Texecom Veritas R8 Plus
About Texecom Veritas R8 PlusHere you can find all about Texecom Veritas R8 Plus like manual and other informations. For example: review.
Texecom Veritas R8 Plus manual (user guide) is ready to download for free.
On the bottom of page users can write a review. If you own a Texecom Veritas R8 Plus please write about it to help other people. [ Report abuse or wrong photo | Share your Texecom Veritas R8 Plus photo ]
Manual
Preview of first few manual pages (at low quality). Check before download. Click to enlarge.
Download
(French)Texecom Veritas R8 Plus, size: 146 KB |
Texecom Veritas R8 Plus
User reviews and opinions
| muckster |
2:09am on Monday, August 30th, 2010 ![]() |
| I like sports. This audi. Cars, never seems to audi, but over the years audi never visited this field. Now. | |
| lobianco |
8:09pm on Thursday, July 22nd, 2010 ![]() |
| Contrary to you editor we found the seats exa... A buddy and me rented the R8 at Frankfurt Airport 4 months There are no cons. | |
Comments posted on www.ps2netdrivers.net are solely the views and opinions of the people posting them and do not necessarily reflect the views or opinions of us.
Documents

THANK YOU FOR VOTING TEXECOM
USER GUIDE
Security Control Panels
User Guide Summary
User Guide
Full Set Part Set User Guide Summary Enter Your Code Press Full Enter Your Code Press Part Set Number Press Part Enter Your Code Enter Your Code Press Full or (Part Set No &) Part Press Omit Press Zone Number(s) Press Prog Enter Your Code Press Reset Enter Your Code Press Chime Press Zone Number(s) Press Prog Press Chime Enter Your Code Press Prog Enter 05 Press 3 (Internal Sounder) Press 2 (Strobe) Press 1 (Bell) Press Reset Press Reset Enter Your Code Press Prog Enter 06 Conduct Walk Test Press Reset Press Reset Enter Existing Code Press Prog Press 60 Enter New Code Press Prog Press Reset
Unset Omit Zones
Reset Chime Zones
Chime On/Off Test Sounders & Strobe
Walk Test
!!!! " !!!! #, $, % or & ' !!!! !!!! " or !' ( ! ) !!!! * !!!! + ! ) + !!!! ) ,% $ # * * !!!! ) ,.
Conduct Walk Test
Change Code
* * !!!! )., !!!! ) *
INS046-8
Setting the System
If any zones are left open (e.g. a door ajar) or are in fault the display will illuminate the zone light of these zones and sound a repeating series of bleeps corresponding to the zone number (i.e. Zone 1 bleeps once, Zone 2 bleeps twice, etc.). If more than one zone is open the bleeps will correspond to the highest zone number (i.e. if Zone 2 and Zone 6 are open the control panel will bleep 6 times). While one or more zones are open the exit timer is suspended. Open zones that will be closed during exit (e.g. exit zones, like the front door) may be disregarded. Other open zones should be closed. The exit tone and exit timer will resume when all zones are closed. If it is necessary to leave a zone open then it must be omitted (see To OMIT Zones During Setting below). If an open zone cannot be closed then it may be in fault. If the fault cannot be corrected contact your alarm company.
Your Installer can program the system so that it can be set using the " or ' keys without the need to first enter a User code.
To FULL Set the System Ensure all zones are closed (e.g. windows and doors). Enter your 4 digit code !!!!. The Unset light will flash. Press ". The exit tone will sound. Leave the premises. When the system has set the exit tone will stop. To PART Set the System Ensure all zones in the intended Part Set area are closed. Enter your 4 digit code !!!!. The Unset light will flash. Press the number of the required Part Set Suite #, $, % or &. Press '. The quiet exit tone will sound. Leave the protected area. When the system has set the exit tone will stop.
1. If Part Set Suite 1 is desired then it is NOT necessary to press # before pressing '. 2. After entering your code the Unset light will flash indicating the control panel is ready to accept a command (e.g. " or '). If no valid command is entered the system will revert to unset after 16 seconds. 3. Excluded zones (whether from part set or manual omit) that are closed will flash during the exit period. 3
To UNSET the System
Enter via a designated entry route. The slow entry tone will start. Enter your 4 digit code !!!!. The system will unset and the entry tone will stop.
During the last 10 seconds of the entry period the entry tone will change from slow to fast.
To OMIT Zones During Setting
It is possible to exclude (omit) or include individual zones during setting. Enter your 4 digit code !!!!. Press " or enter Part Set Suite number #, $, % or & and press '. Press (. The exit tone and exit timer will stop and the display will illuminate the zones that are about to be armed. Press the appropriate numbered button(s) ! of the zone(s) to be omitted or included. Press ) to complete the omitting procedure. The system will revert to exit mode. The exit tone and exit timer will restart.
1. The system may be programmed so that some zones cannot be omitted. 2. The system will automatically revert to exit mode 16 seconds after the last key is pressed. 3. Whilst omitting, included zones that are in fault are indicated by flashing. 4. Omitted zones that are not in fault flash during the exit period. If a zone is illuminated but the system sounds the exit tone (as opposed to an error tone) then the open zone is omitted.
To Set the System With a Power Fault Enter your 4 digit code !!!!. Press " or enter Part Set Suite number #, $, % or & and press '. The system will sound a repeating series of 10 bleeps. Press (. The display will illuminate the zones that are about to be armed. Press ,. The Power light will turn off. Press ). The exit tone and exit timer will restart.
To RESET During an Alarm Activation
To silence the alarm enter your 4 digit code !!!!. The internal and external sounders will stop but the external strobe will continue to flash. The display will flash the zone light of the zone which first caused the alarm activation and illuminate the zone lights of all subsequently opened zones (if any). To cancel the display and stop the external strobe press *. The system will chime and return to unset.
To RESET After an Alarm Activation
After an alarm activation the internal and external sounders will stop after a pre-set time. The system will re-arm but the external strobe will continue to flash. Enter via a designated entry route. The entry tone will start. Enter your 4 digit code !!!!. The system will unset and the entry tone will stop. The display will flash the zone light of the zone which first caused the alarm activation and illuminate the zone lights of all subsequently opened zones (if any). To cancel the display and stop the external strobe press *. The system will chime and return to unset.
If the System Requires an Anti-Code After an Alarm Activation
The system may be programmed to require an Anti-Code after an alarm activation. You will still be able to silence the alarm by entering your code as normal. However you will not be able to reset the system without first obtaining the Anti-Code. The zone lights will display a random 4 digit sequence. They will flash each digit in turn and then pause before repeating. Contact the phone number on the last page with this sequence in order to obtain a 4 digit Anti-Code which will allow the system to be reset.
To display the zone(s) which caused the alarm press *. The zone light of the zone which first caused the alarm activation will flash, and the zone lights of all subsequently opened zones (if any) will illuminate. To return to the random sequence display press * again.
The CHIME Facility
When the system is unset it is possible to set one or more zones to Chime. When a zone is set to Chime the control panel will sound a tone whenever the zone is entered. INS046-8 5
User Guide To Program the Zones which CHIME To program the zones which will chime, enter your 4 digit code The Unset light will flash. Press +. The display will illuminate the zones that will Chime. Press the appropriate numbered button(s) ! of the individual zone(s) to be included or excluded. Press ) to turn Chime on (the system will sound the chime tone) or press * to turn Chime off (the system will sound an error tone).
To Turn CHIME On or Off To turn Chime on or off press +. The system will sound the chime tone when Chime is turned on and an error tone when Chime is turned off.
If no zones have been programmed to Chime then turning Chime on and off will have no effect.
To Test the Sounders and Strobe
The control panel has a test facility to check the operation of the internal sounder, the external sounder and strobe. Enter your 4 digit code !!!!. The Unset light will flash. Press ). All the zone lights will illuminate. Enter ,-. All the zone lights will turn off. The system outputs may be tested as follows: Key System Output Internal sounder at high level (alarm level) Internal sounder at low level (entry/exit level) Strobe External sounder (bell) Turns off all of the above
& % $ # ,
The zone light corresponding to the number pressed will illuminate.
Press *. All the zone lights will illuminate. Press * again. The system will return to unset and all the zone lights will turn off.
To Display Log Events
The control panel is capable of recalling the last 7 alarm activations. The zone light of the zone which first caused the alarm activation will flash, and the zone lights of all subsequently opened zones (if any) will illuminate. 6 INS046-8
User Guide Enter your 4 digit code !!!!. Press ). All the zone lights will illuminate. Press & followed by the number corresponding to the desired event, # being most recent, / being least recent (e.g. to recall the second most recent event enter &$). On completion press *, all the zone lights will illuminate. Press * again. The system will return to unset and all the zone lights will turn off.
To Walk Test the System
The control panel has a Walk Test facility to check the operation of the system's detection devices. Enter your 4 digit code !!!!. The Unset light will flash. Press ). All the zone lights will illuminate. Enter ,. Initially all the zone lights will turn off and the control panel will sound the quiet exit tone. When any zone is opened the control panel will illuminate the corresponding zone light. The control panel will in addition sound a repeating series of bleeps corresponding to the open zone number (i.e. Zone 1 bleeps once, Zone 2 bleeps twice, etc.). If more than one zone is open the bleeps will correspond to the highest zone number (e.g. if Zone 2 and Zone 6 are open the control panel will bleep 6 times). Conduct a walk test by triggering each of the systems detection devices in turn and check that the control panel registers the corresponding zone as open. To terminate Walk Test press *. All the zone lights will illuminate. Press * again. The system will return to unset and all the zone lights will turn off.
To Change Your Code
Before changing your code, it is vital that you memorise or write down the new code you are about to program. Failure to remember your new code will require an engineer visit to re-program a new code for you. This may incur a call-out charge.
Enter your existing 4 digit code !!!!. The Unset light will flash. Press ). All the zone lights will illuminate. Enter.,. All the zone lights will turn off. Enter your new 4 digit code !!!!. Zone lights 1, 2, 3 and 4 will illuminate in turn as each digit of the new code is entered. Press ). The system will chime to confirm the new code has been accepted and all the zone lights will illuminate. Press *. The system will return to unset and all the zone lights will turn off.
If Your System is Due for Maintenance
The system has a service timer which may be programmed by the installer to give a reminder when maintenance is due. The reminder may be either turning Chime on or preventing the system from being set. Chime may be turned off as previously described. In either case contact your installer. INS046-8 7
Installation Details
Installation Engineer: Installation Company: Address:
Telephone: Installation Date: Zone Allocation Zone 7 8
Tick Zones Included in Full & Part Sets
Full Set
Part Set 1
Part Set 2
Part Set 3
Part Set 4
Area Protected
Service Record System Due for Maintenance System Serviced Servicing Engineer
Anti-Code Phone Number
If Required

THANK YOU FOR VOTING TEXECOM
INSTALLATION MANUAL
Security Control Panel with Communicator Interface
Issue 10
Contents
Veritas R8 Plus & Excel Installation Manual
1. Quick Reference and Factory Settings.. 4
Programming Guide..4 Reference Table...5 Miscellaneous Options..6 The Miscellaneous Selections
2. System Overview.. 7
System Architecture..7
Control Panels...7 Veritas R8 Plus & Excel...7 Remote Keypads...7 Veritas R8 Remote Keypad..7 Veritas Excel Remote Keypad...7
3. Installation... 8
Installation Sequence..8 Control Panel...8
Mounting the Control Panel..8 Wiring the Control Panel...8 Control Panel PCB Layout..9 Connecting AC Mains..10 Connecting Batteries..10
. !! - !$. 21 Miscellaneous Selections Zero.. !!.. 21 Miscellaneous Selections One.. !%.. 21 Miscellaneous Selections Two.. !&.. 22 Miscellaneous Selections Three. !$.. 23 Number of Alarm Activations (Re-arms). !'. 23 Testing the Sounders, Strobe.. !(. 24 Walk Testing.. !) or %". 24 Re-Loading the Factory Settings. !*. 24 Programming the SW+ Output. !#. 25 Configuring Remote Keypads.. !". 25
Programming Zone Types
Programming the Zone Type
. %% - %#. 26. %% - %#.. 27
24 Hour Zone Types... 27
Changing Part Set Zone Types
Installing Remote Keypads..10
Cable Distances...10 Keypad Addressing...10 Configuring the Keypads...10
Zone Connections...11
Magnetic Contacts and Panic Buttons..11 Powered Detectors...12 End Of Line Technology..13
Global System Tamper..14 Speaker Connections...14 Internal Siren(s)..14 Wiring the External Sounder..15
Popular SAB Wiring Diagrams..15
Wiring a Communicator..16
Wiring Example...16
Connecting a Computer..17 PC-Com...17 Commissioning (Initial Power Up)..17 Servicing the System...18 Trouble Shooting...18
4. Programming the Control Panel.. 20
Introduction...20
The Programming Menu Programming With an LCD Keypad..20
.. !! - "#.20
Available LCD Menus...20
&( - &). 28 Programming the Date. &(.. 28 Programming the Time.. &).. 29 Programming the Service Timers &* - &". 29 Programming Service Timer One. &*.. 29 Programming Service Timer Two. &#.. 29 Programming Service Timer Three. &".. 29 Programming System Timers. $% - $". 30 The Seven Event Basic Log. '! - '*. 30 Clearing the Seven Event Basic Log. '!.. 30 Displaying the Seven Event Basic Log '% - '*.. 30 Programming the Suites. '# - (". 31 Programming the Zone Disable Suite. '#.. 31 Programming the Zone Soak Test Suite. '".. 31 Programming the Full Set Suite. (!.. 31 Programming the Part Set Suites. (% - ('.. 31 Programming the Chime Suite.. ((.. 32 Programming the Cleaner Suite. ().. 32 Programming the Double Knock Suite. (*.. 32 Programming the Manual Omit Suite.. (#.. 32 Programming the Zone Invert Suite. (".. 32
Programming the Date and Time INS045
. &! - &$. 27 Programming Part Sets Zone Changes. &!.. 28 Changing Zones to Entry/Exit. &%.. 28 Changing Zones to Inhibited Entry. &&.. 28 Changing Zones to Guard.. &$.. 28
Veritas R8 Plus & Excel Installation Manual Assigning Access Codes. )!
- *". 33
1. 2. 3.
Quick Reference and Factory Settings System Overview Installation
Installing Remote Keypads Zone Connections External Sounder Connections Commissioning & Troubleshooting
User Number...33 Access Code...33 Access Level...33 Access Types...34 Changing Your Own Access Code Assigning New Access Codes
. )!.34. )% - *#.34
)% - )#.34 Programming Access Levels. *% - *#.34 Displaying User Information. )" & *".35 Displaying Your User Number.. )".35 Displaying Your Access Level.. *".35 The Communicator Interface.. #! - #%. 35 Programming Communicator Selections. #!.35 Testing the Communicator Interface. #%.36
Programming Access Codes.
The 250 Event Extended Log
Viewing the Extended Log
.. !". 36.. !".36
Programming the Control Panel
Miscellaneous Options System Tests and Utilities Programming Zones Part Set Zone Changes Time/Date/Service Timers System Timers Viewing The Alarm Log Zone Suites Full and Part Set Suites Programming Access Codes Communicator Options Programming Text
Event Log Descriptions...36
Programming Text
.. !# - !!. 37. !#.37 Programming User Name Text.. !$.37 Banner Text. !%.37 Broadcast Text.. !&.37 Default Text. !!.37
Programming Zone Text
!! - !" !# - !$ %% - %& '! - '( '# - '$ (% - ($ "! - ") "& - #$ #! - #" *! - )$ &! - &% $# - $$
5. Specifications... 38
Control Panel... 38
Power supply...38 Electrical....38 Physical...38 Environmental...38
Keypads.. 38 Safety Notes... 38 Warranty... 38 European Standards.. 39
EN 50131...39
6. Installation Records.. 40
Installation Details.. 40
Maintenance & Call-Out Record..40 Access Code Table...41 Notes....42
7. Registered Installer Application Form. 43
INS045
Specifications Installation Records
Quick Reference and Factory Settings
1. Quick Reference and Factory Settings
Programming Guide
Programming Option
Miscellaneous Selections Zero Miscellaneous Selections One Miscellaneous Selections Two Miscellaneous Selections Three Number of Alarm Activations Test Sounders, Strobe, SW+ Walk Test (Non-Latching) Re-Load Factory Settings Switched Positive Output Configure Remote Keypads Detector Programmable Features Zone 1 Zone Type Zone 2 Zone Type Zone 3 Zone Type Zone 4 Zone Type Zone 5 Zone Type Zone 6 Zone Type Zone 7 Zone Type Zone 8 Zone Type Walk Test (Latching) Part Sets Which Change Zone Types Change into Entry/Exit Suite Change into Inhibited Entry Suite Change into Guard Suite Program Current Date Program Current Time Program Service Timer 1 Date Program Service Timer 2 Date Program Service Timer 3 Date Full Set Exit Time (sec) Part Set Exit Time (sec) Full Set Entry Time (sec) Part Set Entry Time (sec) Bell Cut-Off Time (min) Error Tone Suspension Time (sec) Bell Delay Time (min) Confirmation Time (min) Zone Soak Test Time (days) Clear Seven Event Basic Log Basic Log Event 1 (most recent) Basic Log Event 2 Basic Log Event 3 Basic Log Event 4 Basic Log Event 5 Basic Log Event 6 Basic Log Event 7 (least recent)
Option Code
Programming Procedure
Factory Setting
!!+ !%+ !&+ !$+ !'+ !(+ !)+ !*+ !#+ !"+ %!+ %%+ %&+ %$+ %'+ %(+ %)+ %*+ %#+ %"+ &!+ &%+ &&+ &$+ &(+ &)+ &*+ &#+ &"+ $%+ $&+ $$+ $'+ $(+ $)+ $*+ $#+ $"+ '!+ '%+ '&+ '$+ ''+ '(+ ')+ '*+
% # , % to # Press , Select/De-select Option Number(s) % to # Press , Select/De-select Option Number(s) % to # Press , Enter Number of Alarm Activations -- Press , Press ('$&% in Turn Press. Conduct Walk Test Press. Press , Select Function % to # Press , View Display Press , Select Feature Set ! to " Press , Select Zone Type % to # Press , Select Zone Type % to # Press , Select Zone Type % to # Press , Select Zone Type % to # Press , Select Zone Type % to # Press , Select Zone Type % to # Press , Select Zone Type % to # Press , Select Zone Type % to # Press , Conduct Walk Test Press. Select Part Set(s) % to ' Press , Select Zone Number(s) % to # Press , Select Zone Number(s) % to # Press , Select Zone Number(s) % to # Press , Enter Date DD/MM/YY Press , Enter Time HH:MM:SS Press , Enter Date DD/MM/YY Press , Enter Date DD/MM/YY Press , Enter Date DD/MM/YY Press , Enter Exit Time -- Press , Enter Exit Time -- Press , Enter Entry Time -- Press , Enter Entry Time -- Press , Enter Cut-Off Time -- Press , Enter Suspension Time -- Press , Enter Delay Time -- Press , Enter Second Intruder Time -- Press , Enter Soak Test Time -- Press , Press , View Display (Press / for Extended Display) Press. View Display (Press / for Extended Display) Press. View Display (Press / for Extended Display) Press. View Display (Press / for Extended Display) Press. View Display (Press / for Extended Display) Press. View Display (Press / for Extended Display) Press. View Display (Press / for Extended Display) Press.
Select/De-select Option Number(s) Select/De-select Option Number(s) to Press
Set +Ve with Reset (6) None (0) Entry/Exit (6) Inhibited Entry (2) Guard (3) Guard (3) Guard (3) Guard (3) Guard (3) Guard (3)
Parts Sets 1 & 3 Zone 2 Included No Zones Included Zone 1 Included
30 sec 30 sec 30 sec 30 sec 15 min 10 sec 00 (Instant Bells) 45 min 14 days
Zone Disable Suite Zone Soak Test Suite Full Set Suite Part Set Suite 1 Part Set Suite 2 Part Set Suite 3 Part Set Suite 4 Chime Suite Cleaner Suite Double Knock Suite Manual Omit Suite Zone Invert Suite Program Your Own Code PIN Program Code 1 PIN Program Code 2 PIN Program Code 3 PIN Program Code 4 PIN Program Code 5 PIN Program Code 6 PIN Program Code 7 PIN Program Code 8 PIN Display Your Own User Number Display Panel Type Program Code 1 Access Level Program Code 2 Access Level Program Code 3 Access Level Program Code 4 Access Level Program Code 5 Access Level Program Code 6 Access Level Program Code 7 Access Level Program Code 8 Access Level Display Your Own Access Level Communicator Interface Selections Test Communicator Interface
Programming Procedure Factory Setting
No Zones Included No Zones Included All Zones Included Zones 5, 6, 7 Omitted Zones 5, 6, 7 Omitted Zones 5, 6, 7 Omitted Zones 5, 6, 7 Omitted No Zones Included No Zones Included No Zones Included Zone 1 Omitted No Zones Included
'#+ '"+ (!+ (%+ (&+ ($+ ('+ ((+ ()+ (*+ (#+ ("+ )!+ )%+ )&+ )$+ )'+ )(+ ))+ )*+ )#+ )"+ *!+ *%+ *&+ *$+ *'+ *(+ *)+ **+ *#+ *"+ #!+ #%+
% # , % to # Press , Select Zone Number(s) % to # Press , Select Zone Number(s) % to # Press , Select Zone Number(s) % to # Press , Select Zone Number(s) % to # Press , Select Zone Number(s) % to # Press , Select Zone Number(s) % to # Press , Select Zone Number(s) % to # Press , Select Zone Number(s) % to # Press , Select Zone Number(s) % to # Press , Select Zone Number(s) % to # Press , Enter New Code PIN ---- Press , Enter New Code PIN ---- Press , Enter New Code PIN ---- Press , Enter New Code PIN ---- Press , Enter New Code PIN ---- Press , Enter New Code PIN ---- Press , Enter New Code PIN ---- Press , Enter New Code PIN ---- Press , Enter New Code PIN ---- Press , View Display Press. View Display Press. Select Access Level % to # Press , Select Access Level % to # Press , Select Access Level % to # Press , Select Access Level % to # Press , Select Access Level % to # Press , Select Access Level % to # Press , Select Access Level % to # Press , Select Access Level % to # Press , View Display Press. Select/De-select Option Number(s) % to # Press , Toggle Channel(s) % to # Press.
Select Zone Number(s) Select Zone Number(s) to Press
'$&%+ %&$'+
Z1, Z2, Z3 On Master User (5) Boss Engineer (8) Null (7) Null (7) Null (7) Null (7) Null (7) Null (7)
Reference Table
Number 8 All Off Bell Strobe Sounder Lo Sounder Hi SW+ Engineer Hold Off Test Outputs !( SW= Function !# Set +Ve Alarm +Ve & Reset Reset Tamper Mains Fail Set +Ve & Reset Walk Test Entry/Exit Zone Types %Push To Set Inhibit Entry Guard Fire Tamper Entry/Exit PA Keyswitch Extended Display Bell & Global Tamper Power Lid Tamper (inc. RKP) RKP Off-Line Code PIN Tamper Keypad PA
Miscellaneous Options
Option Option Option Option Option Miscellaneous Selections Zero !! Cancel Strobe with Bell Keypad PA (pressing and together causes PA alarm) Single Button Setting Silent Part Set Confirmation Tone EN 50131-1 Requirements Time Limit Engineer Access Reset Button Cancels Setting Automatically Omit a Mains Fail Condition (Auto-Omit AC Off) Factory Setting Off On On Off Off Off On Off Factory Setting On On On Off Off Off Off On Factory Setting Off Off Off Off Off Off On Off Factory Setting Off Off Off Off Off Off Off Off Factory Setting On Off Off Off Off Off Off On
"
Miscellaneous Selections One !% Internal Sounders Only on Unset Tamper Alarm Internal Sounders Only on Part Set Zone Alarm Internal Sounders Only on Part Set Tamper Alarm Silent Part Set (no exit tone on part set) High Level Chime (chime at full volume) Invert Bell Output (negative removed instead of negative applied, useful for SCBs) Final Door Set (system sets 3 seconds after final door closure) Unlock Engineer Code (re-loading factory settings restores default Engineer code) Miscellaneous Selections Two !& Engineer Reset on Any Alarm (see page 22) Engineer Reset on Tamper Alarm (see page 22) Disable User Ability to Omit Tamper Code PIN Tamper (tamper alarm after 16 invalid key presses when unset) Random Number Remote Reset (RNRR, see page 22) Push To Set (see page 23) Strobe Flash on Full Set (see page 22) Invert Switched Positive Output (off = negative removed, on = negative applied) Miscellaneous Selections Three !$ Mains Frequency (off = 50Hz, on = 60Hz) EOL Tamper Alarm on Zone Short Circuit (S/C) EOL Tamper Alarm on Zone Open Circuit (O/C) Enable DD 243:2002 Options (see page 23) Enable Confirmation Signal After Entry Time Out Operation of a Keyswitch Zone is Momentary (Momentary KEYSW) Automatically Omit Zone on Alarm Automatically Omit Keyswitch Zone when EOL Tampered Communicator Selections #! Communicator Outputs Latch until System is Reset Line Monitor Input causes Tamper Alarm on Line Cut Invert Communicator Outputs (off = active low, on = active high) Invert Remote Reset Input (off = active if negative removed, on = active if negative applied) Remote Reset Input Silences Internal Sounder during Alarm Remote Reset Input Clears Engineer Reset (see page 22) Silent PA Enable 90 Second Abort Time Limit
3. Installing the Keypads
Mount and connect the keypads to the control panel (see page 10 for wiring details).
Mains cabling must be secured (e.g. with a cable tie) to one of the anchor points provided. Wiring the Control Panel
4. Installing the Alarm Detection Devices
Install the detection devices, PIRs, Contacts, PA Buttons etc. and connect them to the control panel (see page 11).
5. Install the External Sounder
Install the external sounder and connect to the control panel (see page 15).
BEFORE connecting the control panel ALWAYS disconnect the supply at the consumer unit. If in ANY doubt consult a qualified electrician.
WARNING: ELECTRICITY CAN KILL
6. Other Wiring
Complete all other wiring including speakers and output connections etc. (see pages 14 - 16 for wiring details).
7. Applying Power to the Control Panel
Once steps 1 to 6 are completed, power can be applied to the control panel.
ONLY connect the mains supply to the mains terminal block, NEVER connect the mains supply directly to the PCB.
ALWAYS refer to National Wiring Regulations when conducting installation. An appropriate and readily accessible disconnection device (e.g. an unswitched fused spur) MUST be provided as part of the installation. The disconnection device must NOT be fitted in a flexible cord. Where identification of the neutral in the mains supply is NOT possible a two-pole disconnection device MUST be used. The building mains supply MUST incorporate appropriate short-circuit backup protection (e.g. a fuse or circuit breaker) of High Breaking Capacity (HBC, at least 1500A). Use mains cable of adequate carrying capacity for the rated current (i.e. at least 0.75mm2).
If you need to load the factory default settings (see page 17).
Power should always be connected in the following order: Connect the red battery lead to the positive terminal of the battery and then connect the black battery lead to the negative terminal. Connect the AC mains.
8. Programming the Control Panel
Please refer to section 4 for instruction on programming the control panel.
9. Testing the System
Test the system thoroughly to ensure that all features and functions operate as required (see page 24).
Veritas R8 Plus & Excel Installation Manual Control Panel PCB Layout
Box Tamper
Battery
Power Supply Bell & Strobe
Aux & Speaker
Remote Keypad
Tamp Bell +12V
1: AC Input Connected to the 16.5V transformer.
DO NOT CONNECT THE MAINS SUPPLY TO THE AC INPUT TERMINALS ON THE PCB.
10: Com1 A portable Engineers keypad or a computer (using a PC-Com) can be plugged on here to make programming and testing the system easier.
2: Battery Connections A 12V rechargeable battery must be connected to these terminals in order to provide continuous system operation in the event of an AC Mains failure (see page10). 3: External Sounder Connections These terminals are used for connecting to an external sounder unit (see page 11 for wiring details). 4: Loudspeaker Connections These terminals can be used for connecting up to one 16 or two 8 loudspeakers (see page 14). 5: Auxiliary 12V Connections These terminals are for connecting devices that require 12V power (protected by a 1A fuse F1). 6: SW+ Connections These terminals are for connecting devices that require 12V power (protected by a 1A fuse F1). 7: Auxiliary Tamper Connections These terminals can be used for monitoring the box tamper of auxiliary devices such as power supplies etc. (see page 14). 8: Keypad Network Connections These terminals provide connection for the keypads. The + and terminals provide power whilst the T transmits data and R receives data (see page 10). 9: Programmable Zones 1 - 8 These terminals provide the connections for the 8 zones (see page 11). Each zone is also fully programmable (see page 26).
When using a keypad as an Engineers keypad, the keypads address must all be set to 6 (see page 10).
11: Low Volume Control This variable resistor controls the volume level of advisory (entry/exit) tones (turn anticlockwise to increase volume). 12: Communicator Interface These terminals provide UNFUSED 12V power; a remote reset input, a line fault input and 8 low current (100mA -ve applied) outputs and would normally be used when connecting a stand-alone communicator to the control panel (see page 16). 13: Power Indicator This LED will be ON when AC mains is present on the control panel and will flash when there is no AC mains present on the control panel. 14: Box Tamper Switch This switch provides tamper protection for the main control panel in case of unauthorised access. To disable the box tamper, fit a jumper link across the box tamper pins (if fitted). F1 - F5: Protection Fuses The following fuses are provided:
Fuse F1 F2 F3 F4 F5 Description Battery Bell and Strobe Auxiliary 12V and Speaker Keypad Network Power Supply Rating 1 Amp 1 Amp 500mA 500mA 1.6 Amp
Installation Connecting AC Mains The AC Mains supply is connected to a 3 way Euro Type fused terminal block, which is fitted with a fuse (see page 38).
Veritas R8 Plus & Excel Installation Manual Cable Distances The maximum recommended distance for devices when using standard 7/0.2 alarm cable is:
All other wiring MUST be carried out before AC mains is connected to the control panel.
Figure 6c - Citadel Defender.
Wiring a Communicator
The control panel has eight outputs, which can be used for connecting to a stand-alone communicator. The table below shows the characteristics for each output:
Terminal Type Fire PA Intruder Set/Unset Abort Zone Lockout Duress Confirmed Line Monitor Remote Reset Current 100mA 100mA 100mA 100mA 100mA 100mA 100mA 100mA N/A N/A Operation Switched 0V Switched 0V Switched 0V Switched 0V Switched 0V Switched 0V Switched 0V Switched 0V 0V removed = Fault 0V applied to reset
Figure 6d - Volumatic Flashguard.
L/M R/R
The operation of ALL outputs can be inverted if required (see page 35).
It is NOT possible to invert the individually outputs. Following an alarm, the Zone Lockout output will activate at the end of the 2nd Intruder time if any zone remains open.
Figure 6e - Gardtech Novagard 2.
Do not use non-latching communicator outputs if selecting Automatic Omit (see page 23). The operation of the R/R input may be inverted from 0V to reset to 12V to reset if required (see page 35). The L/M input should be connected to 0V (AUX-) if not required, otherwise Bell Delay will not operate. Wiring Example The diagram below shows a typical wiring example:
Channel Inputs Programmed as Positive Removed
Power 12V 0V
Figure 6f - Activeguard AU101.
Stand Alone Communicator
Line Fault C
DC+ DC-
Figure 6g - CQR Integra HS.
Communicator Interface
For details on testing the communicator outputs, see page 36. INS045
Connecting a Computer
The Veritas R8 Plus and Veritas Excel both support local uploading and downloading between the control panel and a PC running Veritas UDL software. Uploading and Downloading can be used to program and interrogate the control panel.
Enter the factory set User code tone will stop.
'$&%. The error
Enter the factory set Engineer code %&$' and press , to access the Programming Menu and disable 24 Hour zones (Fire, PA and Tamper) via the Engineer code. All the zone lights will illuminate. Perform a Walk Test as described in on page 24. Remember that some powered detectors (e.g. PIRs and Combined Technology Detectors) take several minutes to warm up and become operational. Test the internal sounder, external sounder and strobe as described on page 24. To adjust the low-level volume use the control 'pot' on the PCB (see page 9), volume increases anti-clockwise. If the system fails to operate as expected check that the mounting and wiring are as per the instructions. Correct any mistakes and repeat the test (see page 18, Trouble Shooting). Replace the lid and secure with the two lid screws supplied - do not over-tighten. Fit the screw covers, these can be found in the spares bag. Press. to leave the Programming Menu. All the zone lights will turn off. The Power light will be flashing to indicate that action is required. Switch on the mains supply to the control panel. The Power light will stop flashing and stay on continuously. If the factory settings (see page 4) are not appropriate then re-program the system as described on see page 20. If you have a meter:
Bat ter y
In order to upload and download to the control panel locally, a PC-Com lead is required.
Box Tamp er
JP1 SW1
Pow er
Pow e r Supply Bell & St robe
Au x & Spe ak er
Rem ote Key pad
A.C. Ba tt
Ta mp Be ll +12 V
PC-Com
In order to connect a computer to the control panel, a PCCom lead is required. The PC-Com has a plug at either end of the cable. The 9-way D-type connector is for connection to a serial port on a computer and the 5-way Molex connector is plugged onto Com 1 on the control panel.
Disconnect the battery & check the total non-alarm current is less than 1A. Reconnect the battery & check the total alarm current is not more than 1A. Set your meter to DC current. Connect your meter across F5 (power supply fuse). Remove F5. Record the current drain. Replace F5. Remove your meter. To avoid accidentally powering down the system be sure to follow all the above steps in order.
Commissioning (Initial Power Up)
The total current is measured as follows:
ALWAYS Ensure the mains is off BEFORE removing the front cover
Connect the black battery lead to the negative (-) terminal of the standby battery and the red battery lead to the positive (+) terminal of the standby battery. All the indicator lights will come on. After 10 seconds the zone lights will turn off and a repeating 9 bleep error tone will start.
To Load Factory Settings
Apply power to the control panel and press. OR press and release the lid tamper spring 3 times BEFORE the zone lights turn off and the repeating 9 bleep error tone starts
Installation is now complete and the system is ready for use.
If the battery is flat or faulty the RKP may not accept key presses.
When the system is full set, after the exit period, the external strobe will flash for approximately 6 seconds (this option can be de-selected, see page 22).
Servicing the System
No Power to the Unit (Battery Only)
Check the battery fuse F1 and replace if blown. Check for any loose wires at the BATT terminals on the PCB. Check that the battery wires are connected correctly; red from BATT+ to the battery positive (+), black from BATT- to the battery negative (-).
The light on panel -, Power the batterythe controlcircuit, a is a status indicator for charging steady light meaning normal. A flashing light means action required - mains power can still be present. ALWAYS use a suitable mains test instrument to confirm that mains power is no longer present. The transformer and heatsink may be hot during and after use - do NOT touch.
Miscellaneous Selections Two
!&
From the Programming Menu, enter !&. The display will show the options currently selected.
/$'+3(:8%'(1(((; :8%'3(M(333333O3
If RNRR (sometimes called Anti-Code Reset or Scramble Reset) is enabled and an Engineer Reset is required, a random 4-digit number will be displayed.
Press ,. The system will chime to confirm the new options have been accepted. The system will then automatically revert to the Programming Menu.
Option Miscellaneous Selections Two Engineer Reset on Any Alarm Engineer Reset on Tamper Alarm Disable User Ability to Omit Tamper Code PIN Tamper Random Number Remote Reset Push To Set Strobe Flash on Full Set Invert Switched Positive Output Default Off Off Off Off Off Off On Off
LED Keypad - Each digit will flash in turn and then pause before repeating.
LCD Keypad - A 4-digit number is displayed. Texecoms Anti-Code software will accept this sequence to generate a 4-digit code, which should be entered, after which the system can be reset as normal. Anti-Code software is available from Texecom. The user can press. to toggle between the RNRR and the alarm display. The User Guide has a section to fill in the phone number(s) where the user may obtain the AntiCode. Random Number Remote Reset satisfies the requirements of NACP 10, Issue 2, Section 11.2b.
Option 1 - Engineer Reset on Any Alarm When ON the user is prevented from resetting the system after an alarm activation. 22
Veritas R8 Plus & Excel Installation Manual Option 6 - Push To Set The user starts full set in the usual way and leaves the premises. However the system will ONLY set when an external push button is pressed.
Programming the Control Panel Option 4 - Enable DD 243:2002 Options When ON Opening the initial entry door disables ALL means of confirmation through out the protected premises. When the Confirmation timer expires, the Intruder Alarm output will restore, the next detector to activate will then cause the Intruder Alarm output to re-activate and the Confirmation Timer to restart. When the DD 243:2002 option is enabled, owing to the ability to disable ALL of the confirmation facilities, the customer should be advised in writing by the alarm company that ALL means of confirmation are disabled when the initial entry door is opened. The alarm company should then obtain written acceptance from the customer of the disabling of the means of confirmation. Option 5 - Enable Confirmation After Entry Time Out When ON confirmation is ONLY disabled for the duration of the Entry Time and is RE-ENABLED once the Entry Time has expired, after which activation of a further two zones must occur before the Confirmation output will activate.
Push To Set
Push to Set is intended to reduce false alarms due to user error when full setting the system. The user starts full set in the usual way and leaves the premises. However the system will ONLY set when an external push button is pressed. The Zone Type of the zone to which the external push button is connected must be programmed as Push to Set.
Entry/Exit
Opening a zone with this Zone Type when the system is set will cause the control panel to start entry mode. This Zone Type would typically be used for a front door magnetic contact or, if one is not fitted, a hall PIR.
The Push to Set option must also be selected (see page 22).
The Final Door Set option (see page 21) will cause the exit time to be reduced to 3 seconds when an Entry/Exit zone is closed during exit mode. This option would typically be used only when there is a magnetic contact on the front door.
If a normally open (N/O) push button is used then the zone should be inverted (see page 32) so that it chimes when the button is pressed rather than when it is released. If the zone is set to chime (see User Guide) then the push button can double up as a doorbell. The external push button should be waterproof unless it is located in an enclosed porch. Push to Set does not operate in part set. Push to Set satisfies the requirements of NACP 14, Issue 1, Section 2.1.2.
Personal Attack
This Zone Type is designed specifically for panic buttons. Zones with this Zone Type are monitored constantly even when the panel is unset. If activated, they will cause an immediate alarm, sounding both the internal and external sounders.
The Silent PA option (see page 35) will modify this Zone Type to have a silent response (just activation of the PA channel on the communicator interface with no local audible or visible alarm response at all).
Keyswitch
This Zone Type is designed specifically for key switches. Zones with this Zone Type are monitored constantly. The key switch can be used to full set, unset, silence an alarm and reset the system.
Inhibited Entry
Inhibited Entry is sometimes referred to as 'Intermediate Entry' or 'Walk Through'. Opening a zone with this Zone Type when the panel is set will cause an alarm. During entry mode, activations of a zone with this Zone Type are disregarded. This Zone Type would typically be used for a hall PIR when there is a magnetic contact on the front door.
The Zone Type of any zone can be made to change when the system is part set. The Zone Type can be changed into either Entry/Exit, Inhibited Entry or Guard. It is also possible to program which part set(s) will cause the Zone Type to change. The change will persist until the system is next unset. For example, the tables below show the factory settings:
Part Setting Changes Zone Type Into: Zone Zone Type Entry/Exit Inhibited Entry Guard
If EN 50131-1 Requirements is selected (see page 21) then omitted zones will be re-included when the system is next unset.
When wiring a 24 Hour zone (Fire, PA and Tamper), such as a panic button, using EOL operation it may be more convenient to fit the EOL resistor(s) in the panel than in the detector. Programming the Zone Type
%% - %#
Each of the eight Zone Types has an associated Zone Type number which is used when programming the Zone Type of a zone:
Zone Type Number Zone Type Push to Set Inhibited Entry Guard Fire Tamper Entry/Exit Personal Attack (Panic) Keyswitch
Entry/Exit Inhibited Entry Guard Guard Guard Guard Guard Guard
&%
&&
&$
Zone 1 will change (from Entry/Exit) into Guard and Zone 2 will change (from Inhibited Entry) into Entry/Exit.
Part Set Number Part Set 1 Part Set 2 Part Set 3 Part Set 4
&!
Zone Type Changes For Part Set
From the Programming Menu, press % followed by the zone number. The Zone Type currently selected will indicate i.e. Guard.
These changes will occur when using Part Sets 1 and 3 but not when using Part Sets 2 and 4.
B02(B59"(0(((((; M)9%#DY)*$%
Press the Zone Type number required. Press ,. The system will chime to confirm the new Zone Type has been accepted. The system will then automatically revert to the Programming Menu.
24 Hour zones (Fire, PA and Tamper), Keyswitch zones and Push to Set zones should be monitored constantly and should NOT be programmed to change when the system is part set.
Programming the Control Panel Programming Part Sets Zone Changes
Changing Zones to Guard
The Control Panel has four part sets. Zone Types will only be changed on selected part sets. For example the Control Panel is factory set with Part Sets 1 and 3 selected. Thus Zone Types will only be changed on Part Set 1 and Part Set 3, not on Part Set 2 or Part Set 4. From the Programming Menu, enter currently selected will indicate.
This suite defines the zones which will be changed into Guard zones on the selected part sets. For example the Control Panel is factory set with Zone 1 included. Thus the Zone Type of Zone 1 will be changed (from Entry/Exit) into Guard on Part Sets 1 and 3. From the Programming Menu, enter are currently included will indicate.
Press the appropriate numbered button(s) of the zone(s) to be included or excluded (omitted). Press ,. The system will chime to confirm that the new Full Set Suite has been accepted. The system will then automatically revert to the Programming Menu. Programming the Part Set Suites
(% - ('
A Part Set Suite defines the zones that will be automatically included and excluded (omitted) when the system is part set. From the Programming Menu, press ( followed by the suite number %, &, $, or ' (e.g. to program Part Set Suite 2, enter (&). The zones currently active in the selected part set will indicate (the omitted zones will remain off).
B59"(G5&R(C"'%(; B59"'(M(33333333
?&#%(G"%(GJ$%"0; B59"'(M(01N]333P
Press the appropriate numbered button(s) of the zone(s) to be included or excluded. Press ,. The system will chime to confirm that the new Zone Soak Test Suite has been accepted. The system will then automatically revert to the Programming Menu.
Press the appropriate numbered button(s) of the zone(s) to be included or excluded (omitted). Press ,. The system will chime to confirm that the new Part Set Suite has been accepted. The system will then automatically revert to the Programming Menu.
Programming the Control Panel Programming the Chime Suite
The Chime Suite defines the zones that will be automatically included and excluded (omitted) when chime is turned on. From the Programming Menu, enter ((. The zones that will chime when chime is turned on will indicate (zones that wont chime will remain off).
A zone should be assigned a double knock attribute when maximum false alarm protection is required. A zone with a double knock attribute must be activated either twice within 10 seconds or once for longer than 10 seconds in order to cause an alarm.
Double knock is not recommended for Entry/Exit zones. Double knock will not operate with Push to Set or Keyswitch zones. Double knock should NOT be used for Fire, Panic, or Tamper zones. Programming the Manual Omit Suite
4E$A"(GJ$%"((((; B59"'(M(33333333
Press the appropriate numbered button(s) of the zone(s) to be included or excluded. Press ,. The system will chime to confirm that the new Chime Suite has been accepted. The system will then automatically revert to the Programming Menu.
B59"(K9Q"#%((((; B59"'(M(33333333
>5J[,"(X95+R(((; B59"'(M(33333333
Press the appropriate numbered button(s) of the zone(s) to be included or excluded. Press ,. The system will chime to confirm that the new Zone Invert Suite has been accepted. The system will then automatically revert to the Programming Menu.
Press the appropriate numbered button(s) of the zone(s) to be included or excluded. Press ,. The system will chime to confirm the new Double Knock Suite has been accepted. The system will automatically revert to the Programming Menu.
Most detectors are normally closed (N/C).
The most common normally open (N/O) sensor is a pressure pad or push to set button.
Assigning Access Codes
)! - *"
The Control Panel allows up to eight users to operate the alarm system, each user is assigned an Access code, Access Level and User Number. The figure below shows an example of users assigned to a typical alarm system:
User Number: 1 Access Code: 4321 Access Level: Master User Access Type: Customer
User Number: 2 Access Code: 1234 Access Level: Boss Engineer Access Type: Installer
User Number: 3 Access Code: 5678 Access Level: User Access Type: Customer
User Number: 8 Access Code: 2580 Access Level: Cleaner Access Type: Customer
User Number Each user is identified by the alarm system as User 1 through to User 8. Access Code Each user has a programmable 4 digit Personal Identification Number (PIN) which the user enters in order to operate the alarm system. Access Level Each user has a programmable Access Level that determines how the alarm system responds and which of the system facilities the user can access. Each Access Level has an associated number (1 8) which is used when programming the Access Level of a user. There are eight possible user Access Levels:
Entering a PA code will cause an immediate alarm, sounding both the internal and external sounders.
Duress
A Duress code behaves exactly as a User code (Level 1) but will in addition activate the Duress channel on the communicator interface to secretly summon assistance.
Master User
A Master User may set, unset, silence an alarm and reset the system. In addition a Master can test the system outputs (see page 24), perform a Walk Test (see page 24) and view the Basic Log (see page 30). A Master User can also assign new Customer Access code and Access Levels.
Cleaner
If the system is full set or part set then a Cleaner code will automatically omit the Cleaner Suite zones (see page 32) without affecting the other zones. In addition pressing a key will NOT cause the system to start entry mode. On leaving the cleaner should enter their Access code and press either 0 or 1. The / key is disabled and the previous set will be restored irrespective of which key was pressed. A cleaner cannot access chime. Nor can they cancel an alarm or reset the system.
Tags
180I-MB5 8240HD Headset H375 Polyphonic 37LG7000 CMT-PX7 All-IN-ONE CMT-E301 32SII 120 IS RA-30 QB5020W GZ-MS100 Keypad Surestep Casio SA-5 ALL-IN-ONE WF-552SPP Magic Server MZ-R500 Dslr-A200K Office 25 P G Reference LE46C550 SC-HT340 NV-MX2000 Chessman PRO ICF-304 MMV-200 Fuel 2100 MP560 RY30000 Motorola H555 Hkts 8 Graph25 Pentax MZ6 LE32C570 GF200 SC-EH600 TTM310 KX-TG7302FX AP-700 DFL-860E LAC-M6500R Sans FM Sennheiser E945 SCH-C280 BP8990S Review Xdvd710 VP-D530I Motorola K1M DVD-SH873 50376 LXD75 Converter DCR-VX2200E NV-RZ10EN 50V720 Receiver QC5010 26PFL5522D-12 DIR-825 Dimension 3 Battlefield 1942 IC-A3 Farfisa Fevs CDA-7876 AX34II USA 850 MYW-8 DVX340 RL41hgps HDC-SD9PC Rogue 650BD CDX-R5810 Brain Bash DAV-C700 STR-LV500 TC7102 MAX PL Romeo GT KV-20FS120 System Chicco 6560 AT-141 AWF5120W DC-202V6 VGN-S380P KDL-26B4050 M198WDP-BZJ TX-L19x10EW Toshiba A110 Client ME102 GPS4100 TTR-8632UCE DXZ715
manuel d'instructions, Guide de l'utilisateur | Manual de instrucciones, Instrucciones de uso | Bedienungsanleitung, Bedienungsanleitung | Manual de Instruções, guia do usuário | инструкция | návod na použitie, Užívateľská príručka, návod k použití | bruksanvisningen | instrukcja, podręcznik użytkownika | kullanım kılavuzu, Kullanım | kézikönyv, használati útmutató | manuale di istruzioni, istruzioni d'uso | handleiding, gebruikershandleiding
Sitemap
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101









