. Radiator circuit control with outdoor curve. The water temperature setpoint is changed according to the outdoor temperature. A single PI control loop is used. A room temperature sensor can be added to give corrective action if the room temperature differs from the setpoint
5. Domestic hot water control. The water temperature is kept constant by controlling the output signal on AO1. A single PID control loop is used.
Control modes 1, 2 and 3
These three modes have a lot in common and will therefore be treated in a single section. For control mode 1, Supply air temperature control you need only one sensor,Supply air sensor on AI1.
For control mode 2, Supply air temperature control with outdoor compensation you need two sensors, Supply air sensor on AI1 and Outdoor sensor on AI2.
For control mode 3, Cascade connected room / extract air temperature control you also need 2 sensors, Supply air sensor on AI1 and Room sensor, which are placed in the room or in the extract air on AI2. The cascade controller has inputs for supply air sensors and room sensors. The room temperature setpoint is set and the controller will adjust the supply air setpoint until reaching the desired room temperature. The supply air setpoint is minimum and maximum limited. The P-band and I-time values for the supply air control are chosen so that a stable control is achieved. The P-band for the room temperature influence is set on PCd. The I-time for the room temperature influence is a fixed value of 600 seconds. Definition of P-band the room temperature influence (PCd): The change in room temperature which results in a change in the supply air setpoint, corresponding to the difference in temperature between the set maximum and the minimum limits.
The analogue outputs can be configured to the following combinations:
1. Heating 2. Cooling 3. Heating 4. Heating 5. Cooling 6. Heating 7. Cooling
/ Cooling / Heating / Cooling / Dampers / Dampers
In alternative 4, Heating-Heating AO2 will be activated first on increasing heat demand. In alternative 5, Cooling-Cooling AO2 will be activated first on increasing cooling cemand. In alternative 6, Heating-Damper, at temperatures above the setpoint the damper on AO2 will be fully open. On increasing heating demand, the damper on AO2 will first close to the set minimum value before the heating output on AO1 starts to increase. In alternative 7, Cooling-Damper, at temperatures below the setpoint the damper on AO2 will be fully open. On increasing cooling demand, the damper on AO2 will first close to the set minimum value before the cooling output on AO1 starts to increase.
3-position control
Instead of an analogue output you can configure a single 3-position (increase / decrease) output. You will then only have the following output choices: Heating Cooling DO1 is used for increase signal and DO2 for decrease. This option cannot be combined with alarm output. A single P control loop is used. OP10-230 generates 24 V AC itself for control of 3-position actuators. 230 V actuators cannot be used without relays.
External setpoint
From revision 20, it is possible to use an external PT1000 setpoint device, e.g. TG-R4/PT1000 or TBI-PT1000. The setpoint device is connected between terminal 54 SPI and the reference for the analogue inputs, AGND. For more information on configuration and setpoint reading, see chapters 7 and 10.
Universal input UI1
Electric heating If the Optigo is used to control electric heating UI1 is used for the high temperature limit switch. Connect and configure as a digital input. The input is normally closed. Whenever the running mode switches to Off, (normal shutdown) the heating output will be shut down immediately but the fan will run on for a further 3 minutes to cool the heater. On activation of the high temperature limit, the heating output will be shut down immediately and there will be no cool-down period.
Relay el. heating
Control voltage
High limit thermostat Contr. voltage Auxilliary relay
Optigo
Wiring suggestion for high temp limit when using electric heating. Drawn with high temp limit activated.
N.B. It is important that the high temperature thermostat is hardwired to disconnect the power to the heater to ensure that the heating is shut down when the thermostat is activated even if the Optigo should be faulty.
Water heating When controlling a water heater, UI1 can, when necessary, be used for a frost protection sensor. Connect and configure as an analogue input. The frost protection function can be tied to either of the analogue outputs. The heater return water temperature is monitored by the frost protection sensor. Should the temperature at the frost protection sensor fall below 12C an internal, proportional signal is generated that is used to force the heating valve open to try and prevent freeze-up of the heater. Optigo OP10 user manual Chapter 5 Control modes 16
Internal signal Prop.band 100 %
0% 7C 12C
The frost protection signal (Internal signal) will increase linearly to 100 % at 7C at which point the frost protection alarm is triggered. The fan will then be shut down and the controller will go into shutdown mode.
Shutdown mode (Only if frost protection sensor has been configured) Whenever the running mode switches to Off, (normal shut-down or frost protection is activated) the controller will go into Shutdown mode. The shutdown controller will control the output that is tied to the frost protection function to maintain a constant 25C at the frost protection sensor.
Outdoor compensation
In control mode 2, Supply air control with outdoor temperature compensation, the supply air temperature setpoint can be displaced according to outdoor temperature. The displacement starts from outdoor temperature S.P and reaches the setpoint value + the compensation (CMP) at -20C outdoor temperature. For example: Normal setpoint = 20, S.P=10 and CMP = 5 will give the following result:
Setpoint
Setpoint + CM 25C P Setpoint 20C -20C 10C S. P Outdoor temp
Damper
It is possible to set a minimum limit value to the damper output signal. The damper-output will then not go lower than the set value during normal operation. On shut-down however the signal will go to zero. In the output mode heating damper the damper will be fully open for temperatures higher than the setpoint. On increasing heat demand the damper will first close to the minimum value before the heating output starts to increase. In the output mode cooling damper the damper will be fully open for temperatures lower than the setpoint. On increasing cooling demand the damper will first close to the minimum value before the cooling output starts to increase.
DI1, Fan indication
Unless the fan indication input is active (closed) indicating that the fan is running, the controller will not start normal temperature control and an alarm will be generated. An alarm will also be generated if the input is active (closed) when the fan control output is off.
DI2, Extended running
Activation of this input will force the controller to running mode even if internal scheduler is in Off-mode. The unit will run as long as the input is activated.
Wiring examples
See also chapter 4 Installation and wiring.
A. OP10 with electric heating (for example via PULSER-X/D or TTC25X) and damper. Cascade control.
B. OP10-230 with water heating, 3-position output. Supply air temperature control with outdoor compensation and external setpoint device. OP10-230 generates 24V AC itself for control of 3-position actuators. 230 V actuators cannot be used without relays.
Control mode 4, Radiator circuit control with outdoor curve
For this control mode you need two sensors, GT1 Supply temperature on AI1 and GT2 Outdoor sensor on AI2. You can also have a room temperature sensor on UI1 to let the room temperature offset give correction to the supply temperature. Wire UI1 as an analogue input. When using a room sensor, it is possible to set the room setpoint via an external PT1000 setpoint device (this applies to controllers with revision R20 or later).
Instead of the analogue output you can configure a 3-position (increase / decrease) output using DO1 and DO2. DO1 is used for increase signal and DO2 for decrease. This option cannot be combined with alarm output. A single P control loop is used. OP10-230 generates 24V AC itself for control of 3-position actuators. 230 V actuators cannot be used without relays.
Control curve
The supply temperature setpoint is determined by a outdoor temperature/supply temperature curve. The basic control curve is a straight line between the two setpoints SPL and SPH where SPL is the supply temperature to be held when the outdoor temperature is +20C and SPH is the temperature to be held at an outdoor temperature of -20C. An extra temperature boost can be added at 0C outdoor temperature. The boost receeds from the set value to 0 over 3 degrees. In the Setpoint menu a parallel displacement of the whole curve can be added.
OP10 with 0.10V actuator
All setting and configuration is done using the display and encoder. The menu information on the display is organised in a tree fashion. Using the encoder you can move between menus, set values etc. In any of the configuration menus, a click on the encoder will activate change mode. You can then rotate the encoder button to move between choices or set values. A second click of the button will accept the choice. The menu system is divided into three levels: The Basic level, the 3-second level which contains the clock and scheduler settings and the 10-second level which contains all the configuration menus.
The Basic level
The Basic level comprises four sets of menu displays, the Base Display, the I/O Displays, the alarm handling display and the Setpoint Display.
Base Display
This is an example of the Base Display, the display that is normally shown when there is no operator activity. It shows the current time and the actual value of the main parameter. There are bar-graphs showing the current output levels together with symbols showing how the outputs have been configured (Heating, Cooling or damper etc). Also a symbol showing which of the five control modes is configured and an alarm symbol that is displayed in the event of an alarm condition. The fan symbol (control modes 1, 2 and 3 only) is lit as long as the fan indication input is activated.
When the Base Display is shown, by twisting the knob counter clockwise until the text I/O is displayed and then clicking on it, you can gain access to a menu where you can look at the values and states of all inputs and outputs. To exit this menu again, click on the knob and then twist the knob clockwise and you will be returned to the Base display.
When in the Base Display, a click on the encoder button gives direct access to the Setpoint menu. See chapter 7 Setpoint.
If there are any active alarms, clicking on the encoder button will instead give access to the alarm handling menus. Here the alarms are displayed and can be acknowledged. There is one menu display for each alarm with symbols showing which type of alarm it is. See chapter 8 Alarm handling.
Calculated setpoint
For control modes with outdoor temperature compensation or cascade control, the controller does not work towards a fixed setpoint value. Instead, it works towards a calculated setpoint, which varies with the outdoor temperature or, when using cascade control, the room temperature. The calculated setpoint is displayed by turning the knob clockwise when in the Base Display.
Scheduler, general
The scheduler function is only available for control modes 1, 2, 3 and 4. The easiest way to understand the scheduler function is to compare it to the type of mechanical timer that has a rotating disk where you can pull out knobs that on passing the switch kan turn it ON or OFF. There are 4 ON-points and 4 OFF-points. Each point has its own menupage where 0.1, 0.3, 0.5 and 0.7 are ON-points and 0.2, 0.4, 0.6 and 0.8 are OFFpoints. Control modes 1, 2 and 3 have the same type of scheduler where the ON-points will start the unit and the OFF-points will shut it down. Control mode 4 uses the scheduler for switching to economy mode (ECO) where the temperature is lowered by a settable number of degrees. Here the ON-points will switch ECOnomy period on and the OFF-points will switch back to comfort temperature.
Scheduler, control modes 1, 2 and 3 Menus 0.1 0.8
With the 4 pairs of on-off menus you can create 4 different running periods, either for single days or for a group of days. The day of the week number can be set to any value 1 to 9 or -- for unused menus. Numbers 1 to 7 represent the days of the week Monday to Sunday. Number 8 will apply the set time every day Monday through Friday and number 9 will apply the set time all 7 days of the week. Optigo OP10 user manual Chapter 9 Clock and scheduler 27
For example, you wish the unit to run Monday to Friday between 07:30 and 18:00, Saturday 8:00 to 14:00. Set first on-time to day 8 and 7:30, the first off-time to day 8 and 18:00. Set the second ontime to day 6 and 8:00 and the second off-time to day 6 and 14:00. Set all others to day --.
If you want the unit to run around the clock, set the on-time to 0:00 and the off-time to 0:00.
Menu 0.9, Override
After the eight switching point menus there is a ninth, 0.9. There the present output status of the scheduler is shown and you can manually override the setting. If, for example, the switch is shown as ON and you change it to OFF it will remain off either until you manually change it to On again or until the next timer ON-point is reached.
Menu OK
After the scheduler menus there is a final menu, OK. A klick on the encoder knob will exit the Clock and Scheduler level and return you to the Basic Display.
Scheduler, control mode 4 Menus 0.1 0.8
With the 4 pairs of on-off menus you can create 4 different economy periods, either for single days or for a group of days. The day of the week number can be set to any value 1 to 9 or -- for unused menus. Numbers 1 to 7 represent the days of the week Monday to Sunday. Number 8 will apply the set time every day Monday through Friday and number 9 will apply the set time all 7 days of the week. In this application you need to remember that ON will switch ECOnomy period (lowered temperature) on and OFF will switch ECOnomy period off. For example, every weekday morning you want the temperature to start rising at 06:00 and to remain at comfort level until 21:00. On Saturday and Sunday you want high temperature from 07:00 to 23:30. Set first on-time to day 8 and 21:00, the first off-time to day 8 and 06:00. Set the second ontime to day 6 and 23:30 and the second off-time to day 6 and 07:00. Set the third on-time to day 7 and 23:30 and the third off-time to day 7 and 07:00.
0C temperature boost
In control mode 4 an extra temperature boost can be added at 0C outdoor temperature. The boost recedes from the set value to 0 over 3 degrees.
D-factor
Control mode 5, Domestic hot water temperature control is often a very difficult application which calls for responsive control. Optigo therefore utilises PID-control for this control mode. In this menu you set the D-factor (the derivative factor).
Menus X.7 Universal input UI1 (Control modes 1, 2, 3) Pump exercise (Control mode 4) Periodic overheating (Control mode 5)
Input UI1
For control modes 1, 2 and 3 you can choose to configure the universal input UI1 as either an analogue input for a frost protection sensor on either output (snowflake-symbol) in a waterheated system or as a digital input for a high temperature limiting switch (sun-symbol) in an electric heater. It can also be set to --, not active. If set to frost protection sensor Optigo will activate the frost protection function and also shutdown mode, see chapter 5. If set to high temperature limit switch, the fan will run for an extra 3 minutes after the heating output has been turned off at shutdown.
Frost protection on AO1
Frost protection on AO2
High temp. limit switch
Not used
Pump exercise
If the pump stands still for prolonged periods during the summer there is the risk of the pump impeller seizing. To reduce this risk the Optigo has a pump exercise function which will start and run the pump for 5 minutes at 15:00 each day. In this menu the exercise function can be turned Off if not desired. Default is On.
To reduce the risk of Legionella bacteria growth a periodic overheating of the water can be configured. The water temperature will be raised to 65C once daily at 03:00 (3 am). The elevated temperature is maintained for 10 minutes. In this menu the overheating function can be turned Off if not desired. Default is On.
Menus X.8 Startpoint for outdoor compensation, S.P (Control mode 2) Supply air min limit (Control mode 3) Low temperature setpoint (Control mode 4)
For control mode 2. S.P is the outdoor temperature at which the setpoint compensation starts. At temperatures lower than S.P a compensation will be added to the setpoint value. The maximum compensation is set in menu 2.9 and is achieved at -20C
For control mode 3 the supply air temperature can be minimum and maximum limited. In this menu you set the minimum supply air temperature.
For control mode 4 you need to establish a relationship between outdoor temperature and supply water temperature. This is set by the two setpoints SPL and SPH where SPL is the water temperature to be held at an outdoor temperature of +20C and SPH is the water temperature to be held at -20C. Intermediate values are calculated with linear interpolation. In this menu you set SPL.
Menus X.9 Maximum compensation, CMP (Control mode 2) Supply air max limit (Control mode 3) High temperature setpoint (Control mode 4)
For control mode 2. The maximum setpoint compensation value. Compensation will start to be added to the setpoint value when the outdoor temperature falls below the start point S.P entered in menu 2.8. The compensation will increase linearily up to the maximum value CMP which is reached when the outdoor temperature has fallen to -20C
For control mode 3 the supply air temperature can be minimum and maximum limited. In this menu you set the maximum supply air temperature.
For control mode 4 you need to establish a relationship between outdoor temperature and supply water temperature. This is set by the two setpoints SPL and SPH where SPL is the water temperature to be held at an outdoor temperature of +20C and SPH is the water temperature to be held at -20C. Intermediate values are calculated with linear interpolation. In this menu you set SPH.
Menu X.E
In this meny, you set whether you want to use an external setpoint device or set the setpoint via the display. External setpoint can be used for control modes 1-3 and control mode 4 when using a room sensor. This menu is only available for controllers with revision number R20 or later.
Menu I/O
After the last configuration menus there is a menu where you can look at the actual values of all the inputs and outputs.
Last of the configuration level menus is the OK-menu. To leave the configuration level, go to this menu and klick on the encoder knob.
On exit from the configuration level you will not be returned to the Basic level but to the Time and Scheduler level. There is also a time-out function that will automatically exit the configuration level after 5 minutes of inaction.
Storage of settings
All configuration settings become valid as soon as they are entered by clicking the encoder knob. They are however not written to the flash memory until you exit the configuration level either via the OK menu or via the time-out function. To exit the configuration level without saving the changes to flash memory, cut the supply voltage when still in the configuration level. All values will be kept as they were before you entered the configuration level.
Reset to factory setting
The OP10 can be reset to factory settings by configuring Domestic hot water control (mode 5) and setting the D-factor to 99. Go to the Basic Display. Then cut the power supply. When power is reapplied all configuration and scheduler settings will be reset to factory setting.
10-second level.. 23, 30
Factory settings, reset to..36 Fan indication...17
3-second level.. 23, 27
Inputs and outputs..7, 12 Analogue inputs..12 Analogue outputs..12 Digital inputs...12 Universal inputs..12 Installation...10
Analogue inputs.. 12 Analogue outputs.. 12
Basic level... 22
LVD....8
Clock... 27 Configuration... 30 Configuration level.. 23 Control modes.. 7 Domestic hot water control. 21 Radiator circuit control.. 19 Temperature control.. 14
Menu Configuration..30 I/O...22, 36 OK..28, 29, 36 Setback..29 Setpoint..23, 25 X.E...35 Mounting...6
Damper... 17 Digital inputs.. 12 Display and encoder... 22 Domestic hot water overheating.. 34
Outdoor compensation..17 Overheating...34 Override...28
EMC.... 8 Extended running.. 18
Pump exercise..34
Scheduler...27 Optigo OP10 user manual Chapter 11 Index 37
Scheduler override..28 Setback...29 Setpoint...25 Shutdown mode...17
Universal inputs.. 12
Technical data..8 Inputs..8 Outputs...9
Wiring.. 11 Wiring diagram Control mode 4.. 20 Control mode 5.. 21 general.. 11
R E G I N
C H A L L E N G E R
B U I L D I N G
A U T O M A T I O N
AB Regin
Head office
Box 116, S-Kllered, Sweden Phone: +00 Fax: +50 info@regin.se www.regin.se
Germany
RICCIUS + SOHN GmbH
Haynauer Str. 49 D-12249 Berlin Phone: +40 info@riccius-sohn.eu www.riccius-sohn.eu
France
Regin Controls SARL
32 rue Delizy F-93500 Pantin Phone: +info@regin.fr www.regin.fr
Regin Ibrica, S.A.
C/Arganda 18 local E-28005 Madrid Phone: +65 info@regin.es www.reginiberica.com
Singapore
Regin Controls Asia Pacific Pte Ltd
66 Tannery Lane # 03-04 Sindo Building Singapore 347805 Phone: +8233 info@regin.com.sg www.regin.com.sg
Hong Kong
Regin Controls Hong Kong Ltd
Room 2901 EW International Tower 120 Texaco Road Tsuen Wan, NT Hong Kong Phone: +0281 info@regin.com.hk www.regin.com.hk
R E G I N
C H A L L E N G E R
B U I L D I N G
A U T O M A T I O N
Optigo - Compact, economic and versatile stand-alone controller
The Optigo line represents a range of compact, reliable and cost-efficient stand-alone controllers for control of temperature, CO2, pressure, humidity and domestic hot water. Optigo is extremely easy to install, set-up and control and is mainly intended for smaller applications.
The timer handles for example night set-back, start or stop of fans during weekdays or during a day.
Quick and simple installation
Optigo is suitable for DIN-rail or cabinet mounting. Since the terminals are detachable, all connections can be made before Optigo is installed.
Operated with just a knob
Optigo has a knob with an encoder which makes the menu system very easy to use. You can read and set values shown in the back-lit display. A value is approved by pressing the knob.
Display information
Outdoor compensation configured Temperature control Menu holds changable values Active 010V input signal Change over Configuration level Menu number AO1 Graphic output signal Control mode 1 only Bargraph AO1 output level Bargraph AO2 output level AO2 Graphic output signal Control mode 1 only
TURN: Move up/down in the menus CLICK: Enter new menus or accept new setting PRESS 10 SEC: Enter the configuration menus
Chapter 2
Page 81
Applications Optigo 5
1. Temperature control
Applications Optigo 10
1. Supply temperature control
2. Humidity control
2. Outdoor compensated supply temperature control
3. CO2 control
3. Cascade temperature control
4. Pressure control
4. Heating control
5. Outdoor compensated pressure control
5. Domestic hot water control
Page 82
Chapter 2
Optigo - The controller for simple applications
Optigo represents a range of pre-programmed, configurable controllers intended for DIN-mounting. They can be set to handle applications like temperature control, humidity control, CO2 control, pressure control or domestic hot water control. Optigo has a knob with an encoder which makes the menu system very easy to use. You can read and set values shown in the back-lit display. A value is approved by pressing the knob. Optigo is suitable for DIN-rail or cabinet mounting. The terminals are detachable, which makes it possible to prewire before installation.
Display with language independent symbols Easy to configure Numeric/graphic display withbackground illumination Pre-loaded with several application nodes Simple handling with puch-/ turn knob
Optigo OP5
Optigo OP10
Supply voltage: 24 V AC
Optigo OP10-230
Supply voltage: 230 V AC
Control alternatives:
Temperature control CO2 control Humidity control Pressure control Pressure control with outdoor compensation
Supply air control Supply air control with outdoor compensation Extract air/room control with cascade function Radiator control with outdoor compensation Domestic hot water control
Functions as in OP10.
Functions:
Settable P and I values Selectable output signals for heating and/ or cooling (temperature control) Adjustable setting ranges for different sensors Changeover function (temperature control)
Air handling Minimum limit for dampers Start and stop of fans Frost protection regulation with heat retention Input for overheating protection from a heater 3-point or 010 V DC control Selectable output signals for heating and/ or cooling with/without damper control Alarm Frost protection/Overheating/Sensor error/Fan Indication Run indication from fans Built-in week-scheduler Input for extended running
Radiator systems
Night set-back of the setpoint for radiator control Pump stop and pump exercise Outdoor compensated supply temperature control with settable additional compensation of the curve at 0C outdoor temperature
Domestic hot water systems
PID control Periodical overheating of domestic hot water Prevents growth of Legionella bacteria
Page 83
Technical data Supply voltage Power consumption Ambient temperature Storage temperature Ambient humidity Mounting Protection class Display Dimensions Clock Inputs Analogue inputs, AI Digital inputs, DI Universal input, UI Outputs Analogue outputs Digital outputs (OP10 and OP10-230 only) 0.10 V DC, short-circuit protected Triac 24 V AC, 0.5 A (3-point control or alarm output) and one change-over relay 230 V AC, 5 A (fan start) OP10 I/O 10 Type OP5 OP10 OP10-230 OP10-10 Notes PT1000 Potential free closure Either 0.10 V DC or digital 24 V AC +/- 15% or 230 V AC (OP10-230 only) 4 VA 0.50C -40.+50C Max 90% RH DIN-rail mounting, 7 modules IP20 Backlit LCD, numeric/graphic 123x123x60 (WxHxD), 7 modules Week based 24 hour clock (OP10 only)
Model Overview AI DI UI AO DO Total I/O Description Controller Controller Controller
OP5 Supply voltage 24 V AC 24 V AC 230 V AC
See also the front mounting kit (e.g. FMCO) for DIN-rail mounting of controllers, displays and other devices from the Regin product range.
Page 84
Tags
Sagem D15V PMP518M PIN 570 Touch 332 IDL556 Navigator 3 F601 Zoom LN32B450 42LG7000 AEU 836 XA RZ67PRO T4543N1 Scenic 860 Travelmate 4720 DI 2010 LV989 DT1350-P Pocket PC LE40C652l2W CDX-4180 VSX-511S DPS16 Dvrk687X R4000 Premier 3 Justy NP-N145P QCE531K LT-26DX7BJ GM-X374 Rally CDX-E100 61-361 22fbst 705CD Ultra TXP42GT20E CD-5001 HTR-5230 Optio W30 Modus Waters TV USB YP-U3AB Verification CDX-GT300EE US2-PM335 Auto Lumi TX-26LE7F 32PFL7862D 10 TU911 T4020 TRF-7150 HP188F4LK IC-245E Sportview GT-S5550 Audiogram6 LBP2900 CS6229-2 21PT4475 EB-X400 IC-F3GS Maestro 4050 Minikit MM-B7 P5N-D RCS-3535C2 WPN802 HDR-CX370E Express Review Satelis 125 Bizhub C30P PV-GS70D Pv-dv102 LS-S1260HL VP-DC171WI 630 530 LP420 Rrus591 Favorit65450VI ZSF6161 Solutions PT-1750 KRF-V5570D N3260W Eight 1993 Digital PK Death LE40A656 676 Thunderbird-1996 Monitor 3311 EXR-40OR Wisl10 LH-C6230 DV-SP404 CDX-T67 Murano KX-TG2432 Dolmar 115
manuel d'instructions, Guide de l'utilisateur | Manual de instrucciones, Instrucciones de uso | Bedienungsanleitung, Bedienungsanleitung | Manual de Instruções, guia do usuário | инструкция | návod na použitie, Užívateľská príručka, návod k použití | bruksanvisningen | instrukcja, podręcznik użytkownika | kullanım kılavuzu, Kullanım | kézikönyv, használati útmutató | manuale di istruzioni, istruzioni d'uso | handleiding, gebruikershandleiding
Sitemap
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101




